Jul 30, 2026 Routine · 1 critical
-
Serious
Critical
Corrected on site
CO ALARM-POOL EQUIPMENT ROOM
There is a fuel-burning device in the equipment room but no functional CO alarm in the equipment room.
Correction: Provide a CO alarm in the equipment room and install per manufacturer's instructions. Corrected after inspection by installing CO alarm in pool equipment room.
Code ATCP 76.33(4)(d)1. -CO ALARM EQPT ROOM
-
Serious
Critical
Corrected on site
-
Jul 1, 2025 Routine · 3 non-critical
-
Not serious
Non-critical
SKIMMERS REPAIRED OR REPLACED AS NEEDED
VGBA main drain covers not replaced as needed. Drain covers expired , new covers purchased but not installed.
Correction: Install new drain covers before the next season. The operator must log daily inspection of the drain cover to ensure no cracks, breaks, missing screws or other visible damage or defects are observed. The operator shall close the pool if any of the above damage or defects are observed. The pool must be closed until a compliant drain cover has been installed.
Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED
-
Not serious
Non-critical
SAFETY DATA SHEET
Updated safety data sheets were not available for all chemicals.
Correction: Maintain a safety data sheet for each chemical on site.
Code ATCP 76.12 (4)(b)1. - SAFETY DATA SHEETS
-
Not serious
Non-critical
COMBINED CHLORINE PLAN PRESENT
The operator has not developed and implemented a plan to minimize combined chlorine in the pool.
Correction: Develop and implement a plan to minimize combined chlorine in the pool.
Code ATCP 76.14(5)(e)1. - PLAN PRESENT
-
Not serious
Non-critical
-
Jun 26, 2024 Routine · 1 critical, 11 non-critical
-
Not serious
Non-critical
LABEL, CONSPICUOUS
Chemical container for soda ash is not conspicuously labeled - container does not have a label.
Correction: Provide a conspicuous, easily visible and read label on the chemical container.
Code ATCP 76.12 (1)(a)
-
Not serious
Non-critical
DOORS
Doors to chemical storage areas not marked to indicate entry is for authorized personnel only.
Correction: Lock doors to chemical storage areas and mark to indicate entry is for authorized personnel only.
Code ATCP 76.12 (2)(i) - DOORS
-
Not serious
Non-critical
EMERGENCY CONTACT PHONE NUMBERS
Emergency contact phone numbers are not in the chemical storage area or readily accessible.
Correction: Provide emergency contact numbers in the chemical storage area or readily accessible.
Code ATCP 76.12 (2)(j) - EMERGENCY CONTACT PHONE NUMBERS
-
Not serious
Non-critical
INTERLOCK-LOG KEPT
A log of the monthly interlock tests is not being kept.
Correction: Keep a log of monthly interlock tests.
Code ATCP 76.13 (1)(c)4 - INTERLOCK, LOG KEPT
-
Not serious
Non-critical
GAS CHLORINE-TAGGED
An empty chlorine gas cylinder was not tagged to indicate it is empty.
Correction: Tag an empty chlorine gas cylinders to indicate it is empty.
Code ATCP 76.14 (3)(d) - TAGGED
-
Not serious
Non-critical
COMBINED CHLORINE PLAN RECORDS, INCLUDING COMPLAINTS
The combined chlorine plan does not include a record shall be maintained documenting combined chlorine test results, date and times breakpoint chlorination was performed, and any complaints of eye or respiratory irritation.
Correction: Include a record documenting combined chlorine test results, date and times breakpoint chlorination was performed, and any complaints of eye or respiratory irritation in the combined chlorine plan.
Code ATCP 76.14(5)(e)2.e. - RECORDS
-
Not serious
Non-critical
LIFEGUARD, ATTENDANT STAFFING PLAN-LIFEGUARD AND ATTENDANT NUMBERS
Lifeguard and attendant staffing plan does not include the number of lifeguards on duty based on square footage and patron load as requried in ATCP 76.23.
Correction: Update lifeguard and attendant staffing plan to include the number of lifeguards on duty based on square footage and patron load.
Code ATCP 76.22(1)(b)6. - LIFEGUARD, ATTENDANT NUMBERS
-
Not serious
Non-critical
OPERATING REPORTS-INTERLOCK TESTING
The operator did not record the following on the operating report: Dates of interlock tests, results and comments.
Correction: Record the following on the operating report, dates of interlock tests, results and comments.
Code ATCP 76.32(1)(d) - INTERLOCK TEST
-
Not serious
Non-critical
OPERATING REPORTS-ANTI-ENTRAPMENT
The operator did not record the following on the operating report: dates of anti-entrapment system testing verification.
Correction: Record the following on the operating report, dates of anti-entrapment system testing verification.
Code ATCP 76.32(1)(e) - ANTIENTRAP TEST
-
Not serious
Non-critical
OPERATING REPORTS-SAFETY AND RESCUE EQUIPMENT
The operator did not record the following on the operating report: Date for verification of safety and rescue equipment maintained.
