Oakbridge Swimming Pool
7917 TREE LN, Madison, WI 53717 · Dane County
Establishment
- Type
- Pool / recreational water (Swimming Pool)
- Inspected by
- Public Health Madison & Dane County
- License / ID
- 30585-15092
- Official record
- Public Health Madison & Dane County inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 1 | 2 | 0 |
| 2025 | 1 | 7 | 0 |
| 2024 | 1 | 4 | 0 |
| 2023 | 1 | 6 | 0 |
| 2021 | 2 | 0 | 0 |
| 2019 | 2 | 0 | 0 |
| 2018 | 1 | 0 | 0 |
| 2017 | 1 | 0 | 0 |
| 2016 | 1 | 0 | 0 |
| 2015 | 1 | 0 | 0 |
| 2014 | 1 | 0 | 0 |
| 2013 | 1 | 0 | 0 |
| 2012 | 1 | 0 | 0 |
Inspections
-
Jul 21, 2026 Routine Inspection · No Reinspection Required
-
Not serious
Action taken:
11e - SDS AVAILABILITY (Pf)
Safety data sheets are not available for all chemicals used in the facility.
Correction: Provide safety data sheets for all chemicals used in the facility.
Code ATCP 76.12(4)(b)
-
Not serious
Action taken:
32d - CARBON MONOXIDE ALARMS (P)
There is no carbon monoxide alarm in pool equipment room and in the indoor pool area where there is a fuel burning appliance.
Correction: Install functioning carbon monoxide alarms as applicable.
Code ATCP 76.33(4)(d)
-
Not serious
Action taken:
-
Aug 26, 2025 Routine Inspection · No Reinspection Required
-
Not serious
Action taken:
06a - SPARE STRAINER BASKET
A spare strainer basket(s) or screen for the recirculation pump is not located on site.
Correction: Provide a spare basket or screen.
Code ATCP 76.11(2)(d)
-
Not serious
Action taken:
11b - CHEMICAL - STORAGE (P)(Pf)
Chemicals are improperly stored in accordance with ATCP 76.12(2). In pump room, containers of acid stored near other chemicals.
Correction: Store chemicals in accordance with ATCP 76.12(2). Provide overspill containment for acid containers to prevent accidental mixing.
Code ATCP 76.12(2)
-
Not serious
Action taken:
16b - CYANURIC ACID (Pf)
The cyanuric acid concentration is >100ppm.
Correction: Lower the concentration of cyanuric acid to 30 ppm or lower.
Code ATCP 76.14(5)(b)
-
Not serious
Action taken:
21d - READABLE CHART
There is no readable chart that describes the piping, valves, and direction of water flow.
Correction: Labels, tags, or color coding shall correspond to a conspicuously posted, easily read chart that explains the system.
Code ATCP 76.11(5m)(b)
-
Not serious
Action taken:
26g - BREATH HOLDING PROHIBITION - SIGNAGE
Breath holding prohibition is not posted or communicated to patrons.
Correction: Provide signage or otherwise communicate to patrons that activites involving prolonged breath holding are prohibited.
Code ATCP 76.29(1)(f)
-
Not serious
Action taken:
26t - BIOHAZARD SAFETY KIT (Pf)
No biohazard safety kit is located at the first aid station or on the premises.
Correction: Provide a biohazard safety kit with the items listed in ATCP 76.27(2)(b) at the first aid station or on the premise. 1. Scoop and spatula. 2. Sanitizing hand wipes. 3. Sanitizing surface wipes. 4. Neoprene gloves. 5. Paper toweling. 6. Biohazard disposal bag at least 24"X24". 7. Twist tie or other effective means to close the bag. 8. Biohazard sorbent. 9. Storage case.
Code ATCP 76.27(2)
-
Not serious
Action taken:
31b - EQUIPMENT NOT LOCATED/INSTALLED/MAINTAINED/ REPAIRED
Leaks observed on the recirculation system.
Correction: Properly locate, install, maintain and repair equipment.
Code ATCP 76.33(1)(e)
-
Not serious
Action taken:
-
Aug 1, 2024 Routine Inspection · No Reinspection Required
-
Not serious
Action taken:
16b - CYANURIC ACID
The cyanuric acid concentration is 50ppm.
