Southbridge Neighborhood Pool
1513 BLUE RIDGE TRL, Waunakee, WI 53597 · Dane County
Establishment
- Type
- Pool / recreational water (Swimming Pool)
- Inspected by
- Public Health Madison & Dane County
- License / ID
- 73795-82070
- Official record
- Public Health Madison & Dane County inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 1 | 2 | 0 |
| 2025 | 1 | 2 | 0 |
| 2024 | 1 | 0 | 0 |
| 2022 | 1 | 1 | 0 |
| 2021 | 1 | 0 | 0 |
| 2018 | 3 | 0 | 0 |
| 2017 | 1 | 0 | 0 |
| 2015 | 1 | 0 | 0 |
| 2014 | 1 | 0 | 0 |
| 2013 | 1 | 0 | 0 |
| 2012 | 1 | 0 | 0 |
Inspections
-
Jul 10, 2026 Routine Inspection · No Reinspection Required
-
Not serious
Action taken:
32d - CARBON MONOXIDE ALARMS (P)
There is no carbon monoxide alarm in pool equipment room and in the indoor pool area where there is a fuel burning appliance.
Correction: Install functioning carbon monoxide alarms as applicable.
Code ATCP 76.33(4)(d)
-
Not serious
Other
34f - VGBA COVERS DOCUMENTATION (Pf)
No documentation is available on site for VGBA main drain and/or equalizer covers showing make, model, gallons per minute rating, life span, and installation date.
Correction: Maintain documentation (log, receipts, or affidavits from a pool service company) of VGBA covers for main drain and equalizers on site and available for review during inspection. Documentation shall include the following: 1. Make 2. Model 3. Gallons per minute rating. 4. Life span. 5. Installation date.
Code ATCP 76.38
-
Not serious
Action taken:
-
Aug 1, 2025 Routine Inspection · No Reinspection Required
-
Not serious
Action taken:
32d - CARBON MONOXIDE ALARMS (P)
There is no carbon monoxide alarm in pool equipment room and in the indoor pool area where there is a fuel burning appliance.
Correction: Install functioning carbon monoxide alarms as applicable.
Code ATCP 76.33(4)(d)
-
Not serious
Other
34f - VGBA COVERS DOCUMENTATION (Pf)
No documentation is available on site for VGBA main drain and/or equalizer covers showing make, model, gallons per minute rating, life span, and installation date.
Correction: Maintain documentation (log, receipts, or affidavits from a pool service company) of VGBA covers for main drain and equalizers on site and available for review during inspection. Documentation shall include the following: 1. Make 2. Model 3. Gallons per minute rating. 4. Life span. 5. Installation date.
Code ATCP 76.38
-
Not serious
Action taken:
-
Jul 22, 2024 Routine Inspection · No Reinspection Required
No violations cited.
-
Jul 27, 2022 Routine Inspection · No Reinspection Required
-
Not serious
Action taken:
21b - BACKFLOW - HOSE BIBBS
The hose bibb adjacent to the pump room door to the pool is not protected against backsiphonage.
Correction: Install a hose bibb atmospheric vacuum breaker that meets the ASSE 1011 standard on the hose bibb. (ASSE 1011 indoor backflow preventer)
Code ATCP 76.33(1)(d)
-
Not serious
Action taken:
-
Jun 11, 2021 Routine Inspection · No Reinspection Required
No violations cited.
-
Aug 30, 2018 Routine Inspection · No Reinspection Required
No violations cited.
-
Aug 9, 2018 Re-Inspection · No Reinspection Required
No violations cited.
-
Jun 20, 2018 Routine Inspection · Reinspection Required
No violations cited.
-
Jun 6, 2017 Routine Inspection · No Reinspection Required
No violations cited.
-
Jul 20, 2015 Routine Inspection · No Reinspection Required
No violations cited.
-
Aug 18, 2014 Routine Inspection · No Reinspection Required
No violations cited.
-
Aug 19, 2013 Routine Inspection · No Reinspection Required
No violations cited.
-
Aug 29, 2012 Routine Inspection · No Reinspection Required
No violations cited.
Source: Public Health Madison & Dane County. History last read Oct 1, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.