RecordWell Data

Nakoma Heights

4929 CHALET GARDENS RD, Fitchburg, WI 53711 · Dane County

47cited violations
0serious tier
10inspections

Establishment

Type
Pool / recreational water (Swimming Pool)
Inspected by
Public Health Madison & Dane County
License / ID
LICSWD-2017-00321
Official record
Public Health Madison & Dane County inspection reports

Other public records for this business

Year by year

YearInspectionsViolationsSerious
20262210
20251100
2024160
20231100
2021100
2019100
2018100
2017200

Inspections

  1. Jul 3, 2026 Routine Inspection · No Reinspection Required
    • Not serious Action taken: While pool closed, PIC fed

      13d - INTERLOCK DEMONSTRATION OF KNOWLEDGE AND DOCUMENTS (P)

      Operator cannot demonstrate knowledge and/or provide documentation of interlock system per requirements in ATCP 76.13(1)(c). DATCP's interlock checklist form is onsite but not completed.

      Correction: Operator must be able to demonstrate knowledge and provide documentation of interlock system.

      Code ATCP 76.13(1)(c)

    • Not serious Action taken: Employee purchased ice pac Corrected on site

      26r - FIRST AID KIT - SUPPLIES MISSING (Pf)

      Ice pack is missing from the first aid kit.

      Correction: Provide all the items listed in ATCP 76.27(1)(b) in the first aid kit. 1. Gauze pads. 2. Adhesive bandages. 3. Gauze roller bandage. 4. Adhesive tape. 5. Eye wash. 6. Elastic bandage. 7. Disposable surgical gloves. 8. Resuscitation pocket face mask. 9. Instant cold packs.

      Code ATCP 76.27(1)(b)

    • Not serious Action taken: Employee used sharpie to c Corrected on site

      27b - SIGNAGE - SUPERVISION OF CHILDREN

      Statement indicating that children under the age of 12 shall be supervised by an adult is missing from signage. Signage states children under 4 require supervision.

      Correction: Add statement indicating that children under the age of 12 shall be supervised by an adult to the signage requirements in ATCP 76.29(1))(b).

      Code ATCP 76.29(1)(c)

  2. Jun 16, 2026 Re-Inspection · No Reinspection Required
    • Not serious Action taken:

      04c - SKIMMER BASKET/WEIR - Not Corrected

      The weir is missing at the skimmer closest to the mounted Shepherd's Crook.

      Correction: Replace.

      Code ATCP 76.11(2)(b)

    • Not serious Action taken:

      05a - SKIMMER/MAIN DRAIN RATIO (Pf) - Not Corrected

      The skimmer to main drain flow ratio is not set correctly. All valves appear fully open.

      Correction: Readjust the flow so that on pool with skimmers, only 20% of the flow comes through the main drain and 80% comes through the skimmers. On a gutter pool, 75% of the required recirculation flow shall be through the gutter and 25% through the main drain. For reverse flow pools, 100% recirculation must be through gutter or skimmers.

      Code ATCP 76.11(2)(a)

    • Not serious Action taken: PIC ordered sign online.

      11b - CHEMICAL - STORAGE (P)(Pf) - Not Corrected

      Door to chemical storage area is not marked to indicate entry is for authorized personnel only and list of emergency numbers not provided.

      Correction: Provide signage on chemical storage areas and provide list of emergency numbers.

      Code ATCP 76.12(2)

    • Not serious Action taken: Recommended DATCP training

      13d - INTERLOCK DEMONSTRATION OF KNOWLEDGE AND DOCUMENTS (P) - Not Corrected

      Operator demonstrated some knowledge of interconnectivity between pump and chlorine feeder. No documentation of interlock system testing is available per requirements in ATCP 76.13(1)(c).

      Correction: Operator must be able to demonstrate knowledge and provide documentation of interlock system.

      Code ATCP 76.13(1)(c)

    • Not serious Action taken: The pool was adjusted and Corrected on site

      16a - pH - Not Corrected

      The pH is 8.0 and very pink.

      Correction: Close the pool and do not reopen it until the pH falls between 7.2 and 7.8.

