RecordWell Data

Mainstay Suites

5317 High Crossing BLVD, Madison, WI 53718 · Dane County

49cited violations
0serious tier
20inspections

Establishment

Type
Pool / recreational water (Swimming Pool)
Inspected by
Public Health Madison & Dane County
License / ID
LICSWD-2015-00276
Official record
Public Health Madison & Dane County inspection reports

Other public records for this business

Year by year

YearInspectionsViolationsSerious
2026260
2025120
2024140
20233130
20212240
2019700
2018100
2017100
2016100
2015100

Inspections

  1. Sep 3, 2026 Re-Inspection · No Reinspection Required
    • Not serious Action taken:

      29b - BASIN MAINTENANCE AND REPAIR - Not Corrected

      The pool basin has grout missing between tiles.

      Correction: Maintain the pool basin in a clean, sanitary condition and free from cracks and defects.

      Code ATCP 76.33(1)(a)

  2. Sep 2, 2026 Routine Inspection · Reinspection Required
    • Not serious Action taken:

      13d - INTERLOCK DEMONSTRATION OF KNOWLEDGE AND DOCUMENTS (P)

      Operator cannot provide documentation of interlock system per requirements in ATCP 76.13(1)(c).

      Correction: Operator must be able to demostrate knowledge and provide documentation of interlock system.

      Code ATCP 76.13(1)(c)

    • Not serious Action taken: Whirlpool closed.

      14f - NO DISINFECTANT FEEDER (P)

      The pool is not being automatically and continually disinfected via a disinfectant feeder. The chemical controller has been turned switched to "off"; operator is manually switching the feeder on and off to manually feed disinfectant.

      Correction: The pool must be closed and a disinfectant feeder, approved by the department of commerce, must be installed or repaired before the facility can re-open.

      Code ATCP 76.14(1)

    • Not serious Action taken:

      16d - COMBINED CHLORINE (Pf)

      The operator does not have a combined chlorine plan or is not following combined chlorine plan.

      Correction: Provide a plan with all components required under ATCP 76.14(5)(e)

      Code ATCP 76.14(5)(e)

    • Not serious Any of the following conditions or situa Corrected on site

      28a - CLOSING CRITERIA (P)

      The pool was not closed by the operator or responsible supervisor under the following condition: nonfunctional chemical feeder.

      Correction: Ensure that the closing criteria are adhered to under the listed below and post signage indicating closure.

      Code ATCP 76.30

    • Not serious Action taken:

      29b - BASIN MAINTENANCE AND REPAIR

      The pool basin has grout missing between tiles.

      Correction: Maintain the pool basin in a clean, sanitary condition and free from cracks and defects.

      Code ATCP 76.33(1)(a)

  3. Nov 24, 2025 Routine Inspection · No Reinspection Required
    • Not serious Action taken: Total alkalinity was adjus Corrected on site

      16c - ALKALINITY (Pf)

      The total alkalinity is 30 ppm.

      Correction: Maintain the total alkalinity between 60 and 180 ppm.

      Code ATCP 76.14(5)(d)

    • Not serious Action taken:

      29b - BASIN MAINTENANCE AND REPAIR

      Grout is missing between tiles in the pool basin.

      Correction: Maintain the pool basin in a clean, sanitary condition and free from cracks and defects.

      Code ATCP 76.33(1)(a)

  4. Jul 15, 2024 Routine Inspection · No Reinspection Required
    • Not serious Action taken:

      04c - SKIMMER BASKET/WEIR

      The skimmer weir is missing.

      Correction: Replace the weir or install floating weir.

      Code ATCP 76.11(2)(b)

    • Not serious Action taken:

      20c - WATER TESTING - POOLS

      The water testing log is missing total alkalinity test results.

      Correction: Perform water testing in accordance with ATCP 76.18(1). Test total alkalinity at least once a week.

      Code ATCP 76.18(1)

    • Not serious Action taken:

      29b - BASIN DEFECTS

      The pool basin is missing grout between tiles.

      Correction: Repair the pool basin so it is finished and easily cleanable.

      Code ATCP 76.33(1)(a)

    • Not serious Other

      34e - VGBA COVERS

      The VGBA log indicated the Paramount SDX retro equalizer cover was installed 5/27/2019 and has a 5 year lifespan. This cover was due for replacement 5/27/2024 and has not been replaced yet.

