Staybridge Suites Middleton
7790 ELMWOOD AVE, City Of Middleton, WI 53562 · Dane County
Establishment
- Type
- Pool / recreational water (Swimming Pool)
- Inspected by
- Public Health Madison & Dane County
- License / ID
- LICSWD-2023-00318
- Official record
- Public Health Madison & Dane County inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 3 | 22 | 0 |
| 2024 | 1 | 8 | 0 |
| 2023 | 1 | 2 | 0 |
Inspections
-
May 13, 2026 Re-Inspection · No Reinspection Required
-
Not serious
Action taken:
16d - COMBINED CHLORINE (Pf) - Not Corrected
The operator does not have a combined chlorine plan or is not following combined chlorine plan.
Correction: Provide a plan with all components required under ATCP 76.14(5)(e)
Code ATCP 76.14(5)(e)
-
Not serious
Action taken: Pool closed by operator. P
Repeat
26n - TELEPHONE - NOT WORKING (P) - Not Corrected
Emergency phone rings front desk and does not work.
Correction: Provide a functional emergency telephone immediately. Post the emergency numbers near or attached to the designated emergency phone. Ensure calls are picked up within 2 rings, staff are trained on emergency procedures, do not have distractive duties, and do not use cordless phone to leave desk. Post emergency numbers and address at front desk.
Code ATCP 76.26(2)
-
Not serious
Action taken:
28e -REPORTS AND RECORDS (Pf) - Not Corrected
Monthly operating record does not include monthly pump and safety checks.
Correction: Keep the following records available for review. (a) Chemical testing pursuant s. ATCP 76.14. (b) Backwashing completion. (c) Breakpoint chlorination. (d) Interlock testing. (e) Anti-entrapment system testing. (f) Water temperature. (g) Safety and rescue equipment maintaining pursuant to ss. ATCP 76.26 and ATCP 76.27. (h) If monthly reports are requested by the department or its agent, they shall
Code ATCP 76.32(1)
-
Not serious
Action taken: Remodel expected Summer 20
29b - BASIN MAINTENANCE AND REPAIR - Not Corrected
The pool basin is discolored.
Correction: Maintain the pool basin in a clean, sanitary condition and free from cracks and defects.
Code ATCP 76.33(1)(a)
-
Not serious
Action taken:
-
May 11, 2026 Re-Inspection · Reinspection Required
-
Not serious
Action taken:
16d - COMBINED CHLORINE (Pf) - Not Corrected
The operator does not have a combined chlorine plan or is not following combined chlorine plan.
Correction: Provide a plan with all components required under ATCP 76.14(5)(e)
Code ATCP 76.14(5)(e)
-
Not serious
Action taken:
20b - TEST KIT REAGENT STORAGE (Pf) - Not Corrected
The test kit reagents are being used past their expiration date.
Correction: Store reagents properly, in original containers, replace when expired.
Code ATCP 76.17(2)
-
Not serious
Action taken:
20d - WATER TESTING - WHIRLPOOL, THERAPY, EXERCISE (Pf) - Not Corrected
Water testing was not completed daily for each day the whirlpool was open.
Correction: Perform water testing in accordance with ATCP 76.18(2).
Code ATCP 76.18(2)
-
Not serious
Action taken: Poster provided with email
26g - BREATH HOLDING PROHIBITION - SIGNAGE - Not Corrected
Breath holding prohibition is not posted or communicated to patrons.
Correction: Provide signage or otherwise communicate to patrons that activities involving prolonged breath holding are prohibited.
Code ATCP 76.29(1)(f)
-
Not serious
Action taken: Pool closed by operator. P
Corrected on site
26n - TELEPHONE - NOT WORKING (P) - Not Corrected
Emergency phone rings front desk and does not work.
Correction: Provide a functional emergency telephone immediately. Post the emergency numbers near or attached to the designated emergency phone. Ensure calls are picked up within 2 rings, staff are trained on emergency procedures, do not have distractive duties, and do not use cordless phone to leave desk. Post emergency numbers and address at front desk.
Code ATCP 76.26(2)
-
Not serious
Action taken:
28e -REPORTS AND RECORDS (Pf) - Not Corrected
Monthly operating record does not include monthly pump and safety checks.