Correction: Record the following on the operating report: Date for verification of safety and rescue equipment maintained.
Code ATCP 76.32(1)(g) - SAFETY AND RESCUE EQPT
-
Not serious
Non-critical
SHOWER, TOILET, DRESSING FACILITIES-MAINTAINED
The shower, toilet and dressing facilities are not maintained in good repair. Tile along floor/wall is not in good repair.
Correction: Maintain the shower, toilet and dressing facilities in good repair.
Code ATCP 76.33 (2)(a)1. - GOOD REPAIR
-
Serious
Critical
INTERLOCK CHALLENGE TEST
Once monthly challenge testing of the chemical feeder system has not been conducted to assess the interlock.
Correction: Challenge test the chemical feeder system monthly to assess the interlock.
Code ATCP 76.13 (1)(c)3. - INTERLOCK MONTHLY TEST
-
Not serious
Non-critical
-
Jul 24, 2023 Routine · 13 non-critical, 3 repeat
-
Not serious
Non-critical
SAND FILTER BACKWASHING
The high rate sand filter is not being backwashed in accordance with ATCP 76.11(6)(b). The filter is being backwashed at a differential of 5 lb/sq inch.
Correction: Backwash the sand filter in accordance with ATCP 76.11(6)(b). Backwsh the high rate sand filter at a pressure differential of 11 lb/sq inch.
Code ATCP 76.11(6)(b)
-
Not serious
Non-critical
NO POSTED CHLORINE GAS EMERGENCY PLAN
No chlorine gas emergency plan is posted in the facility.
Correction: Author, post and practice a chlorine gas emergency plan for the facility.
Code ATCP 76.14(2)(c)(5)
-
Not serious
Non-critical
Repeat
COMBINED CHLORINE
The combined chlorine is 0.95.
Correction: Treat the pool with breakpoint chlorination using a chlorine product or a nonchlorinated oxidizer.
Code ATCP 76.14(4)(e)
-
Not serious
Non-critical
TEST KIT NOT APPROVED
The test kit used by the facility has not been approved by the department (Color Q).
Correction: Replace the test kit with one from the approved list.
Code ATCP 76.17(1)
-
Not serious
Non-critical
RESCUE EQUIPMENT NOT ACCESSIBLE
Shepherd's crook is on site but not maintained in good repair.
Correction: Mount [equipment] in a readily accessible location.
Code ATCP 76.26(1)(a)
-
Not serious
Non-critical
BIOHAZARD KIT UNAVAILABLE
No biohazard safety kit is located on the premises.
Correction: Provide a biohazard safety kit at the first aid station.
Code ATCP 76.27(2)
-
Not serious
Non-critical
OUT OF SOAP
The soap dispenser in the women's locker room is empty.
Correction: Provide soap at all hand washing sinks and showers.
Code ATCP 76.33(2)(e)
-
Not serious
Non-critical
OUT OF SOAP
Soap is not continually provided at each shower in permanently installed dispensing devices.
Correction: Provide soap at all hand washing sinks and showers.
Code ATCP 76.33(2)(e)
-
Not serious
Non-critical
Repeat
NO SELF-CONTAINED BREATHING APPARATUS
The self-contained breathing apparatus available outside the chlorine gas storage room at the facility is not in working condition.
Correction: Provide a maintained self-contained breathing apparatus outside the chlorine gas storage room at the facility.
Code [A] ATCP 76.14(2)(c)(4)
-
Not serious
Non-critical
LIFEGUARD AND ATTENDANT STAFFING PLAN
The facility's lifeguard and attendant staffing plan is incomplete. The plan does not include a method of communication when 2 or more attendants or lifeguards are required for a water attraction.
Correction: Create a written plan pursuant to the requirements of ATCP 76.22 and submit it for approval.
Code [A] ATCP 76.22(1)(a)
-
Not serious
Non-critical
MONTHLY OPERATION REPORTS NOT SUBMITTED
Monthly operation reports are not being sent to Barron County DHHS in accordance with ATCP 76.32(1).
Correction: Submit monthly operation reports on a monthly basis at watertest@co.barron.wi.us.
Code [A] ATCP 76.32(1)
-
Not serious
Non-critical
Repeat
NO CHLORINE GAS EMERGENCY NUMBERS
No chlorine gas emergency contact numbers are posted next to the nearest accessible phone to the chlorine gas storage room.
Correction: Post the appropriate emergency contact numbers.
Code [B] ATCP 76.14(2)(c)(3)
-
Not serious
Non-critical
BLANKETS MISSING
2 durable blankets are not available in the pool area.
Correction: Provide 2 durable blankets in the pool area.
Code [B] ATCP 76.27(1)
-
Not serious
Non-critical
FIRST AID SUPPLIES MISSING
Elastic bandages, gauze pads (4x4"), and gauze pads (8x10") are missing from the first aid kit.
Correction: Provide all the items listed in ATCP 76.27(1) in the first aid kit.
Code [C] ATCP 76.27(1)
-