      Correction: Maintain documentation of VGBA covers for main drain and equalizers on site and available for review during inspection. Replace covers when lifespan is up.

      Code ATCP 76.11(2)(b)

  5. Jul 21, 2023 Re-Inspection · No Reinspection Required
    • Not serious Any of the following conditions or situa Corrected on site

      28a - CLOSING CRITERIA - Not Corrected

      The pool was not closed at the time of the routine inspection under the following condition: chlorine too low. The pool was not closed at the time of the first re-inspection under the following conditions: chlorine too high, over 13.0 ppm. The pool was not closed at the time of the second re-inspection under the following conditions: chlorine too low, at 0.4 ppm.

      Correction: Ensure that the closing criteria are adhered to under the listed below.

      Code ATCP 76.30

  6. Jul 19, 2023 Re-Inspection · Reinspection Required
    • Not serious Action taken:

      16c - ALKALINITY - Not Corrected

      The total alkalinity is greater than 300 ppm.

      Correction: Maintain the total alkalinity between 60 and 180 ppm.

      Code ATCP 76.14(4)(d)

    • Not serious Any of the following conditions or situa Corrected on site

      28a - CLOSING CRITERIA - Not Corrected

      The pool was not closed at the time of the routine inspection under the following condition: chlorine too low. The pool was not closed at the time of the re-inspection under the following conditions: chlorine too high.

      Correction: Ensure that the closing criteria are adhered to under the listed below.

      Code ATCP 76.30

  7. Jun 9, 2023 Routine Inspection · Reinspection Required
    • Not serious Action taken:

      04c - SKIMMER BASKET/WEIR

      The skimmer weir door is missing.

      Correction: Replace skimmer weir door or install floating weir.

      Code ATCP 76.11(2)(b)

    • Not serious Action taken: Corrected on site

      05b - WATER LEVEL

      The pool water level is too high and not adequate for continuous effective surface skimming.

      Correction: Adjust the water level until the skimming of the water surface is adequate.

      Code ATCP 76.11(2)(a)

    • Not serious Action taken:

      09a - FLOW METER

      The flow meter is not functional.

      Correction: Repair or replace the flowmeter so an accurate rate of flow can be recorded.

      Code ATCP 76.11(5)

    • Not serious Action taken: Operator closed the pool a Corrected on site

      14a - CHLORINE TOO LOW

      The chlorine residual was 0.4 ppm at the time of the inspection.

      Correction: Maintain chlorine residual at 3.0 ppm - 10.0 ppm.

      Code ATCP 76.14(4)(a)

    • Not serious Action taken:

      16c - ALKALINITY

      The total alkalinity is 220 ppm.

      Correction: Maintain the total alkalinity between 60 and 180 ppm.

      Code ATCP 76.14(4)(d)

    • Not serious Action taken:

      20a - TEST KIT NOT APPROVED

      The test kit used by the facility has not been approved by the department. The reagents are expired and the color comparator is dirty.

      Correction: Replace the test kit with one from the approved list. Provide a new pool test kit.

      Code ATCP 76.17(1)

    • Not serious Action taken:

      20d - WATER TESTING - WHIRLPOOL, THERAPY, EXERCISE

      The water testing frequency for total alkalinity and combined chlorine are not in compliance with ATCP 76.18(1) - (2). Total alkalinity tests are not being completed. Combined chlorine test values on the log are inaccurate and do not reflect testable range values.

      Correction: Perform water testing in accordance with ATCP 76.18(1) - (2). Test total alkalinity at least once weekly. Test combined chlorine daily. Test pH and free chlorine at least once daily.

      Code ATCP 76.18(1) - (2)

    • Not serious Any of the following conditions or situa Corrected on site

      28a - CLOSING CRITERIA

      The pool was not closed under the following condition: chlorine too low.

      Correction: Ensure that the closing criteria are adhered to under the listed below.

      Code ATCP 76.30

    • Not serious Action taken:

      29b - BASIN DEFECTS

      The pool basin is missing grout between tiles.

      Correction: Repair the pool basin so it is finished and easily cleanable.

      Code ATCP 76.33(1)(a)

    • Not serious Other

      34e - VGBA COVERS

      No documentation is available on site for VGBA main drain and equalizer covers showing make/model, installation, and replacement date.

