RecordWell Data

Southbridge Neighborhood Pool

1513 BLUE RIDGE TRL, Waunakee, WI 53597 · Dane County

5cited violations
0serious tier
13inspections

Establishment

Type
Pool / recreational water (Swimming Pool)
Inspected by
Public Health Madison & Dane County
License / ID
73795-82070
Official record
Public Health Madison & Dane County inspection reports

Other public records for this business

Year by year

YearInspectionsViolationsSerious
2026120
2025120
2024100
2022110
2021100
2018300
2017100
2015100
2014100
2013100
2012100

Inspections

  1. Jul 10, 2026 Routine Inspection · No Reinspection Required
    • Not serious Action taken:

      32d - CARBON MONOXIDE ALARMS (P)

      There is no carbon monoxide alarm in pool equipment room and in the indoor pool area where there is a fuel burning appliance.

      Correction: Install functioning carbon monoxide alarms as applicable.

      Code ATCP 76.33(4)(d)

    • Not serious Other

      34f - VGBA COVERS DOCUMENTATION (Pf)

      No documentation is available on site for VGBA main drain and/or equalizer covers showing make, model, gallons per minute rating, life span, and installation date.

      Correction: Maintain documentation (log, receipts, or affidavits from a pool service company) of VGBA covers for main drain and equalizers on site and available for review during inspection. Documentation shall include the following: 1. Make 2. Model 3. Gallons per minute rating. 4. Life span. 5. Installation date.

      Code ATCP 76.38

  2. Aug 1, 2025 Routine Inspection · No Reinspection Required
    • Not serious Action taken:

      32d - CARBON MONOXIDE ALARMS (P)

      There is no carbon monoxide alarm in pool equipment room and in the indoor pool area where there is a fuel burning appliance.

      Correction: Install functioning carbon monoxide alarms as applicable.

      Code ATCP 76.33(4)(d)

    • Not serious Other

      34f - VGBA COVERS DOCUMENTATION (Pf)

      No documentation is available on site for VGBA main drain and/or equalizer covers showing make, model, gallons per minute rating, life span, and installation date.

      Correction: Maintain documentation (log, receipts, or affidavits from a pool service company) of VGBA covers for main drain and equalizers on site and available for review during inspection. Documentation shall include the following: 1. Make 2. Model 3. Gallons per minute rating. 4. Life span. 5. Installation date.

      Code ATCP 76.38

  3. Jul 22, 2024 Routine Inspection · No Reinspection Required

    No violations cited.

  4. Jul 27, 2022 Routine Inspection · No Reinspection Required
    • Not serious Action taken:

      21b - BACKFLOW - HOSE BIBBS

      The hose bibb adjacent to the pump room door to the pool is not protected against backsiphonage.

      Correction: Install a hose bibb atmospheric vacuum breaker that meets the ASSE 1011 standard on the hose bibb. (ASSE 1011 indoor backflow preventer)

      Code ATCP 76.33(1)(d)

  5. Jun 11, 2021 Routine Inspection · No Reinspection Required

    No violations cited.

  6. Aug 30, 2018 Routine Inspection · No Reinspection Required

    No violations cited.

  7. Aug 9, 2018 Re-Inspection · No Reinspection Required

    No violations cited.

  8. Jun 20, 2018 Routine Inspection · Reinspection Required

    No violations cited.

  9. Jun 6, 2017 Routine Inspection · No Reinspection Required

    No violations cited.

  10. Jul 20, 2015 Routine Inspection · No Reinspection Required

    No violations cited.

  11. Aug 18, 2014 Routine Inspection · No Reinspection Required

    No violations cited.

  12. Aug 19, 2013 Routine Inspection · No Reinspection Required

    No violations cited.

  13. Aug 29, 2012 Routine Inspection · No Reinspection Required

    No violations cited.

Source: Public Health Madison & Dane County. History last read Oct 1, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.