Anderson Park - Wading Pool
27 E RIVER AVE, Barron, WI 54812 · Barron County
Establishment
- Type
- Pool / recreational water (Wading)
- Inspected by
- Barron County Department of Health & Human Services
- License / ID
- SYOG-7QRMU9
- Status
- Permitted
- Phone
- (715) 637-3097
- Official record
- Barron County Department of Health & Human Services inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 1 | 1 | 1 |
| 2025 | 1 | 5 | 0 |
| 2024 | 1 | 13 | 1 |
| 2023 | 1 | 13 | 0 |
Inspections
-
Jul 30, 2026 Routine · 1 critical
-
Serious
Critical
Corrected on site
CO ALARM-POOL EQUIPMENT ROOM
There is a fuel-burning device in the equipment room but no functional CO alarm in the equipment room.
Correction: Provide a CO alarm in the equipment room and install per manufacturer's instructions. Corrective Action: Staff installed a CO detector in the pool equipment room.
Code ATCP 76.33(4)(d)1. -CO ALARM EQPT ROOM
-
Serious
Critical
Corrected on site
-
Jul 1, 2025 Routine · 5 non-critical, 1 repeat
-
Not serious
Non-critical
SKIMMERS REPAIRED OR REPLACED AS NEEDED
VGBA main drain covers not replaced as needed. Drain covers expired , new covers purchased but not installed.
Correction: Install new drain covers before the next season. The operator must log daily inspection of the drain cover to ensure no cracks, breaks, missing screws or other visible damage or defects are observed. The operator shall close the pool if any of the above damage or defects are observed. The pool must be closed until a compliant drain cover has been installed.
Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED
-
Not serious
Non-critical
Repeat
SPARE STRAINER BASKET OR SCREEN AVAILABLE
Spare strainer or screen not available
Correction: Provide a spare strainer or screen
Code ATCP 76.11(2)(d) 2. - SPARE STRAINER OR SCREEN
-
Not serious
Non-critical
SAFETY DATA SHEET
A safety data sheet was not available for each chemical on-site.
Correction: Maintain a safety data sheet for each chemical on site.
Code ATCP 76.12 (4)(b)1. - SAFETY DATA SHEETS
-
Not serious
Non-critical
COMBINED CHLORINE PLAN PRESENT
The operator has not developed and implemented a plan to minimize combined chlorine in the pool.
Correction: Develop and implement a plan to minimize combined chlorine in the pool.
Code ATCP 76.14(5)(e)1. - PLAN PRESENT
-
Not serious
Non-critical
WATER ATTRACTION-GATES, DOORS OPEN AWAY
A gate is in use and does not open away from the water attraction or have a self-closing and latching device.
Correction: Repair or install gates to open away from the water attraction or equip gates with a self-closing and latching device.
Code ATCP 76.36(1)(h)4. - GATES OR DOORS OPEN AWAY
-
Not serious
Non-critical
-
Jun 26, 2024 Routine · 1 critical, 12 non-critical
-
Not serious
Non-critical
SPARE STRAINER BASKET OR SCREEN AVAILABLE
Spare strainer or screen not available
Correction: Provide a spare strainer or screen
Code ATCP 76.11(2)(d) 2. - SPARE STRAINER OR SCREEN
-
Not serious
Non-critical
FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED
The valve handle on the wading pool sand filter is is broken.
Correction: Repair or replace the handle on the valve.
Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED
-
Not serious
Non-critical
LABEL, CONSPICUOUS
Chemical container for soda ash is not conspicuously labeled.
Correction: Provide a conspicuous, easily visible and read label on the chemical container.
Code ATCP 76.12 (1)(a)
-
Not serious
Non-critical
DOORS
Doors to chemical storage areas not locked and marked to indicate entry is for authorized personnel only.
Correction: Lock doors to chemical storage areas and mark to indicate entry is for authorized personnel only.
Code ATCP 76.12 (2)(i) - DOORS
-
Not serious
Non-critical
EMERGENCY CONTACT PHONE NUMBERS
Emergency contact phone numbers are not in the chemical storage area or readily accessible.
Correction: Provide emergency contact numbers in the chemical storage area or readily accessible.
Code ATCP 76.12 (2)(j) - EMERGENCY CONTACT PHONE NUMBERS
-
Not serious
Non-critical
INTERLOCK-LOG KEPT
A log of the monthly interlock tests is not being kept.
Correction: Keep a log of monthly interlock tests.
Code ATCP 76.13 (1)(c)4 - INTERLOCK, LOG KEPT
-
Not serious
Non-critical
GAS CHLORINE-TAGGED
An empty chlorine gas cylinder was not tagged to indicate it is empty.
Correction: Tag an empty chlorine gas cylinders to indicate it is empty.
Code ATCP 76.14 (3)(d) - TAGGED
-
Not serious
Non-critical
COMBINED CHLORINE PLAN RECORDS, INCLUDING COMPLAINTS
The combined chlorine plan does not include a record. Records must be maintained documenting combined chlorine test results, date and times breakpoint chlorination was performed, and any complaints of eye or respiratory irritation.
Correction: Include a record documenting combined chlorine test results, date and times breakpoint chlorination was performed, and any complaints of eye or respiratory irritation in the combined chlorine plan.