      Correction: Maintain documentation of VGBA covers for main drain and equalizers on site and available for review during inspection. Replace covers when lifespan is up.

      Code ATCP 76.11(2)(b)

  8. Dec 28, 2021 Re-Inspection · No Reinspection Required
    • Not serious Action taken:

      04c - SKIMMER BASKET/WEIR - Not Corrected

      The whirlpool skimmer weir is missing.

      Correction: Replace.

      Code ATCP 76.11(2)(b)

    • Not serious Action taken:

      05a - SKIMMER/MAIN DRAIN RATIO - Not Corrected

      The skimmer to main drain flow ratio is not set correctly.

      Correction: Readjust the flow so that on skimmer pool, only 20% of the flow comes through the main drain and 80% comes through the skimmers. On a gutter pool, 75% of the required recirculation flow shall be through the gutter and 25% through the main drain.

      Code ATCP 76.11(2)(a)

    • Not serious Action taken:

      08d - RECIRCULATION RATE - WHIRLPOOL - Not Corrected

      The whirlpool has a maximum turnover rate of greater than 30 minutes. The recirculation rate could not be calculated because the flow meter is not functioning.

      Correction: Immediately adjust or repair the equipment so the turnover rate does not exceed 30 minutes.

      Code ATCP 76.11(4)(d)

    • Not serious Action taken:

      09a - FLOW METER - Not Corrected

      The flow meter is not functional.

      Correction: Repair or replace the flowmeter so an accurate rate of flow can be recorded.

      Code ATCP 76.11(5)

    • Not serious Action taken:

      13c - DISINFECTANT FEEDER - NOT ELECTRICALLY CONNECTED - Not Corrected

      The disinfectant feeder pump is not electrically connected to the recirculation pump control circuit.

      Correction: Electrically connect the disinfectant feeder to the recirculation pump so it cannot keep running when the recirculation pump is turned off.

      Code ATCP 76.13(1)(c)

    • Not serious Action taken:

      14c - CHLORINE TOO HIGH - Not Corrected

      The chlorine residual exceeded 10 ppm.

      Correction: The pool must be closed and may not reopen until the chlorine residual comes into an acceptable range. Call inspector to notify of the Cl level.

      Code ATCP 76.14(4)(f)

    • Not serious Action taken:

      16a - pH - Not Corrected

      The pH is 8.0.

      Correction: Close the pool and do not reopen it until the pH falls between 7.2 and 7.8.

      Code ATCP 76.14(4)(c)

    • Not serious Action taken:

      16c - ALKALINITY - Not Corrected

      The total alkalinity is 330.

      Correction: Maintain the total alkalinity between 60 and 180 ppm.

      Code ATCP 76.14(4)(d)

    • Not serious Any of the following conditions or situa

      28a - CLOSING CRITERIA - Not Corrected

      The pool was not closed under the following condition: The pH and free chlorine level are well above acceptable level.

      Correction: Ensure that the closing criteria are adhered to under the listed below.

      Code ATCP 76.30

    • Not serious Action taken:

      29g - DRINKING FOUNTAIN - Not Corrected

      The drinking fountain is not functional or not clean.

      Correction: Repair/clean the drinking fountain.

      Code ATCP 76.33(1)(g)

    • Not serious Action taken:

      33a - HAZARDOUS MATERIAL - Not Corrected

      One of the four screw bolt is missing from the main drain cover at the time of the inspection.

      Correction: Remove [item] from the pool area. Close the whirlpool and replace the screw bolt.

      Code ATCP 76.34(1)

    • Not serious Other

      34e - VGBA COVERS - Not Corrected

      No documentation is available on site for VGBA main drain and/or equalizer covers showing make/model, installation, and replacement date.

      Correction: Maintain documentation of VGBA covers for main drain and equalizers on site and available for review during inspection. Replace covers when lifespan is up.

      Code ATCP 76.11(2)(b)

  9. Dec 3, 2021 Routine Inspection · Reinspection Required
    • Not serious Action taken:

      04c - SKIMMER BASKET/WEIR

      The skimmer weir is missing.

      Correction: Replace.