Correction: Keep the following records available for review. (a) Chemical testing pursuant s. ATCP 76.14. (b) Backwashing completion. (c) Breakpoint chlorination. (d) Interlock testing. (e) Anti-entrapment system testing. (f) Water temperature. (g) Safety and rescue equipment maintaining pursuant to ss. ATCP 76.26 and ATCP 76.27. (h) If monthly reports are requested by the department or its agent, they shall
Code ATCP 76.32(1)
-
Not serious
Action taken: Remodel expected Summer 20
29b - BASIN MAINTENANCE AND REPAIR - Not Corrected
The pool basin is discolored.
Correction: Maintain the pool basin in a clean, sanitary condition and free from cracks and defects.
Code ATCP 76.33(1)(a)
-
Not serious
Action taken:
Corrected on site
32d - CARBON MONOXIDE ALARMS (P) - Not Corrected
There is no carbon monoxide alarm in the indoor pool area with a fuel burning appliance in the adjacent equipment room.
Correction: Install functioning carbon monoxide alarm in the pool area.
Code ATCP 76.33(4)(d)
-
Not serious
Other
34f - VGBA COVERS DOCUMENTATION (Pf) - Not Corrected
No pump curve available for recirculation pump.
Correction: Maintain recirculation pump curve onsite.
Code ATCP 76.38
-
Not serious
Action taken:
-
Mar 26, 2026 Routine Inspection · Reinspection Required
-
Not serious
Action taken:
16d - COMBINED CHLORINE (Pf)
The operator does not have a combined chlorine plan or is not following combined chlorine plan.
Correction: Provide a plan with all components required under ATCP 76.14(5)(e)
Code ATCP 76.14(5)(e)
-
Not serious
Action taken:
20b - TEST KIT REAGENT STORAGE (Pf)
The test kit reagents are being used past their expiration date.
Correction: Store reagents properly, in original containers, replace when expired.
Code ATCP 76.17(2)
-
Not serious
Action taken:
20d - WATER TESTING - WHIRLPOOL, THERAPY, EXERCISE (Pf)
Water testing was not completed daily for each day the whirlpool was open.
Correction: Perform water testing in accordance with ATCP 76.18(2).
Code ATCP 76.18(2)
-
Not serious
Action taken: Poster provided with email
26g - BREATH HOLDING PROHIBITION - SIGNAGE
Breath holding prohibition is not posted or communicated to patrons.
Correction: Provide signage or otherwise communicate to patrons that activities involving prolonged breath holding are prohibited.
Code ATCP 76.29(1)(f)
-
Not serious
Action taken: Pool closed by operator. P
Corrected on site
26n - TELEPHONE - NOT WORKING (P)
Emergency phone rings front desk and does not work.
Correction: Provide a functional emergency telephone immediately. Post the emergency numbers near or attached to the designated emergency phone. Ensure calls are picked up within 2 rings, staff are trained on emergency procedures, do not have distractive duties, and do not use cordless phone to leave desk. Post emergency numbers and address at front desk.
Code ATCP 76.26(2)
-
Not serious
Action taken:
28e -REPORTS AND RECORDS (Pf)
Monthly operating record does not include monthly pump and safety checks.
Correction: Keep the following records available for review. (a) Chemical testing pursuant s. ATCP 76.14. (b) Backwashing completion. (c) Breakpoint chlorination. (d) Interlock testing. (e) Anti-entrapment system testing. (f) Water temperature. (g) Safety and rescue equipment maintaining pursuant to ss. ATCP 76.26 and ATCP 76.27. (h) If monthly reports are requested by the department or its agent, they shall
Code ATCP 76.32(1)
-
Not serious
Action taken: Remodel expected Summer 20
29b - BASIN MAINTENANCE AND REPAIR
The pool basin is discolored.
Correction: Maintain the pool basin in a clean, sanitary condition and free from cracks and defects.
Code ATCP 76.33(1)(a)
-
Not serious
Action taken:
Corrected on site
32d - CARBON MONOXIDE ALARMS (P)
There is no carbon monoxide alarm in the indoor pool area with a fuel burning appliance in the adjacent equipment room.