      Code ATCP 76.14(4)(c)

    • Not serious Action taken: PIC printed DATCP's templa

      16d - COMBINED CHLORINE (Pf) - Not Corrected

      The operator does not have a combined chlorine plan.

      Correction: Provide a plan with all components required under ATCP 76.14(5)(e)

      Code ATCP 76.14(5)(e)

    • Not serious Action taken: ORP reader is present in p Repeat

      20c - WATER TESTING - POOLS (Pf) - Not Corrected

      The water testing frequency for all testing is not in compliance with ATCP 76.18(1). Chlorine and pH are consistently tested once per day, twice a day is required for a pool without controllers. Combined chlorine is not tested. Alkalinity was occasionally tested and documented but less than on a weekly basis. Operator is using testing log for pools with controllers when the pool does not have controllers currently set up. Operator informed cyanuric acid was not used in pool this season, therefore, this test is not required.

      Correction: Perform water testing in accordance with ATCP 76.18(1).

      Code ATCP 76.18(1)

    • Not serious Action taken: CPO onsite trained employe Repeat Corrected on site

      20e - WATER TESTING FREQUENCY - ORP - Not Corrected

      The water testing frequency for alkalinity and combined chlorine is not in compliance with ATCP 76.18(3).

      Correction: Perform water testing in accordance with ATCP 76.18(3).

      Code ATCP 76.18(3)

    • Not serious Action taken: PIC worked on connection d Corrected on site

      26m - TELEPHONE - NOT WORKING - Not Corrected

      The emergency telephone does not work. When button pushed, a call did not go through.

      Correction: Provide a functional emergency telephone immediately.

      Code ATCP 76.26(2)

    • Not serious Action taken: PIC completed variance app Corrected on site

      26m - TELEPHONE - NO CONNECTION TO EMERGENCY SERVICES (P) - Not Corrected

      There telephone is a push button phone that connects direct with EMS. The phone was tested during the inspection and connection is loud and clear.

      Correction: Provide a telephone capable of connecting with emergency services at all times during pool operation or apply for a variance.

      Code ATCP 76.26(2)

    • Not serious Action taken: PIC completed variance app

      26m - TELEPHONE - NO CONNECTION TO EMERGENCY SERVICES (P) - Not Corrected

      There telephone is a push button phone that connects direct with EMS. The phone was tested during the inspection and connection is loud and clear. 6/16 RI: Push button emergency phone does not connect to emergency services.

      Correction: Provide a telephone capable of connecting with emergency services at all times during pool operation or apply for a variance.

      Code ATCP 76.26(2)

    • Not serious Action taken:

      26r - FIRST AID KIT - SUPPLIES MISSING (Pf) - Not Corrected

      An ice pack is missing from the first aid kit.

      Correction: Provide all the items listed in ATCP 76.27(1)(b) in the first aid kit. 1. Gauze pads. 2. Adhesive bandages. 3. Gauze roller bandage. 4. Adhesive tape. 5. Eye wash. 6. Elastic bandage. 7. Disposable surgical gloves. 8. Resuscitation pocket face mask. 9. Instant cold packs.

      Code ATCP 76.27(1)(b)

    • Not serious Action taken: PIC ordered first aid kit

      26t - BIOHAZARD SAFETY KIT (Pf) - Not Corrected

      No biohazard safety kit is located at the first aid station or on the premises.

      Correction: Provide a biohazard safety kit with the items listed in ATCP 76.27(2)(b) at the first aid station or on the premise. 1. Scoop and spatula. 2. Sanitizing hand wipes. 3. Sanitizing surface wipes. 4. Neoprene gloves. 5. Paper toweling. 6. Biohazard disposal bag at least 24"X24". 7. Twist tie or other effective means to close the bag. 8. Biohazard sorbent. 9. Storage case.

      Code ATCP 76.27(2)

    • Not serious Action taken: Repair prior to next seaso

      29b - BASIN DEFECTS - Not Corrected

      There is ~3 foot long crack in basin about 10 feet from the staircase entrance.

