Springhill Suites By Marriott
4601 Frey ST, Madison, WI 53705 · Dane County
Establishment
- Type
- Pool / recreational water (Swimming Pool)
- Inspected by
- Public Health Madison & Dane County
- License / ID
- LICSWD-2018-00735
- Official record
- Public Health Madison & Dane County inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 1 | 3 | 0 |
| 2025 | 1 | 3 | 0 |
| 2024 | 1 | 2 | 0 |
| 2022 | 1 | 1 | 0 |
| 2021 | 1 | 0 | 0 |
| 2019 | 1 | 0 | 0 |
Inspections
-
Jan 14, 2026 Routine Inspection · No Reinspection Required
-
Not serious
Action taken:
09a - FLOW METER (P
The flow meter is not functional or installed properly. Flow rate appears to exceed limit of flow meter.
Correction: Repair, replace, or install the flowmeter so an accurate rate of flow can be recorded.
Code ATCP 76.11(5)
-
Not serious
Action taken:
26g - BREATH HOLDING PROHIBITION - SIGNAGE
Breath holding prohibition is not posted or communicated to patrons.
Correction: Provide signage or otherwise communicate to patrons that activities involving prolonged breath holding are prohibited.
Code ATCP 76.29(1)(f)
-
Not serious
Action taken:
26s - BLANKETS MISSING (Pf)
2 conventional or emergency blankets are not available in the pool area.
Correction: Provide 2 conventional or emergency blankets in the pool area.
Code ATCP 76.27(1)(3)
-
Not serious
Action taken:
-
Feb 14, 2025 Routine Inspection · No Reinspection Required
-
Not serious
Action taken: pool operator, Gabriel, in
14e - WATER POTENTIAL ORP
The water potential was 969 mV at the time of the inspection.
Correction: Manually test the pool water and recalibrate the oxidation potential controller if needed to maintain the water potential between 650 to 900 mV.
Code ATCP 76.14(5)(a)
-
Not serious
Action taken:
16d - COMBINED CHLORINE
The combined chlorine is 0.8ppm.
Correction: Treat the pool with breakpoint chlorination using a chlorine product or a nonchlorinated oxidizer.
Code ATCP 76.14(4)(e)
-
Not serious
Action taken: Adam Schomaker will add co
20c - WATER TESTING - POOLS
The water testing frequency for combined chlorine is not in compliance with ATCP 76.18(1).
Correction: Perform water testing in accordance with ATCP 76.18(1). Test/record results for combined chlorine at least 2x/week.
Code ATCP 76.18(1)
-
Not serious
Action taken: pool operator, Gabriel, in
-
Jan 31, 2024 Routine Inspection · No Reinspection Required
-
Not serious
Action taken:
09a - FLOW METER
The flow meter is not functional or the flowrate is too high (>110 gpm).
Correction: Repair or replace the flowmeter or the recirculation system so an accurate rate of flow can be recorded.
Code ATCP 76.11(5)
-
Not serious
Action taken:
16d - COMBINED CHLORINE
The combined chlorine is 1.2 ppm.
Correction: Treat the pool with breakpoint chlorination using a chlorine product or a nonchlorinated oxidizer to eliminate the combined chorine.
Code ATCP 76.14(4)(e)
-
Not serious
Action taken:
-
Dec 21, 2022 Routine Inspection · No Reinspection Required
-
Not serious
Action taken: Discussed with operator. S
20e - WATER TESTING FREQUENCY - ORP
Water testing for pH and chlorine is not completed on Sundays when the pool is open.
Correction: Perform water testing in accordance with ATCP 76.18(3). Test pH and chlorine once on Sundays.
Code ATCP 76.18(3)
-
Not serious
Action taken: Discussed with operator. S
-
Aug 2, 2021 Routine Inspection · No Reinspection Required
No violations cited.
-
Mar 20, 2019 Pre-Inspection · No Reinspection Required
No violations cited.
Source: Public Health Madison & Dane County. History last read Oct 1, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.