Correction: Install functioning carbon monoxide alarm in the pool area.
Code ATCP 76.33(4)(d)
-
Not serious
Other
34f - VGBA COVERS DOCUMENTATION (Pf)
No pump curve available for recirculation pump.
Correction: Maintain recirculation pump curve onsite.
Code ATCP 76.38
-
Not serious
Action taken:
-
Jan 17, 2024 Routine Inspection · No Reinspection Required
-
Not serious
Action taken: Muriatic acid safety data
11e - SDS AVAILABILITY
Safety data sheets are not available for all chemicals used in the facility including muriatic acid, sodium hydrogen sulfite, calcium chloride taylor test kit reagents and defoaming agent.
Correction: Provide safety data sheets for all chemicals used in the facility.
Code ATCP 76.12(4)(b)
-
Not serious
Action taken: Video training provided wi
13c - DISINFECTANT FEEDER - NOT ELECTRICALLY CONNECTED
Operator unable to demonstrate that the disinfectant feeder pump is electrically connected to the recirculation pump control circuit.
Correction: Ensure disinfectant feeder is electrically connected to the recirculation pump so it cannot keep running when the recirculation pump is turned off. Obtain training to demonstrate system is electrically connected.
Code ATCP 76.13(1)(c)
-
Not serious
Action taken:
14e - WATER POTENTIAL ORP
The water potential was 879 mV at the time of the inspection. System alarm flashing.
Correction: Manually test the pool water and recalibrate the oxidation potential controller if needed to maintain the water potential between 650 to 850 mV.
Code ATCP 76.14(5)(a)
-
Not serious
Action taken:
16d - COMBINED CHLORINE
The combined chlorine is 1.6ppm
Correction: Treat the pool with breakpoint chlorination using a chlorine product or a non-chlorinated oxidizer.
Code ATCP 76.14(4)(e)
-
Not serious
Action taken: Factsheet provided with em
20d - WATER TESTING - WHIRLPOOL, THERAPY, EXERCISE
Combined chlorine and alkalinity is not tested at a frequency specified with ATCP 76.18(2). Electronic ORP monitor is improperly functioning. Increase testing frequency for pH and disinfectant in accordance with ATCP 76.18(2).
Correction: Perform water testing in accordance with ATCP 76.18(2). Test pH and disinfectant 4/day, combined chlorine 1/day and alkalinity 1/week.
Code ATCP 76.18(2)
-
Not serious
Action taken:
28d - MONTHLY REPORTS AVAILABLE
Pump curve and CDC fecal response procedure are not available for review.
Correction: Keep records available for review.
Code ATCP 76.32(3)
-
Not serious
Action taken:
34a - GATES NOT MAINTAINED
The gate or door to the pool enclosure from the courtyard is not being maintained. Mechanism requires repair. Parts ordered per operator. Door temporarily locked. Email sanitarian when repair is complete.
Correction: Repair and maintain the gate or door.
Code ATCP 76.34(2)
-
Not serious
Other
34e - VGBA COVERS
No documentation is available on site for VGBA main drain and/or equalizer covers showing make/model, installation, and replacement date. Covers appear secure and intact.
Correction: Maintain documentation of VGBA covers for main drain and equalizers on site and available for review during inspection. Replace covers when lifespan is up.
Code ATCP 76.11(2)(b)
-
Not serious
Action taken: Muriatic acid safety data
-
Jun 15, 2023 Pre-Inspection · No Reinspection Required
-
Not serious
Action taken:
26r - BLANKETS MISSING
2 durable blankets are not available in the pool area. There was only 1 rescue blanket available in the first aid kit.
Correction: Provide 2 durable blankets in the pool area.
Code ATCP 76.27(1)
-
Not serious
Action taken: self-latching bar is on or
34c - DOOR/GATE
The courtyard door to the pool enclosure is self-closing and lockable, however, the self-latching mechanism is missing.
Correction: Repair the door immediately so that it is self-closing, self-latching, and is lockable.
Code ATCP 76.34(4)
-
Not serious
Action taken:
Source: Public Health Madison & Dane County. History last read Oct 1, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.