      Correction: Repair the pool basin so it is finished and easily cleanable.

      Code ATCP 76.33(1)(a)

    • Not serious Action taken: 3. PIC has plans to repair

      31b - EQUIPMENT NOT MAINTAINED - Not Corrected

      1. One of the three railings to enter the pool is wobbly. 2. In the restrooms, hot water is not provided at the hand sinks. 3. In pump room water is leaking along wall main pipes enter from pool.

      Correction: Repair and maintain all equipment.

      Code ATCP 76.33(1)(e)

    • Not serious Action taken:

      31b - EQUIPMENT NOT LOCATED/INSTALLED/MAINTAINED/ REPAIRED - Not Corrected

      In pump room, water observed on floor near skimmer and main drain pipes and wall. Water also observed on valve to filter. On deck, one of three railings by staircase to enter pool wobbles.

      Correction: Properly locate, install, maintain and repair equipment.

      Code ATCP 76.33(1)(e)

    • Not serious Action taken:

      31b - EQUIPMENT NOT LOCATED/INSTALLED/MAINTAINED/ REPAIRED - Not Corrected

      On deck, one of three railings by staircase to enter pool wobbles.

      Correction: Properly locate, install, maintain and repair equipment.

      Code ATCP 76.33(1)(e)

    • Not serious Other Repeat

      41a - MISCELLANEOUS - Not Corrected

      Deck surface, especially the third of the deck nearest to the patron entrance gate has large prominent cracks. At 5 foot mark, concrete has eroded away where the deck meets the edge of the pool leaving sharp edges. On deck, at midway point of pool along fence, there is a ~10 foot long crack about 1" deep.

      Correction: Deck areas shall be maintained in good repair.

      Code ATCP 76.33(1)(b)

  3. Aug 27, 2025 Routine Inspection · Reinspection Required
    • Not serious Action taken:

      04c - SKIMMER BASKET/WEIR

      The weir is missing at the skimmer closest to the mounted Shepherd's Crook.

      Correction: Replace.

      Code ATCP 76.11(2)(b)

    • Not serious Action taken:

      05a - SKIMMER/MAIN DRAIN RATIO (Pf)

      The skimmer to main drain flow ratio is not set correctly. All valves appear fully open.

      Correction: Readjust the flow so that on pool with skimmers, only 20% of the flow comes through the main drain and 80% comes through the skimmers. On a gutter pool, 75% of the required recirculation flow shall be through the gutter and 25% through the main drain. For reverse flow pools, 100% recirculation must be through gutter or skimmers.

      Code ATCP 76.11(2)(a)

    • Not serious Action taken: PIC ordered sign online.

      11b - CHEMICAL - STORAGE (P)(Pf)

      Door to chemical storage area is not marked to indicate entry is for authorized personnel only and list of emergency numbers not provided.

      Correction: Provide signage on chemical storage areas and provide list of emergency numbers.

      Code ATCP 76.12(2)

    • Not serious Action taken: Recommended DATCP training

      13d - INTERLOCK DEMONSTRATION OF KNOWLEDGE AND DOCUMENTS (P)

      Operator demonstrated some knowledge of interconnectivity between pump and chlorine feeder. No documentation of interlock system testing is available per requirements in ATCP 76.13(1)(c).

      Correction: Operator must be able to demonstrate knowledge and provide documentation of interlock system.

      Code ATCP 76.13(1)(c)

    • Not serious Action taken: PIC printed DATCP's templa

      16d - COMBINED CHLORINE (Pf)

      The operator does not have a combined chlorine plan.

      Correction: Provide a plan with all components required under ATCP 76.14(5)(e)

      Code ATCP 76.14(5)(e)

    • Not serious Action taken: ORP reader is present in p Repeat

      20c - WATER TESTING - POOLS (Pf)

      The water testing frequency for all testing is not in compliance with ATCP 76.18(1). Chlorine and pH are consistently tested once per day, twice a day is required for a pool without controllers. Combined chlorine is not tested. Alkalinity was occasionally tested and documented but less than on a weekly basis. Operator is using testing log for pools with controllers when the pool does not have controllers currently set up. Operator informed cyanuric acid was not used in pool this season, therefore, this test is not required.

