Northwood Shores-pool
1876 29 3/4 AVE, Rice Lake, WI 54868 · Barron County
Establishment
- Type
- Pool / recreational water (Swimming)
- Inspected by
- Barron County Department of Health & Human Services
- License / ID
- GHUH-8GHHZW
- Status
- Permitted
- Phone
- (715) 234-1150
- Official record
- Barron County Department of Health & Human Services inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 1 | 8 | 2 |
| 2025 | 1 | 9 | 3 |
| 2024 | 1 | 17 | 1 |
| 2023 | 2 | 0 | 0 |
Inspections
-
Jun 3, 2026 Routine · 2 critical, 6 non-critical, 4 repeat
-
Not serious
Non-critical
Repeat
INTERLOCK-LOG KEPT
A log of the monthly interlock tests is not being kept.
Correction: Keep a log of monthly interlock tests.
Code ATCP 76.13 (1)(c)4 - INTERLOCK, LOG KEPT
-
Not serious
Non-critical
Repeat
COMBINED CHLORINE PLAN ACTION LEVEL
The combined chlorine plan does not include the combined chlorine action level.
Correction: Includes the combined chlorine action level in the combined chlorine plan.
Code ATCP 76.14(5)(e)2.a. - ACTION LEVEL LISTED
-
Not serious
Non-critical
Repeat
COMBINED CHLORINE PLAN SHOWERING REQUIREMENTS
The combined chlorine plan does not include description of showering requirements and how communicated to patrons.
Correction: Include a description of showering requirements and how communicated to patrons in the combined chlorine plan.
Code ATCP 76.14(5)(e)2.d. - SHOWERING REQUIREMENTS
-
Not serious
Non-critical
REAGENTS REPLACED
Test kit reagents not replaced as recommended by the manufacturer. The pH, Total Alkalinty, and CYA are expired.
Correction: Discard expired reagents. Replace test kit reagents as recommended by the manufacturer.
Code ATCP 76.17 (2)(b) - REAGENTS REPLACED
-
Not serious
Non-critical
COMBINED CHLORINE TEST
Chlorine is used and pool water is not tested at least twice a week for the combined chlorine level. Combined Chlorine should be tested twice a week, records showed it is being tested weekly.
Correction: Test pool water at least twice a week for the combined chlorine level.
Code ATCP 76.18(1)(b) - WATER TESTED COMBINED CHLORINE,
-
Not serious
Non-critical
Repeat
POOL BASIN MAINTAINED FREE OF DEFECTS
Pool basin not Maintained free of cracks or other defects and repaired or refinished as necessary to maintain it in a cleanable condition.Some cracks visible and paint is chipping on the floor of the pool.
Correction: Maintained the pool basin free of cracks or other defects, and repaired or refinished as necessary to maintain it in a cleanable condition.
Code ATCP 76.33(1)(a)2 - POOL BASIN GOOD REPAIR
-
Serious
Critical
Corrected on site
RECIRCULATION SYSTEM CONTINUOUS OPERATION
The pool recirculation system is not operational or not continuously operated. Sand filter was being bypassed in circulation system.Operator backwashed and returned circulation through sand filter
Correction: The pool must be closed immediately until the recirculation system is in place and in continuous operation. Corrective Action: Operator returned the flow to circulate through the sand filter.
Code ATCP 76.11(1) - RECIRCULATION SYSTEM PRESENT, CONTINUOUSLY O
-
Serious
Critical
Corrected on site
CLOSING CRITERIA-NON-OPERATIONAL RECIRD PUMP
The Responsible Supervisor or operator has not closed the pool when there is a nonoperational circulation pump, filter, or disinfectant or sanitizer feeder. Sand filter was being bypassed in circulation system.Operator backwashed and returned circulation through sand filter
Correction: Close the pool in the event of a nonoperational circulation pump, filter, or disinfectant or sanitizer feeder. Corrective action: Operator returned circulation to sand filter
Code ATCP 76.30 (1)(d) - NON-OPERATIONAL RECIRC PUMP
-
Not serious
Non-critical
Repeat
-
Jul 23, 2025 Routine · 3 critical, 6 non-critical, 2 repeat
-
Not serious
Non-critical
Repeat
SAFETY DATA SHEET
A safety data sheet was not available for a many of the chemicals used with the pool. Get updated SDS for all chemicals used with pool.
