The Meadows Apartments
225 SWANTON RD, Madison, WI 53714 · Dane County
Establishment
- Type
- Pool / recreational water (Swimming Pool)
- Inspected by
- Public Health Madison & Dane County
- License / ID
- 64316-65506
- Official record
- Public Health Madison & Dane County inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 1 | 9 | 0 |
| 2025 | 2 | 5 | 0 |
| 2023 | 1 | 4 | 0 |
| 2022 | 1 | 9 | 0 |
| 2021 | 1 | 0 | 0 |
| 2019 | 1 | 0 | 0 |
| 2018 | 1 | 0 | 0 |
| 2017 | 1 | 0 | 0 |
| 2016 | 1 | 0 | 0 |
| 2015 | 1 | 0 | 0 |
| 2013 | 1 | 0 | 0 |
| 2012 | 1 | 0 | 0 |
Inspections
-
Jul 9, 2026 Routine Inspection · No Reinspection Required
-
Not serious
Action taken: Cleaned during inspection.
Corrected on site
04b - SKIMMERS/GUTTERS CLEANED
Skimmers have debris and are not clean.
Correction: Maintain in a clean condition.
Code ATCP 76.11(2)(b)
-
Not serious
Action taken: Adjusted during inspection
Corrected on site
05a - SKIMMER/MAIN DRAIN RATIO (Pf)
The skimmer to main drain flow ratio is not set correctly.
Correction: Readjust the flow so that on pool with skimmers, only 20% of the flow comes through the main drain and 80% comes through the skimmers.
Code ATCP 76.11(2)(a)
-
Not serious
Action taken: Repaired during inspection
Corrected on site
09a - FLOW METER (P
The flow meter is not functional.
Correction: Repair, replace, or install the flowmeter so an accurate rate of flow can be recorded.
Code ATCP 76.11(5)
-
Not serious
Action taken:
13d - INTERLOCK DEMONSTRATION OF KNOWLEDGE AND DOCUMENTS (P)
Operator cannot provide documentation of interlock system per requirements in ATCP 76.13(1)(c).
Correction: Operator must be able to demostrate knowledge and provide documentation of interlock system.
Code ATCP 76.13(1)(c)
-
Not serious
Action taken:
16d - COMBINED CHLORINE (Pf)
The operator does not have a combined chlorine plan or is not following combined chlorine plan.
Correction: Provide a plan with all components required under ATCP 76.14(5)(e)
Code ATCP 76.14(5)(e)
-
Not serious
Action taken:
20c - WATER TESTING - POOLS (Pf)
The water testing frequency for combined chlorine is not being completed 2x per week and pH and free chlorine tests are missing on some dates.
Correction: Perform water testing in accordance with ATCP 76.18(1)&(3). Test combined chlorine 2x per week. Test pH and free chlorine levels daily.
Code ATCP 76.18(1)&(3)
-
Not serious
Action taken: Signs were ordered during
27d - SIGNAGE - NO DIVING (Pf)
'NO DIVING' is not posted in the pool rules for a pool that is 200 square feet in area or greater without an approved diving well configuration. Staff suspect the signs were stolen.
Correction: Post approved signage with letters at least 4 inches in height.
Code ATCP 76.29(1)(d)
-
Not serious
Action taken:
29a - BASIN CLEANING
Basin has sediment, lint, hair, and debris and is in need of cleaning.
Correction: Keep the basin in a clean and sanitary condition pursuant to ATCP 76.33(1)(a).
Code ATCP 76.33(1)(a)
-
Not serious
Action taken: Repaired during the inspec
Corrected on site
31b - EQUIPMENT NOT LOCATED/INSTALLED/MAINTAINED/ REPAIRED
Railing of one of the pool ladders is loose.
Correction: Properly locate, install, maintain and repair equipment.
Code ATCP 76.33(1)(e)
-
Not serious
Action taken: Cleaned during inspection.
Corrected on site
-
Jun 12, 2025 Re-Inspection · No Reinspection Required
-
Not serious
Other
34f - VGBA COVERS DOCUMENTATION (Pf) - Not Corrected
Main drain cover is overdue for replacement, was due for replacement May 2025.
Correction: Maintain documentation (log, receipts, or affidavits from a pool service company) of VGBA covers for main drain and equalizers on site and available for review during inspection. Documentation shall include the following: 1. Make 2. Model 3. Gallons per minute rating. 4. Life span. 5. Installation date. Replace main drain cover.
Code ATCP 76.38
-
Not serious
Other
-
Jun 11, 2025 Routine Inspection · Reinspection Required
-
Not serious
Action taken: Ordered and waiting to be
26t - BIOHAZARD SAFETY KIT (Pf)
No biohazard safety kit is located at the first aid station or on the premises.
Correction: Provide a biohazard safety kit with the items listed in ATCP 76.27(2)(b) at the first aid station or on the premise. 1. Scoop and spatula. 2. Sanitizing hand wipes. 3. Sanitizing surface wipes. 4. Neoprene gloves. 5. Paper toweling. 6. Biohazard disposal bag at least 24"X24". 7. Twist tie or other effective means to close the bag. 8. Biohazard sorbent. 9. Storage case.
Code ATCP 76.27(2)
-
Not serious
Any of the following conditions or situa
28a - CLOSING CRITERIA (P)
The pool was observed to not be closed under the following condition: the gate to the pool enclosure is not self-closing.