      Correction: Perform water testing in accordance with ATCP 76.18(1).

      Code ATCP 76.18(1)

    • Not serious Action taken: PIC completed variance app Corrected on site

      26m - TELEPHONE - NO CONNECTION TO EMERGENCY SERVICES (P)

      There telephone is a push button phone that connects direct with EMS. The phone was tested during the inspection and connection is loud and clear.

      Correction: Provide a telephone capable of connecting with emergency services at all times during pool operation or apply for a variance.

      Code ATCP 76.26(2)

    • Not serious Action taken:

      26r - FIRST AID KIT - SUPPLIES MISSING (Pf)

      An ice pack is missing from the first aid kit.

      Correction: Provide all the items listed in ATCP 76.27(1)(b) in the first aid kit. 1. Gauze pads. 2. Adhesive bandages. 3. Gauze roller bandage. 4. Adhesive tape. 5. Eye wash. 6. Elastic bandage. 7. Disposable surgical gloves. 8. Resuscitation pocket face mask. 9. Instant cold packs.

      Code ATCP 76.27(1)(b)

    • Not serious Action taken: PIC ordered first aid kit

      26t - BIOHAZARD SAFETY KIT (Pf)

      No biohazard safety kit is located at the first aid station or on the premises.

      Correction: Provide a biohazard safety kit with the items listed in ATCP 76.27(2)(b) at the first aid station or on the premise. 1. Scoop and spatula. 2. Sanitizing hand wipes. 3. Sanitizing surface wipes. 4. Neoprene gloves. 5. Paper toweling. 6. Biohazard disposal bag at least 24"X24". 7. Twist tie or other effective means to close the bag. 8. Biohazard sorbent. 9. Storage case.

      Code ATCP 76.27(2)

    • Not serious Action taken:

      31b - EQUIPMENT NOT LOCATED/INSTALLED/MAINTAINED/ REPAIRED

      In pump room, water observed on floor near skimmer and main drain pipes and wall. Water also observed on valve to filter. On deck, one of three railings by staircase to enter pool wobbles.

      Correction: Properly locate, install, maintain and repair equipment.

      Code ATCP 76.33(1)(e)

  4. Aug 7, 2024 Routine Inspection · No Reinspection Required
    • Not serious Action taken: The pool was adjusted and Corrected on site

      16a - pH

      The pH is 8.0 and very pink.

      Correction: Close the pool and do not reopen it until the pH falls between 7.2 and 7.8.

      Code ATCP 76.14(4)(c)

    • Not serious Action taken: CPO onsite trained employe Repeat Corrected on site

      20e - WATER TESTING FREQUENCY - ORP

      The water testing frequency for alkalinity and combined chlorine is not in compliance with ATCP 76.18(3).

      Correction: Perform water testing in accordance with ATCP 76.18(3).

      Code ATCP 76.18(3)

    • Not serious Action taken: PIC worked on connection d Corrected on site

      26m - TELEPHONE - NOT WORKING

      The emergency telephone does not work. When button pushed, a call did not go through.

      Correction: Provide a functional emergency telephone immediately.

      Code ATCP 76.26(2)

    • Not serious Action taken: Repair prior to next seaso

      29b - BASIN DEFECTS

      There is ~3 foot long crack in basin about 10 feet from the staircase entrance.

      Correction: Repair the pool basin so it is finished and easily cleanable.

      Code ATCP 76.33(1)(a)

    • Not serious Action taken: 3. PIC has plans to repair

      31b - EQUIPMENT NOT MAINTAINED

      1. One of the three railings to enter the pool is wobbly. 2. In the restrooms, hot water is not provided at the hand sinks. 3. In pump room water is leaking along wall main pipes enter from pool.

      Correction: Repair and maintain all equipment.

      Code ATCP 76.33(1)(e)

    • Not serious Other Repeat

      41a - MISCELLANEOUS

      Deck surface, especially the third of the deck nearest to the patron entrance gate has large prominent cracks. At 5 foot mark, concrete has eroded away where the deck meets the edge of the pool leaving sharp edges. On deck, at midway point of pool along fence, there is a ~10 foot long crack about 1" deep.