Correction: Maintain a safety data sheet for each chemical on site.
Code ATCP 76.12 (4)(b)1. - SAFETY DATA SHEETS
-
Not serious
Non-critical
Repeat
INTERLOCK-LOG KEPT
A log of the monthly interlock tests is not being kept.
Correction: Keep a log of monthly interlock tests.
Code ATCP 76.13 (1)(c)4 - INTERLOCK, LOG KEPT
-
Not serious
Non-critical
COMBINED CHLORINE PLAN ACTION LEVEL
The combined chlorine plan does not include the combined chlorine action level.
Correction: Includes the combined chlorine action level in the combined chlorine plan.
Code ATCP 76.14(5)(e)2.a. - ACTION LEVEL LISTED
-
Not serious
Non-critical
COMBINED CHLORINE PLAN SHOWERING REQUIREMENTS
The combined chlorine plan does not include description of showering requirements and how communicated to patrons.
Correction: Include a description of showering requirements and how communicated to patrons in the combined chlorine plan.
Code ATCP 76.14(5)(e)2.d. - SHOWERING REQUIREMENTS
-
Not serious
Non-critical
SHOWER, TOILET, DRESSING FACILITIES-MAINTAINED
The men's and women's shower facilities are not maintained in good repair. Showers have chipping paint.
Correction: Maintain the shower, toilet and dressing facilities in good repair.
Code ATCP 76.33 (2)(a)1. - GOOD REPAIR
-
Not serious
Non-critical
POOL BASIN MAINTAINED FREE OF DEFECTS
Pool basin not Maintained free of cracks or other defects and repaired or refinished as necessary to maintain it in a cleanable condition. Pool basin has chipping paint..
Correction: Maintained the pool basin free of cracks or other defects, and repaired or refinished as necessary to maintain it in a cleanable condition.
Code ATCP 76.33(1)(a)2 - POOL BASIN GOOD REPAIR
-
Serious
Critical
Corrected on site
MINIMUM DISINFECTANT RESIDUAL
Minimum disinfectant or sanitizer level is 0.95 for chlorine.
Correction: Pool closed until disinfectant level is in compliance with ATCP 76.14 Table A.
Code ATCP 76.14(5)(a) - MINIMUM DISINFECTANT RESIDUAL
-
Serious
Critical
Corrected on site
PH
The pH is 7.0.
Correction: Maintain the pH at 7.2 to 7.8. Pool pH adjusted during the inspection o appropriate level.
Code ATCP 76.14(5)(c) - PH
-
Serious
Critical
CO ALARM-POOL EQUIPMENT ROOM
There is a fuel-burning device in the pump room but no functional CO alarm in the equipment room.
Correction: Provide a CO alarm in the equipment room and install per manufacturer's instructions.
Code ATCP 76.33(4)(d)1. -CO ALARM EQPT ROOM
-
Not serious
Non-critical
Repeat
-
Jun 12, 2024 Routine · 1 critical, 16 non-critical
-
Not serious
Non-critical
PIPING LABELED, TAGGED OR CODED
The piping is not labeled so that it is easily read- labeling wearing off.
Correction: Ensure that the piping is labeled, tagged or color-coded to indicate valves, piping and direction of water flow.
Code ATCP 76.11(5m)(a) - PIPING NOT LABELED,TAGGED, CODED
-
Not serious
Non-critical
BACKWASH PROCEDURES POSTED ON EASILY READ CHART
The backwash procedure is not conspicuously posted on an easily read chart in the pump room.
Correction: Post the backwash procedure on an easily read chart.
Code ATCP 76.11(6)(a) 4. - PROCEDURE POSTED
-
Not serious
Non-critical
FILTER MEDIA INSPECTED ANNUALLY
Filter media is not being inspected annually or cleaned or replaced as necessary.
Correction: Inspect the filters annually and clean and replace media as needed.
Code ATCP 76.11(6)(a) 5. - FILTER MEDIA INSPECTED ANNUALLY
-
Not serious
Non-critical
DOORS
Doors to chemical storage areas not marked to indicate entry is for authorized personnel only.
