Chetek River Campground
590 24TH ST, Chetek, WI 54728 · Barron County
Establishment
- Type
- Pool / recreational water (Pool - Simple)
- Inspected by
- Barron County Department of Health & Human Services
- License / ID
- TMYS-CBMMSY
- Status
- Permitted
- Phone
- (715) 924-2440
- Official record
- Barron County Department of Health & Human Services inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 2 | 2 | 0 |
| 2025 | 1 | 3 | 1 |
| 2024 | 1 | 11 | 1 |
| 2023 | 1 | 2 | 0 |
Inspections
-
Aug 11, 2026 Follow Up · 1 non-critical, 1 repeat
-
Not serious
Non-critical
Repeat
SKIMMERS REPAIRED OR REPLACED AS NEEDED
VGBA main drain covers not replaced as needed. Drain covers expired , new covers purchased and installed, but no proof available during inspection.
Correction: Install new drain covers before the next season or provide proof of installed drain covers. The operator must log daily inspection of the drain cover to ensure no cracks, breaks, missing screws or other visible damage or defects are observed. The operator shall close the pool if any of the above damage or defects are observed. The pool must be closed until a compliant drain cover has been installe
Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED
-
Not serious
Non-critical
Repeat
-
Jul 28, 2026 Routine · 1 non-critical
-
Not serious
Non-critical
SKIMMERS REPAIRED OR REPLACED AS NEEDED
VGBA main drain covers not replaced as needed. Drain covers expired , new covers purchased and installed, but no proof available during inspection.
Correction: Install new drain covers before the next season or provide proof of installed drain covers. The operator must log daily inspection of the drain cover to ensure no cracks, breaks, missing screws or other visible damage or defects are observed. The operator shall close the pool if any of the above damage or defects are observed. The pool must be closed until a compliant drain cover has been installe
Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED
-
Not serious
Non-critical
-
Jul 9, 2025 Routine · 1 critical, 2 non-critical
-
Not serious
Non-critical
OPERATING REPORTS-ANTI-ENTRAPMENT
The operator did not record the following on the operating report: dates of anti-entrapment system testing verification.
Correction: Record the following on the operating report, dates of anti-entrapment system testing verification.
Code ATCP 76.32(1)(e) - ANTIENTRAP TEST
-
Not serious
Non-critical
SOAP-PROVIDED
Soap not provided in permanently-installed dispensing device at each shower.
Correction: Provide soap in a permanently-installed dispensing device at each shower.
Code ATCP 76.33 (2)(e)1. - SOAP
-
Serious
Critical
Corrected on site
PH
The pH is 7.0.
Correction: Maintain the pH at 7.2 to 7.8. Note: *it is strongly encouraged to use a pH meter with an accuracy greater than 0.1 or better. pH was adjusted to 7.2 during the inspection.
Code ATCP 76.14(5)(c) - PH
-
Not serious
Non-critical
-
Jul 24, 2024 Routine · 1 critical, 10 non-critical
-
Not serious
Non-critical
BACKWASH PROCEDURES POSTED ON EASILY READ CHART
The backwash procedure is no conspicuously posted on an easily read chart.
Correction: Post the backwash procedure on an easily read chart.
Code ATCP 76.11(6)(a) 4. - PROCEDURE POSTED
-
Not serious
Non-critical
DOORS
Doors to chemical storage areas not marked to indicate entry is for authorized personnel only.
Correction: Lock doors to chemical storage areas and mark to indicate entry is for authorized personnel only.
Code ATCP 76.12 (2)(i) - DOORS
-
Not serious
Non-critical
EMERGENCY CONTACT PHONE NUMBERS
Emergency contact phone numbers are not in the chemical storage area or readily accessible.
Correction: Provide emergency contact numbers in the chemical storage area or readily accessible.
Code ATCP 76.12 (2)(j) - EMERGENCY CONTACT PHONE NUMBERS
-
Not serious
Non-critical
INTERLOCK-LOG KEPT
A log of the monthly interlock tests is not being kept.
Correction: Keep a log of monthly interlock tests.
Code ATCP 76.13 (1)(c)4 - INTERLOCK, LOG KEPT
-
Not serious
Non-critical
COMBINED CHLORINE PLAN PRESENT
The operator has not developed and implemented a plan to minimize combined chlorine in the pool.
Correction: Develop and implement a plan to minimize combined chlorine in the pool.
Code ATCP 76.14(5)(e)1. - PLAN PRESENT
-
Not serious
Non-critical
BIOHAZARD KIT-AVAILABLE
A biohazard kit is not available.
Correction: Provide a biohazard kit for the pool.
Code ATCP 76.27(2)(a) - BIOHAZ KIT AVAILABLE
-
Not serious
Non-critical
OPERATING REPORTS-BREAKPOINT CHLORINATION
The operator did not record the following on the operating report: The dates breakpoint chlorination was completed.
Correction: Record the following on the operating report, dates when breakpoint chlorination was completed.
Code ATCP 76.32(1)(c) - BREAKPOINT CHLOR
-
Not serious
Non-critical
OPERATING REPORTS-INTERLOCK TESTING
The operator did not record the following on the operating report: Dates of interlock tests, results and comments.
Correction: Record the following on the operating report, dates of interlock tests, results and comments.
Code ATCP 76.32(1)(d) - INTERLOCK TEST
-
Not serious
Non-critical
OPERATING REPORTS-ANTI-ENTRAPMENT
The operator did not record the following on the operating report: dates of anti-entrapment system testing verification.
Correction: Record the following on the operating report, dates of anti-entrapment system testing verification.
Code ATCP 76.32(1)(e) - ANTIENTRAP TEST
-
Not serious
Non-critical
OPERATING REPORTS-SAFETY AND RESCUE EQUIPMENT
The operator did not record the following on the operating report: Date for verification of safety and rescue equipment maintained.
Correction: Record the following on the operating report: Date for verification of safety and rescue equipment maintained.
Code ATCP 76.32(1)(g) - SAFETY AND RESCUE EQPT
-
Serious
Critical
INTERLOCK CHALLENGE TEST
Once monthly challenge testing of the chemical feeder system has not been conducted to assess the interlock.
Correction: Challenge test the chemical feeder system monthly to assess the interlock.
Code ATCP 76.13 (1)(c)3. - INTERLOCK MONTHLY TEST
-
Not serious
Non-critical
-
Jun 13, 2023 Routine · 2 non-critical
-
Not serious
Non-critical
COMBINED CHLORINE
The combined chlorine is 0.64 ppm.
Correction: Treat the pool with breakpoint chlorination using a chlorine product or a nonchlorinated oxidizer.
Code ATCP 76.14(4)(e)
-
Not serious
Non-critical
RULES MISSING - GENERAL
The following rules are missing from the posting: Diaper changing on the pool deck is prohibited.
Correction: Provide a sign in compliance with ATCP 76.29(1)(b).
Code [B] ATCP 76.29(1)(b)
-
Not serious
Non-critical
Source: Barron County Department of Health & Human Services. History last read Oct 1, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.