      Code ATCP 76.11(2)(b)

    • Not serious Action taken:

      05a - SKIMMER/MAIN DRAIN RATIO

      The skimmer to main drain flow ratio is not set correctly.

      Correction: Readjust the flow so that on skimmer pool, only 20% of the flow comes through the main drain and 80% comes through the skimmers. On a gutter pool, 75% of the required recirculation flow shall be through the gutter and 25% through the main drain.

      Code ATCP 76.11(2)(a)

    • Not serious Action taken:

      08d - RECIRCULATION RATE - WHIRLPOOL

      The whirlpool has a maximum turnover rate of greater than 30 minutes. The recirculation rate could not be calculated because the flow meter is not functioning.

      Correction: Immediately adjust or repair the equipment so the turnover rate does not exceed 30 minutes.

      Code ATCP 76.11(4)(d)

    • Not serious Action taken:

      09a - FLOW METER

      The flow meter is not functional.

      Correction: Repair or replace the flowmeter so an accurate rate of flow can be recorded.

      Code ATCP 76.11(5)

    • Not serious Action taken:

      13c - DISINFECTANT FEEDER - NOT ELECTRICALLY CONNECTED

      The disinfectant feeder pump is not electrically connected to the recirculation pump control circuit.

      Correction: Electrically connect the disinfectant feeder to the recirculation pump so it cannot keep running when the recirculation pump is turned off.

      Code ATCP 76.13(1)(c)

    • Not serious Action taken:

      14c - CHLORINE TOO HIGH

      The chlorine residual exceeded 10 ppm.

      Correction: The pool must be closed and may not reopen until the chlorine residual comes into an acceptable range. Call inspector to notify of the Cl level.

      Code ATCP 76.14(4)(f)

    • Not serious Action taken:

      16a - pH

      The pH is 8.

      Correction: Close the pool and do not reopen it until the pH falls between 7.2 and 7.8.

      Code ATCP 76.14(4)(c)

    • Not serious Action taken:

      16c - ALKALINITY

      The total alkalinity is 330.

      Correction: Maintain the total alkalinity between 60 and 180 ppm.

      Code ATCP 76.14(4)(d)

    • Not serious Any of the following conditions or situa

      28a - CLOSING CRITERIA

      The pool was not closed under the following condition: [condition].

      Correction: The pool was not closed under the following condition: The pH and free chlorine level are well above acceptable level.Ensure that the closing criteria are adhered to under the listed below.

      Code ATCP 76.30

    • Not serious Action taken:

      29g - DRINKING FOUNTAIN

      The drinking fountain is not functional or not clean.

      Correction: Repair/clean the drinking fountain.

      Code ATCP 76.33(1)(g)

    • Not serious Action taken:

      33a - HAZARDOUS MATERIAL

      One of the four screw bolt is missing from the main drain cover at the time of the inspection.

      Correction: Remove [item] from the pool area.

      Code ATCP 76.34(1)

    • Not serious Other

      34e - VGBA COVERS

      No documentation is available on site for VGBA main drain and/or equalizer covers showing make/model, installation, and replacement date.

      Correction: Maintain documentation of VGBA covers for main drain and equalizers on site and available for review during inspection. Replace covers when lifespan is up.

      Code ATCP 76.11(2)(b)

  10. Sep 3, 2019 Re-Inspection · No Reinspection Required

    No violations cited.

  11. Aug 13, 2019 Re-Inspection · Reinspection Required

    No violations cited.

  12. Aug 13, 2019 Re-Inspection · Reinspection Required

    No violations cited.

  13. Jul 17, 2019 Re-Inspection · Reinspection Required

    No violations cited.

  14. Jun 28, 2019 Re-Inspection · Reinspection Required

    No violations cited.

  15. Jun 14, 2019 Re-Inspection · Reinspection Required

    No violations cited.

  16. May 7, 2019 Routine Inspection · Reinspection Required

    No violations cited.

  17. May 24, 2018 Routine Inspection · No Reinspection Required

    No violations cited.

  18. Jun 28, 2017 Routine Inspection · No Reinspection Required

    No violations cited.

  19. Mar 2, 2016 Routine Inspection · No Reinspection Required

    No violations cited.

  20. Sep 22, 2015 Pre-Inspection · No Reinspection Required

    No violations cited.

Source: Public Health Madison & Dane County. History last read Nov 3, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.