Harbor Athletic Club
2529 ALLEN BLVD, Middleton, WI 53562 · Dane County
Establishment
- Type
- Pool / recreational water (Swimming Pool)
- Inspected by
- Public Health Madison & Dane County
- License / ID
- 73053-81225
- Official record
- Public Health Madison & Dane County inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 1 | 0 | 0 |
| 2025 | 1 | 0 | 0 |
| 2023 | 1 | 3 | 0 |
| 2021 | 1 | 3 | 0 |
| 2018 | 1 | 0 | 0 |
| 2017 | 2 | 0 | 0 |
| 2016 | 1 | 0 | 0 |
| 2015 | 1 | 0 | 0 |
| 2014 | 1 | 0 | 0 |
| 2013 | 1 | 0 | 0 |
| 2012 | 1 | 0 | 0 |
Inspections
-
May 27, 2026 Routine Inspection · No Reinspection Required
No violations cited.
-
Mar 11, 2025 Routine Inspection · No Reinspection Required
No violations cited.
-
Jan 10, 2023 Routine Inspection · No Reinspection Required
-
Not serious
Action taken: To avoid a charged reinspe
13c - DISINFECTANT FEEDER - NOT ELECTRICALLY CONNECTED
The disinfectant feeder pump is not electrically connected to the recirculation pump control circuit.
Correction: Electrically connect the disinfectant feeder to the recirculation pump so it cannot keep running when the recirculation pump is turned off.
Code ATCP 76.13(1)(c)
-
Not serious
Action taken:
16d - COMBINED CHLORINE
The combined chlorine is 1.0 ppm.
Correction: Treat the pool with breakpoint chlorination using a chlorine product or a nonchlorinated oxidizer.
Code ATCP 76.14(4)(e)
-
Not serious
Action taken: Robin restocked a new cont
17a - CHLORINE GENERATORS - SECONDARY SYSTEM
There is no secondary disinfection system online to provide the capacity to superchlorinate. No chlorine available, disinfectant feeder not online.
Correction: Provide an automatically controlled online secondary disinfection system for the saltwater chlorine generator.
Code ATCP 76.15(1)
-
Not serious
Action taken: To avoid a charged reinspe
-
Sep 30, 2021 Routine Inspection · No Reinspection Required
-
Not serious
Action taken: San requested operator to
Corrected on site
14c - CHLORINE TOO HIGH
The chlorine residual exceeded 10 ppm.
Correction: The pool must be closed and may not reopen until the chlorine residual comes into an acceptable range (3.0 - 10.0 ppm).
Code ATCP 76.14(4)(f)
-
Not serious
Action taken: Robin will replace chlorin
17a - CHLORINE GENERATORS - SECONDARY SYSTEM
There is a secondary disinfection system to provide the capacity to superchlorinate, however, chorine container was missing and feeder tube was removed.
Correction: Provide a chorine container and re-install proper feeder tube to maintain a functioning secondary disinfection system for the salt water generator.
Code ATCP 76.15(1)
-
Not serious
Other
34e - VGBA COVERS
No documentation is available on site for VGBA main drain and/or equalizer covers showing make/model, installation, and replacement date.
Correction: Maintain documentation of VGBA covers for main drain and equalizers on site and available for review during inspection. Replace covers when lifespan is up.
Code ATCP 76.11(2)(b)
-
Not serious
Action taken: San requested operator to
Corrected on site
-
Dec 18, 2018 Routine Inspection · No Reinspection Required
No violations cited.
-
Dec 12, 2017 Routine Inspection · No Reinspection Required
No violations cited.
-
Feb 8, 2017 Routine Inspection · No Reinspection Required
No violations cited.
-
Jan 13, 2016 Routine Inspection · No Reinspection Required
No violations cited.
-
Feb 24, 2015 Routine Inspection · No Reinspection Required
No violations cited.
-
Feb 11, 2014 Routine Inspection · No Reinspection Required
No violations cited.
-
Jun 11, 2013 Routine Inspection · No Reinspection Required
No violations cited.
-
Jun 11, 2012 Routine Inspection · No Reinspection Required
No violations cited.
Source: Public Health Madison & Dane County. History last read Oct 1, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.