Correction: Ensure that the closing criteria are adhered to under the listed below and post signage indicating closure.
Code ATCP 76.30
-
Not serious
Action taken:
34d - DOOR/GATE (P)
The gate to the pool enclosure is not self-closing.
Correction: Repair the gate immediately so that it is self-closing, latching, lockable, and does not require a key, punch code, or electronic method to exit the pool enclosure.
Code ATCP 76.34(4)
-
Not serious
Other
34f - VGBA COVERS DOCUMENTATION (Pf)
Main drain cover is overdue for replacement, was due for replacement May 2025.
Correction: Maintain documentation (log, receipts, or affidavits from a pool service company) of VGBA covers for main drain and equalizers on site and available for review during inspection. Documentation shall include the following: 1. Make 2. Model 3. Gallons per minute rating. 4. Life span. 5. Installation date. Replace main drain cover.
Code ATCP 76.38
-
Not serious
Action taken: Ordered and waiting to be
-
Jul 21, 2023 Routine Inspection · No Reinspection Required
-
Not serious
Action taken:
05b - WATER LEVEL
The pool water level is not adequate for continuous effective surface skimming.
Correction: Adjust the water level until the skimming of the water surface is adequate.
Code ATCP 76.11(2)(a)
-
Not serious
Action taken:
26p - FIRST AID KIT - AVAILABLE
A first aid kit is not available in the pool area. The first aid kit was being stored in the pump room/garage.
Correction: Provide a first aid kit in the pool area.
Code ATCP 76.27(1)
-
Not serious
Action taken:
26r - BLANKETS MISSING
2 durable blankets are not available in the pool area. The blankets were being stored in the pump room/garage.
Correction: Provide 2 durable blankets in the pool area.
Code ATCP 76.27(1)
-
Not serious
Other
34e - VGBA COVERS
Two of the three equalizer covers are due for replacement. Last year in July one of the equalizer covers was missing and replaced. The other two equalizer covers were installed in May 2018 and were due for replacement in May 2023.
Correction: Maintain documentation of VGBA covers for main drain and equalizers on site and available for review during inspection. Replace covers when lifespan is up.
Code ATCP 76.11(2)(b)
-
Not serious
Action taken:
-
Jul 19, 2022 Routine Inspection · No Reinspection Required
-
Not serious
Action taken:
16b - CYANURIC ACID
The cyanuric acid concentration is 60 ppm.
Correction: Lower the concentration of cyanuric acid to 30 ppm or lower.
Code ATCP 76.14(4)(b)
-
Not serious
Action taken:
20c - WATER TESTING - POOLS
The water testing frequency for pH and free Chlorine is not in compliance with ATCP 76.18(1). These tests are only being done once daily.
Correction: Perform water testing in accordance with ATCP 76.18(1). Test pH and free chlorine two times per day.
Code ATCP 76.18(1)
-
Not serious
Action taken:
26o - EMERGENCY NUMBERS AND ADDRESS
The emergency numbers and/or the facility's location are not posted near the designated emergency phone.
Correction: Post the emergency numbers and the facility's address near the designated emergency phone.
Code ATCP 76.26(2)
-
Not serious
Action taken:
26q - FIRST AID KIT - SUPPLIES MISSING
Instant cold packs, scissors, and eye wash solution are missing from the first aid kit.
Correction: Provide all the items listed in ATCP 76.27(1) in the first aid kit.
Code ATCP 76.27(1)
-
Not serious
Action taken:
29b - BASIN DEFECTS
At the base of the ladder on the pool deck, there is concrete chipping away.
Correction: Repair the pool deck so it is finished and easily cleanable.
Code ATCP 76.33(1)(a)
-
Not serious
Action taken:
29f - DEPTH MARKINGS VISIBLE
The depth markings on the pool deck are faded.
Correction: Repair the markings so they are clearly visible and readable.
Code ATCP 76.33(1)(b)
-
Not serious
Action taken:
31b - EQUIPMENT NOT MAINTAINED
An equalizer cover is missing.
Correction: Repair and maintain all equipment.
Code ATCP 76.33(1)(e)
-
Not serious
Other
34e - VGBA COVERS
No documentation is available on site for VGBA main drain and/or equalizer covers showing make/model, installation, and replacement date.
Correction: Maintain documentation of VGBA covers for main drain and equalizers on site and available for review during inspection. Replace covers when lifespan is up.
Code ATCP 76.11(2)(b)
-
Not serious
Other
41a - MISCELLANEOUS
The leading edge of the steps is the same color as the pool basin.
Correction: Leading edge of all steps shall be distinguished by a color contrasting with the steps and pool floor.
Code 390.12(3)a (11)
-
Not serious
Action taken:
-
Aug 18, 2021 Routine Inspection · No Reinspection Required
No violations cited.
-
Aug 29, 2019 Routine Inspection · No Reinspection Required
No violations cited.
-
Jun 12, 2018 Routine Inspection · No Reinspection Required
No violations cited.
-
Jun 14, 2017 Routine Inspection · No Reinspection Required
No violations cited.
-
Jun 20, 2016 Routine Inspection · No Reinspection Required
No violations cited.
-
Jun 16, 2015 Routine Inspection · No Reinspection Required
No violations cited.
-
Aug 14, 2013 Routine Inspection · No Reinspection Required
No violations cited.
-
Jul 11, 2012 Routine Inspection · No Reinspection Required
No violations cited.
Source: Public Health Madison & Dane County. History last read Nov 2, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.