Code ATCP 76.14(5)(e)2.e. - RECORDS
-
Not serious
Non-critical
OPERATING REPORTS-INTERLOCK TESTING
The operator did not record the following on the operating report: Dates of interlock tests, results and comments.
Correction: Record the following on the operating report, dates of interlock tests, results and comments.
Code ATCP 76.32(1)(d) - INTERLOCK TEST
-
Not serious
Non-critical
OPERATING REPORTS-ANTI-ENTRAPMENT
The operator did not record the following on the operating report: dates of anti-entrapment system testing verification.
Correction: Record the following on the operating report, dates of anti-entrapment system testing verification.
Code ATCP 76.32(1)(e) - ANTIENTRAP TEST
-
Not serious
Non-critical
OPERATING REPORTS-SAFETY AND RESCUE EQUIPMENT
The operator did not record the following on the operating report: Date for verification of safety and rescue equipment maintained.
Correction: Record the following on the operating report: Date for verification of safety and rescue equipment maintained.
Code ATCP 76.32(1)(g) - SAFETY AND RESCUE EQPT
-
Not serious
Non-critical
SHOWER, TOILET, DRESSING FACILITIES-MAINTAINED
The shower, toilet and dressing facilities are not maintained in good repair. In the shower area along the floor wall junction many tiles are no longer attached to the wall.
Correction: Maintain the shower, toilet and dressing facilities in good repair.
Code ATCP 76.33 (2)(a)1. - GOOD REPAIR
-
Serious
Critical
INTERLOCK CHALLENGE TEST
Once monthly challenge testing of the chemical feeder system has not been conducted to assess the interlock.
Correction: Challenge test the chemical feeder system monthly to assess the interlock.
Code ATCP 76.13 (1)(c)3. - INTERLOCK MONTHLY TEST
-
Not serious
Non-critical
-
Jul 24, 2023 Routine · 13 non-critical, 4 repeat
-
Not serious
Non-critical
SAND FILTER BACKWASHING
The sand filter is not being backwashed in accordance with ATCP 76.11(6)(b).
Correction: Backwash the sand filter in accordance with ATCP 76.11(6)(b).
Code ATCP 76.11(6)(b)
-
Not serious
Non-critical
NO POSTED CHLORINE GAS EMERGENCY PLAN
No chlorine gas emergency plan is posted in the facility.
Correction: Author, post and practice a chlorine gas emergency plan for the facility.
Code ATCP 76.14(2)(c)(5)
-
Not serious
Non-critical
Repeat
COMBINED CHLORINE
The combined chlorine is 0.53 ppm.
Correction: Treat the pool with breakpoint chlorination using a chlorine product or a nonchlorinated oxidizer.
Code ATCP 76.14(4)(e)
-
Not serious
Non-critical
TEST KIT NOT APPROVED
The test kit (color Q) used by the facility has not been approved by the department.
Correction: Replace the test kit with one from the approved list.
Code ATCP 76.17(1)
-
Not serious
Non-critical
BIOHAZARD KIT UNAVAILABLE
No biohazard safety kit is located on the premises.
Correction: Provide a biohazard safety kit at the first aid station.
Code ATCP 76.27(2)
-
Not serious
Non-critical
OUT OF SOAP
No soap is provided in the showers
Correction: Provide soap at all hand washing sinks and showers.
Code ATCP 76.33(2)(e)
-
Not serious
Non-critical
Repeat
MAXIMUM PATRON LOAD NOT POSTED
The maximum patron load is not posted in the facility.
Correction: Post the maximum patron load in accordance with ATCP 76.29(1)(d).
Code [A] ATCP 76.29(1)(d)
-
Not serious
Non-critical
MONTHLY OPERATION REPORTS NOT SUBMITTED
Monthly operation reports are not being kept in accordance with ATCP 76.32(1).
Correction: Keep monthly operation reports in accordance with ATCP 76.32(1).
Code [A] ATCP 76.32(1)
-
Not serious
Non-critical
Repeat
NO CHLORINE GAS EMERGENCY NUMBERS
No chlorine gas emergency contact numbers are posted next to the nearest accessible phone to the chlorine gas storage room.
Correction: Post the appropriate emergency contact numbers.
Code [B] ATCP 76.14(2)(c)(3)
-
Not serious
Non-critical
NO SELF-CONTAINED BREATHING APPARATUS REPLACEMENT PARTS
The self-contained breathing apparatus that is on site is not being maintained and is not in working condition. .
Correction: Acquire the appropriate replacement parts for the self-contained breathing apparatus.
Code [B] ATCP 76.14(2)(c)(4)
-
Not serious
Non-critical
BLANKETS MISSING
2 durable blankets are not available in the pool area.
Correction: Provide 2 durable blankets in the pool area.
Code [B] ATCP 76.27(1)
-
Not serious
Non-critical
Repeat
RULES MISSING - GENERAL
Pool rules are not posted in the wading pool area
Correction: Provide a sign in compliance with ATCP 76.29(1)(b).
Code [B] ATCP 76.29(1)(b)
-
Not serious
Non-critical
FIRST AID SUPPLIES MISSING
Elastic bandage, gauze pad 4x4, and gauze pad 8x10 are missing from the first aid kit.
Correction: Provide all the items listed in ATCP 76.27(1) in the first aid kit.
Code [C] ATCP 76.27(1)
-
Not serious
Non-critical
Source: Barron County Department of Health & Human Services. History last read Oct 1, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.