Correction: Lower the concentration of cyanuric acid to 30 ppm or lower.
Code ATCP 76.14(4)(b)
-
Not serious
Action taken:
26s - BIOHAZARD SAFETY KIT
No biohazard safety kit is located on the premises.
Correction: Provide a biohazard safety kit at the first aid station.
Code ATCP 76.27(2)
-
Not serious
Action taken:
31b - EQUIPMENT NOT MAINTAINED
Three leaks observed on the recirculation system.
Correction: Repair and maintain all equipment.
Code ATCP 76.33(1)(e)
-
Not serious
Other
34e - VGBA COVERS
No documentation is available on site for VGBA main drain and/or equalizer covers showing make/model, installation, and replacement date.
Correction: Maintain documentation of VGBA covers for main drain and equalizers on site and available for review during inspection. Replace covers when lifespan is up.
Code ATCP 76.11(2)(b)
-
Not serious
Action taken:
-
Jul 25, 2023 Routine Inspection · No Reinspection Required
-
Not serious
Action taken: main drain set to 20% duri
Corrected on site
05a - SKIMMER/MAIN DRAIN RATIO
The skimmer to main drain flow ratio is not set correctly. Main drain was set to full open.
Correction: Readjust the flow so that on skimmer pool, only 20% of the flow comes through the main drain and 80% comes through the skimmers. On a gutter pool, 75% of the required recirculation flow shall be through the gutter and 25% through the main drain.
Code ATCP 76.11(2)(a)
-
Not serious
Action taken: san recommended draining a
16b - CYANURIC ACID
The cyanuric acid concentration is 90 ppm.
Correction: Lower the concentration of cyanuric acid to 30 ppm or lower.
Code ATCP 76.14(4)(b)
-
Not serious
Action taken:
20c - WATER TESTING - POOLS
The water testing frequency for pH, free chlorine, alkalinity, and cyanuric acid are not in compliance with ATCP 76.18(1).
Correction: Perform water testing in accordance with ATCP 76.18(1). Test and record readings for pH and free chlorine 2x/day, alkalinity and cyanuric acid 1x/week.
Code ATCP 76.18(1)
-
Not serious
Action taken: Leigh and Patrick indicate
29b - BASIN DEFECTS
The pool basin appears rough in the deep end of the pool, paint is wearing away.
Correction: Repair the pool basin so it is finished and easily cleanable.
Code ATCP 76.33(1)(a)
-
Not serious
Action taken:
31b - EQUIPMENT NOT MAINTAINED
There is a leak on the recirculation system and on the erosion feeder.
Correction: Repair and maintain all equipment to eliminate leaks.
Code ATCP 76.33(1)(e)
-
Not serious
Other
34e - VGBA COVERS
No documentation is available on site for VGBA main drain and/or equalizer covers showing make/model, installation, and replacement date.
Correction: Maintain documentation of VGBA covers for main drain and equalizers on site and available for review during inspection. Replace covers when lifespan is up.
Code ATCP 76.11(2)(b)
-
Not serious
Action taken: main drain set to 20% duri
Corrected on site
-
Aug 18, 2021 Re-Inspection · No Reinspection Required
No violations cited.
-
Aug 16, 2021 Routine Inspection · Reinspection Required
No violations cited.
-
Aug 19, 2019 Re-Inspection · No Reinspection Required
No violations cited.
-
Aug 15, 2019 Routine Inspection · Reinspection Required
No violations cited.
-
Jun 1, 2018 Routine Inspection · No Reinspection Required
No violations cited.
-
Jun 23, 2017 Routine Inspection · No Reinspection Required
No violations cited.
-
Jun 8, 2016 Routine Inspection · No Reinspection Required
No violations cited.
-
May 27, 2015 Routine Inspection · No Reinspection Required
No violations cited.
-
Jun 17, 2014 Routine Inspection · No Reinspection Required
No violations cited.
-
Jun 17, 2013 Routine Inspection · No Reinspection Required
No violations cited.
-
Jun 13, 2012 Routine Inspection · No Reinspection Required
No violations cited.
Source: Public Health Madison & Dane County. History last read Oct 1, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.