Correction: Lock doors to chemical storage areas and mark to indicate entry is for authorized personnel only.
Code ATCP 76.12 (2)(i) - DOORS
-
Not serious
Non-critical
EMERGENCY CONTACT PHONE NUMBERS
Emergency contact phone numbers are not in the chemical storage area or readily accessible.
Correction: Provide emergency contact numbers in the chemical storage area or readily accessible.
Code ATCP 76.12 (2)(j) - EMERGENCY CONTACT PHONE NUMBERS
-
Not serious
Non-critical
SAFETY DATA SHEET
A safety data sheet was not available for a pool chemicals.
Correction: Maintain a safety data sheet for each chemical on site.
Code ATCP 76.12 (4)(b)1. - SAFETY DATA SHEETS
-
Not serious
Non-critical
INTERLOCK-LOG KEPT
A log of the monthly interlock tests is not being kept.
Correction: Keep a log of monthly interlock tests.
Code ATCP 76.13 (1)(c)4 - INTERLOCK, LOG KEPT
-
Not serious
Non-critical
COMBINED CHLORINE PLAN PRESENT
The operator has not developed and implemented a plan to minimize combined chlorine in the pool.
Correction: Develop and implement a plan to minimize combined chlorine in the pool.
Code ATCP 76.14(5)(e)1. - PLAN PRESENT
-
Not serious
Non-critical
ALKALINITY TEST
Pool water not tested at least once a week for total alkalinity.
Correction: Test pool water at least once a week for total alkalinity.
Code ATCP 76.18(1)(c) - WATER TESTED ALKALINITY
-
Not serious
Non-critical
WATER LEVEL-SKIMMERS MAINTAINED
Water level in a skimmer pool is not allowing for effective skimming.
Correction: Maintain the water level in the pool so that the skimmer weir is half submerged, or, in the case of a floating weir, used according to manufacturer's instructions.
Code ATCP 76.19(3)(a) - SKIMMERS MAINTAINED
-
Not serious
Non-critical
BIOHAZARD KIT-PAPER TOWELING
The biohazard kit is missing paper toweling.
Correction: For the biohazard kit, provide paper toweling.
Code ATCP 76.27(2)(b)5 - PAPER TOWELS
-
Not serious
Non-critical
POSTING SIGNAGE- NO PROLONGED BREATH HOLDING
Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.
Correction: Provide signage or provide other communication warning against prolonged breath holding.
Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING
-
Not serious
Non-critical
OPERATING REPORTS-BREAKPOINT CHLORINATION
The operator did not record the following on the operating report: The dates breakpoint chlorination was completed.
Correction: Record the following on the operating report, dates when breakpoint chlorination was completed.
Code ATCP 76.32(1)(c) - BREAKPOINT CHLOR
-
Not serious
Non-critical
OPERATING REPORTS-INTERLOCK TESTING
The operator did not record the following on the operating report: Dates of interlock tests, results and comments.
Correction: Record the following on the operating report, dates of interlock tests, results and comments.
Code ATCP 76.32(1)(d) - INTERLOCK TEST
-
Not serious
Non-critical
OPERATING REPORTS-ANTI-ENTRAPMENT
The operator did not record the following on the operating report: dates of anti-entrapment system testing verification.
Correction: Record the following on the operating report, dates of anti-entrapment system testing verification.
Code ATCP 76.32(1)(e) - ANTIENTRAP TEST
-
Not serious
Non-critical
OPERATING REPORTS-SAFETY AND RESCUE EQUIPMENT
The operator did not record the following on the operating report: Date for verification of safety and rescue equipment maintained.
Correction: Record the following on the operating report: Date for verification of safety and rescue equipment maintained.
Code ATCP 76.32(1)(g) - SAFETY AND RESCUE EQPT
-
Serious
Critical
INTERLOCK CHALLENGE TEST
Once monthly challenge testing of the chemical feeder system has not been conducted to assess the interlock.
Correction: Challenge test the chemical feeder system monthly to assess the interlock.
Code ATCP 76.13 (1)(c)3. - INTERLOCK MONTHLY TEST
-
Not serious
Non-critical
-
Aug 31, 2023 Re-inspection · No items found
No violations cited.
-
Aug 29, 2023 Routine · No items found
No violations cited.