Harbor Athletic Club
2529 ALLEN BLVD, Middleton, WI 53562 · Dane County
Establishment
- Type
- Pool / recreational water (Swimming Pool)
- Inspected by
- Public Health Madison & Dane County
- License / ID
- LICSWD-2010-00375
- Official record
- Public Health Madison & Dane County inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 1 | 2 | 0 |
| 2025 | 1 | 0 | 0 |
| 2023 | 1 | 1 | 0 |
| 2021 | 1 | 2 | 0 |
| 2018 | 1 | 0 | 0 |
| 2017 | 2 | 0 | 0 |
| 2016 | 1 | 0 | 0 |
| 2015 | 1 | 0 | 0 |
| 2014 | 1 | 0 | 0 |
| 2013 | 1 | 0 | 0 |
| 2012 | 1 | 0 | 0 |
Inspections
-
May 27, 2026 Routine Inspection · No Reinspection Required
-
Not serious
Action taken:
11b - CHEMICAL - STORAGE (P)(Pf)
Chemicals are improperly stored in accordance with ATCP 76.12(2). The door to the pump room (with chemicals) is not locked - the door knob is not lockable).
Correction: Store chemicals in accordance with ATCP 76.12(2).
Code ATCP 76.12(2)
-
Not serious
Action taken:
31b - EQUIPMENT NOT LOCATED/INSTALLED/MAINTAINED/ REPAIRED
The flow meter has a slight leak where it is attached to the pvc piping (this might be affecting the accuracy of the flow meter and turnover rate calculation).
Correction: Properly locate, intall, maintain and repair equipment.
Code ATCP 76.33(1)(e)
-
Not serious
Action taken:
-
Mar 11, 2025 Routine Inspection · No Reinspection Required
No violations cited.
-
Jan 10, 2023 Routine Inspection · No Reinspection Required
-
Not serious
Action taken:
31b - EQUIPMENT NOT MAINTAINED
Small leak observed on recirculation piping located directly above pump.
Correction: Repair piping to eliminate leak and maintain.
Code ATCP 76.33(1)(e)
-
Not serious
Action taken:
-
Sep 30, 2021 Routine Inspection · No Reinspection Required
-
Not serious
Action taken:
31a - WALLS, CEILING AND FLOORS
Several missing tiles in deck near window area.
Correction: Provide/repair/replace missing floor tiles. Maintain the walls, ceilings, and floors in a clean and sanitary condition.
Code ATCP 76.33(1)(c)
-
Not serious
Other
34e - VGBA COVERS
No documentation is available on site for VGBA main drain and/or equalizer covers showing make/model, installation, and replacement date.
Correction: Maintain documentation of VGBA covers for main drain and equalizers on site and available for review during inspection. Replace covers when lifespan is up.
Code ATCP 76.11(2)(b)
-
Not serious
Action taken:
-
Dec 18, 2018 Routine Inspection · No Reinspection Required
No violations cited.
-
Dec 12, 2017 Routine Inspection · No Reinspection Required
No violations cited.
-
Feb 8, 2017 Routine Inspection · No Reinspection Required
No violations cited.
-
Jan 13, 2016 Routine Inspection · No Reinspection Required
No violations cited.
-
Feb 24, 2015 Routine Inspection · No Reinspection Required
No violations cited.
-
Feb 11, 2014 Routine Inspection · No Reinspection Required
No violations cited.
-
Jun 11, 2013 Routine Inspection · No Reinspection Required
No violations cited.
-
Jun 11, 2012 Routine Inspection · No Reinspection Required
No violations cited.
Source: Public Health Madison & Dane County. History last read Oct 1, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.