Pool / recreational water (Swimming Pool)
Inspected by
Public Health Madison & Dane County
License / ID
LICSWD-2023-00278
Official record
Public Health Madison & Dane County inspection reports

Other public records for this business

Year by year

YearInspectionsViolationsSerious
20261100
2025100
2024130
2023100

Inspections

  1. Jul 15, 2026 Routine Inspection · No Reinspection Required
    • Not serious Action taken:

      04c - SKIMMER BASKET/WEIR

      Several weir doors are missing.

      Correction: Provide weir doors.

      Code ATCP 76.11(2)(b)

    • Not serious Action taken:

      09a - FLOW METER (P

      The flow meter is is not detecting flow and is designed for Schedule 80 pvc pipe. The piping is Schedule 40.

      Correction: Replace with a flowmeter designed for Schedule 40 piping so an accurate rate of flow can be recorded.

      Code ATCP 76.11(5)

    • Not serious Action taken:

      13d - INTERLOCK DEMONSTRATION OF KNOWLEDGE AND DOCUMENTS (P)

      Monthly interlocked testing is documented by a checkmark only.

      Correction: Monthly interlock testing shall be documented with date, results, and name of the person performing the test.

      Code ATCP 76.13(1)(c)

    • Not serious Action taken:

      21d - READABLE CHART

      There is no readable chart that describes the piping, valves, and direction of water flow.

      Correction: Labels, tags, or color coding shall correspond to a conspicuously posted, easily read chart that explains the system.

      Code ATCP 76.11(5m)(b)

    • Not serious Action taken:

      24a - LIFEGUARD - STAFFING PLAN (Ppf)

      The lifeguard staffing plan is missing: 1) a separate diagram for each pool use, and 2) arrows designating roaming patterns. The plan is missing one diving board and contains features that were never installed.

      Correction: Create a written plan pursuant to the requirements of ATCP 76.22 and submit it for approval.

      Code ATCP 76.22(1)

    • Not serious a. Do not enter the pool if you have a c

      27e - SIGNAGE - POOL RULES

      Pools rules signage not posted near the waterslide plunge area.

      Correction: Provide a sign in compliance with ATCP 76.29(1)(b).

      Code ATCP 76.29(1)(b) and ATCP 76.29(2)(a)

    • Not serious POOL SLIDES AND WATERSLIDES. For the plu

      27h - SIGNAGE - SLIDE RULES

      The waterslide rules signage is not posted at the entrance to the slide tower, contains lettering less than one inch, and is missing one rule: follow the instructions of the attendant. There is a code-compliant sign in the office.

      Correction: Waterslide rules with minimum one inch lettering shall be conspicuously posted at the entrance to the slide tower.

      Code ATCP 76.29(2)

    • Not serious Action taken: Door was closed. Corrected on site

      34d - DOOR/GATE (P)

      The front door to the building was propped open without being staffed with an attendant thus providing unmonitored access to the pools.

      Correction: The door shall remain closed at all times unless staffed with an attendant and at least one lifeguard present.

      Code ATCP 76.34(4)(b)

    • Not serious Action taken:

      39a - WATER ATTRACTION - MAINTANED SAFE (P)

      Waterslide gate at base of stairs is not locked when slide is not in operation.

      Correction: Gate shall be locked or secured using recognized safe practices to prevent patrons from accessing water slide when it is not in use.

      Code ATCP 76.37(1)(a)

    • Not serious Action taken:

      39c - DAILY INSPECTION AND TESTING (P)

      The water slide is not being inspected and their operation is not tested each day before use by patrons.

      Correction: Begin a daily inspection and operational testing program immediately.

      Code ATCP 76.37(2)(b)

  2. Jul 23, 2025 Routine Inspection · No Reinspection Required

    No violations cited.

  3. Jul 26, 2024 Routine Inspection · No Reinspection Required
    • Not serious Action taken: Discussed variance request

      24a - LIFEGUARD - STAFFING PLAN

      The lifeguard staffing plan requires revision. The PIC plans to submit a variance for alternative staffing for several scenarios.

      Correction: Create a written plan pursuant to the requirements of ATCP 76.22 and submit it for approval.

      Code ATCP 76.22(1)(a)

    • Not serious Action taken: PIC printed labels to atta Corrected on site

      26o - EMERGENCY NUMBERS AND ADDRESS

      The facility's location are not posted near the designated emergency phone.

      Correction: Post the emergency numbers near the designated emergency phone.

      Code ATCP 76.26(2)

    • Not serious Action taken: PIC plans to order complet

      26s - BIOHAZARD SAFETY KIT

      Some components of the biohazard kit are available but not complete.

      Correction: Provide a biohazard safety kit at the first aid station.

      Code ATCP 76.27(2)

  4. May 26, 2023 Pre-Inspection · No Reinspection Required

    No violations cited.

Source: Public Health Madison & Dane County. History last read Oct 1, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.