      Correction: Deck areas shall be maintained in good repair.

      Code ATCP 76.33(1)(b)

  5. Aug 9, 2023 Routine Inspection · No Reinspection Required
    • Not serious Action taken:

      06a - SPARE STRAINER BASKET

      A spare strainer basket for the recirculation pump is not located on site.

      Correction: Provide a spare basket or screen.

      Code ATCP 76.11(2)(d)

    • Not serious Action taken: Send testing log reports t Repeat

      20c - WATER TESTING - POOLS

      The water testing frequency is not in compliance with ATCP 76.18(1). The pool is tested for pH and Cl only once a day and alkalinity and combined chlorine is not tested.

      Correction: Perform water testing in accordance with ATCP 76.18(1).

      Code ATCP 76.18(1)

    • Not serious Action taken:

      26r - BLANKETS MISSING

      2 durable blankets are not available in the pool area.

      Correction: Provide 2 durable blankets in the pool area.

      Code ATCP 76.27(1)

    • Not serious Action taken:

      26s - BIOHAZARD SAFETY KIT

      No biohazard safety kit is located on the premises.

      Correction: Provide a biohazard safety kit at the first aid station.

      Code ATCP 76.27(2)

    • Not serious Action taken:

      29f - DEPTH MARKINGS VISIBLE

      The depth markings along the edge of the pool are numbers only and do not indicate that they represent feet on the deck and vertical basin wall.

      Correction: Repair the markings so they are clearly visible and readable.

      Code ATCP 76.33(1)(b)

    • Not serious Action taken:

      30a - SHOWER, TOILET AND DRESSING ROOM FACILITIES

      (1) The men and women's restroom facilities are not clean. There is toilet paper/ empty toilet paper rolls on the floor. PIC informed restrooms are cleaned once per week. (2) The soap dispenser in the showers are empty. (3) No hand towels are available in the men and women restroom's hand washing sink.

      Correction: Clean and disinfect the walls, partitions and floors of showers, toilet rooms and dressing areas.

      Code ATCP 76.33(2)

    • Not serious Action taken: 2. Thermometer discarded a

      31b - EQUIPMENT NOT MAINTAINED

      1) The railings by the staircase of the pool are loose and wobbly. 2) Thermometer used to test pool is inaccurate.

      Correction: Repair and maintain all equipment.

      Code ATCP 76.33(1)(e)

    • Not serious Action taken:

      32a - WATER HEATER

      The water heater is not maintaining tempered water in the restrooms. PIC informed water heater is no longer working and requires repair/replacement.

      Correction: Repair the water heater and maintain it in an operating condition.

      Code ATCP 76.33(4)(a)

    • Not serious Other

      34e - VGBA COVERS

      No documentation is available on site for VGBA main drain and/or equalizer covers showing make/model, installation, and replacement date.

      Correction: Maintain documentation of VGBA covers for main drain and equalizers on site and available for review during inspection. Replace covers when lifespan is up.

      Code ATCP 76.11(2)(b)

    • Not serious Other

      41a - MISCELLANEOUS

      Deck surface, especially perimeter surrounding the pool basin is pitting and peeling. At 4 foot mark, concrete has eroded away where the deck meets the edge of the pool. Large cracks are prominent on deck surface.

      Correction: Deck areas shall be maintained in good repair.

      Code ATCP 76.33(1)(b)

  6. Aug 24, 2021 Routine Inspection · No Reinspection Required

    No violations cited.

  7. Aug 28, 2019 Routine Inspection · No Reinspection Required

    No violations cited.

  8. Jun 12, 2018 Routine Inspection · No Reinspection Required

    No violations cited.

  9. Jul 13, 2017 Re-Inspection · No Reinspection Required

    No violations cited.

  10. Jun 23, 2017 Pre-Inspection · Reinspection Required

    No violations cited.

Source: Public Health Madison & Dane County. History last read Nov 2, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.