Villa At Apple Creek Pool
2228 E MILESTONE DR, Appleton, WI 54913 · Outagamie County
Establishment
- Type
- Pool / recreational water (Swimming)
- Inspected by
- City of Appleton Health Department
- License / ID
- HSAT-7QWRS4
- Status
- Permitted
- Phone
- (920) 560-5030
- Official record
- City of Appleton Health Department inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 1 | 4 | 0 |
| 2025 | 1 | 6 | 1 |
| 2024 | 1 | 3 | 0 |
| 2023 | 1 | 2 | 0 |
Inspections
-
Aug 4, 2026 Routine · 4 non-critical, 3 repeat
-
Not serious
Non-critical
BACKWASH PROCEDURES POSTED ON EASILY READ CHART
The backwash procedure is no conspicuously posted on an easily read chart.
Correction: Post the backwash procedure on an easily read chart.
Code ATCP 76.11(6)(a) 4. - PROCEDURE POSTED
-
Not serious
Non-critical
Repeat
INTERLOCK-LOG KEPT
A log of the monthly interlock tests is not being kept.
Correction: Keep a log of monthly interlock tests.
Code ATCP 76.13 (1)(c)4 - INTERLOCK, LOG KEPT
-
Not serious
Non-critical
Repeat
COMBINED CHLORINE PLAN PRESENT
The operator has not developed and implemented a plan to minimize combined chlorine in the pool.
Correction: Develop and implement a plan to minimize combined chlorine in the pool.
Code ATCP 76.14(5)(e)1. - PLAN PRESENT
-
Not serious
Non-critical
Repeat
COMBINED CHLORINE TEST
Chlorine is used and pool water is not tested at least twice a week for the combined chlorine level.
Correction: Test pool water at least twice a week for the combined chlorine level.
Code ATCP 76.18(1)(b) - WATER TESTED COMBINED CHLORINE,
-
Not serious
Non-critical
-
Jul 21, 2025 Routine · 1 critical, 5 non-critical, 3 repeat
-
Not serious
Non-critical
Corrected on site
FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED
The needle is broken on the sand filter psi guage.
Correction: Adjust or repair the needle. Resident indicated it is on order.
Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED
-
Not serious
Non-critical
Repeat
INTERLOCK-LOG KEPT
A log of the monthly interlock tests is not being kept.
Correction: Keep a log of monthly interlock tests.
Code ATCP 76.13 (1)(c)4 - INTERLOCK, LOG KEPT
-
Not serious
Non-critical
Repeat
COMBINED CHLORINE PLAN PRESENT
The operator has not developed and implemented a plan to minimize combined chlorine in the pool.
Correction: Develop and implement a plan to minimize combined chlorine in the pool.
Code ATCP 76.14(5)(e)1. - PLAN PRESENT
-
Not serious
Non-critical
ELECTRONIC MONITORING WATER POTENTIAL
The water potential ("ORP") is 485mV and now 635 water has not been tested manually.
Correction: Maintain water potential between 650−900 mV, and manually test the water if the water potential reads below 650 mV or above 900 mV.
Code ATCP 76.14(6)(a) - OXIDATION POTENTIAL
-
Not serious
Non-critical
Repeat
COMBINED CHLORINE TEST
Chlorine is used and pool water is not tested at least twice a week for the combined chlorine level.
Correction: Test pool water at least twice a week for the combined chlorine level.
Code ATCP 76.18(1)(b) - WATER TESTED COMBINED CHLORINE,
-
Serious
Critical
Corrected on site
MINIMUM DISINFECTANT RESIDUAL
Minimum disinfectant or sanitizer level is .36 for chlorine. Rechecked and now 5.02 ppm
Correction: Close the pool until disinfectant level is in compliance with ATCP 76.14 Table A.
Code ATCP 76.14(5)(a) - MINIMUM DISINFECTANT RESIDUAL
-
Not serious
Non-critical
Corrected on site
-
Jul 25, 2024 Routine · 3 non-critical
-
Not serious
Non-critical
INTERLOCK-LOG KEPT
A log of the monthly interlock tests is not being kept.
Correction: Keep a log of monthly interlock tests.
Code ATCP 76.13 (1)(c)4 - INTERLOCK, LOG KEPT
-
Not serious
Non-critical
COMBINED CHLORINE PLAN PRESENT
The operator has not developed and implemented a plan to minimize combined chlorine in the pool.
Correction: Develop and implement a plan to minimize combined chlorine in the pool.
Code ATCP 76.14(5)(e)1. - PLAN PRESENT
-
Not serious
Non-critical
COMBINED CHLORINE TEST
Chlorine is used and pool water is not tested at least twice a week for the combined chlorine level.
Correction: Test pool water at least twice a week for the combined chlorine level.
Code ATCP 76.18(1)(b) - WATER TESTED COMBINED CHLORINE,
-
Not serious
Non-critical
-
Jul 18, 2023 Routine · 2 non-critical
-
Not serious
Non-critical
WATER TESTING FREQUENCY - POOLS
The water testing frequency for combine chlorine is not in compliance with ATCP 76.18(1).
Correction: Perform water testing in accordance with ATCP 76.18(1). Test combined at least twice a week.
Code ATCP 76.18(1)
-
Not serious
Non-critical
WATER TESTING FREQUENCY - ELECTRONIC MONITORING DEVICE
ORP is at 620 and shall be between 650 and 850. ATCP 76.18(3). .
Correction: Perform water testing in accordance with ATCP 76.18(3) or adjust ORP to a minimum of 650.
Code ATCP 76.18(3)
-
Not serious
Non-critical
Source: City of Appleton Health Department. History last read Oct 1, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.