Harbor Athletic Club
2529 ALLEN BLVD, Middleton, WI 53562 · Dane County
Establishment
- Type
- Pool / recreational water (Swimming Pool)
- Inspected by
- Public Health Madison & Dane County
- License / ID
- LICSWD-2010-00374
- Official record
- Public Health Madison & Dane County inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 1 | 1 | 0 |
| 2025 | 1 | 0 | 0 |
| 2023 | 1 | 1 | 0 |
| 2021 | 1 | 2 | 0 |
| 2018 | 1 | 0 | 0 |
| 2017 | 2 | 0 | 0 |
| 2016 | 1 | 0 | 0 |
| 2015 | 1 | 0 | 0 |
| 2014 | 1 | 0 | 0 |
| 2013 | 1 | 0 | 0 |
| 2012 | 1 | 0 | 0 |
Inspections
-
May 27, 2026 Routine Inspection · No Reinspection Required
-
Not serious
Action taken:
10i - DE - BACKFLOW PREVENTION (P)
There is no backflow prevention on the threaded outlet of the service sink in the pump room (there is a red hose attached to the sink outlet and a backflow preventer is required).
Correction: Install a backflow prevention device on the line going to the tank to correct the problem.
Code ATCP 76.11(6)(c)(4)
-
Not serious
Action taken:
-
Mar 11, 2025 Routine Inspection · No Reinspection Required
No violations cited.
-
Jan 10, 2023 Routine Inspection · No Reinspection Required
-
Not serious
Action taken: Robin closed the whirlpool
Corrected on site
14c - CHLORINE TOO HIGH
The chlorine residual exceeded 10 ppm. Free chlorine measured at 15 ppm.
Correction: The pool must be closed and may not reopen until the chlorine residual comes into an acceptable range.
Code ATCP 76.14(4)(f)
-
Not serious
Action taken: Robin closed the whirlpool
Corrected on site
-
Sep 30, 2021 Routine Inspection · No Reinspection Required
-
Not serious
Action taken:
16d - COMBINED CHLORINE
The combined chlorine is 1.0 ppm.
Correction: Treat the whirlpool with breakpoint chlorination using a chlorine product or a nonchlorinated oxidizer.
Code ATCP 76.14(4)(e)
-
Not serious
Other
34e - VGBA COVERS
No documentation is available on site for VGBA main drain and/or equalizer covers showing make/model, installation, and replacement date.
Correction: Maintain documentation of VGBA covers for main drain and equalizers on site and available for review during inspection. Replace covers when lifespan is up.
Code ATCP 76.11(2)(b)
-
Not serious
Action taken:
-
Dec 18, 2018 Routine Inspection · No Reinspection Required
No violations cited.
-
Dec 12, 2017 Routine Inspection · No Reinspection Required
No violations cited.
-
Feb 8, 2017 Routine Inspection · No Reinspection Required
No violations cited.
-
Jan 13, 2016 Routine Inspection · No Reinspection Required
No violations cited.
-
Feb 24, 2015 Routine Inspection · No Reinspection Required
No violations cited.
-
Feb 11, 2014 Routine Inspection · No Reinspection Required
No violations cited.
-
Jun 11, 2013 Routine Inspection · No Reinspection Required
No violations cited.
-
Jun 11, 2012 Routine Inspection · No Reinspection Required
No violations cited.
Source: Public Health Madison & Dane County. History last read Oct 1, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.