Northwoods Best Inn-pool
115 2ND ST, Chetek, WI 54728 · Barron County
Establishment
- Type
- Pool / recreational water (Swimming)
- Inspected by
- Barron County Department of Health & Human Services
- License / ID
- PWIN-BGLNZ5
- Status
- Permitted
- Phone
- (715) 924-4888
- Official record
- Barron County Department of Health & Human Services inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 1 | 11 | 0 |
| 2024 | 1 | 19 | 2 |
Inspections
-
Mar 11, 2026 Routine · 11 non-critical, 4 repeat
-
Not serious
Non-critical
COMBINED CHLORINE PLAN VOLUME OF POOL
The combined chlorine plan does not include volume of pool.
Correction: Include the volume of pool in the combined chlorine plan.
Code ATCP 76.14(5)(e)2.b.- VOLUME OF POOL
-
Not serious
Non-critical
COMBINED CHLORINE PLAN VOLUME OF SOURCE WATER ADDED-RANGE
The combined chlorine plan does not include range of volume of fresh source water added to pool each day.
Correction: Include the range of volume of fresh source water added to pool each day in the combined chlorine plan.
Code ATCP 76.14(5)(e)2.c. - VOLUME OF SOURCE WATER ADDED
-
Not serious
Non-critical
COMBINED CHLORINE PLAN SHOWERING REQUIREMENTS
The combined chlorine plan does not include description of showering requirements and how communicated to patrons.
Correction: Include a description of showering requirements and how communicated to patrons in the combined chlorine plan.
Code ATCP 76.14(5)(e)2.d. - SHOWERING REQUIREMENTS
-
Not serious
Non-critical
COMBINED CHLORINE PLAN RECORDS, INCLUDING COMPLAINTS
The combined chlorine plan does not include a record shall be maintained documenting combined chlorine test results, date and times breakpoint chlorination was performed, and any complaints of eye or respiratory irritation.
Correction: Include a record documenting combined chlorine test results, date and times breakpoint chlorination was performed, and any complaints of eye or respiratory irritation in the combined chlorine plan.
Code ATCP 76.14(5)(e)2.e. - RECORDS
-
Not serious
Non-critical
REAGENTS REPLACED
Test kit reagents not replaced as recommended by the manufacturer. Reagents are expired.
Correction: Discard expired reagents. Replace test kit reagents as recommended by the manufacturer.
Code ATCP 76.17 (2)(b) - REAGENTS REPLACED
-
Not serious
Non-critical
BIOHAZARD KIT-AVAILABLE
A biohazard kit is not available.
Correction: Provide a biohazard kit for the pool.
Code ATCP 76.27(2)(a) - BIOHAZ KIT AVAILABLE
-
Not serious
Non-critical
Repeat
OPERATING REPORTS-BREAKPOINT CHLORINATION
The operator did not record the following on the operating report: The dates breakpoint chlorination was completed.
Correction: Record the following on the operating report, dates when breakpoint chlorination was completed.
Code ATCP 76.32(1)(c) - BREAKPOINT CHLOR
-
Not serious
Non-critical
Repeat
OPERATING REPORTS-INTERLOCK TESTING
The operator did not record the following on the operating report: Dates of interlock tests, results and comments.
Correction: Record the following on the operating report, dates of interlock tests, results and comments.
Code ATCP 76.32(1)(d) - INTERLOCK TEST
-
Not serious
Non-critical
Repeat
FILES MAINTAINED PERMANENT-ATCP 76 CURRENT COPY
A copy of the most current version of ch. ATCP 76 was not permanently maintained on premises:
Correction: Maintain a copy of the most current version of ch. ATCP 76 on premises.
Code ATCP 76.32(3)(a)1. - CURRENT ATCP 76 COPY
-
Not serious
Non-critical
Repeat
SOAP-PROVIDED
Soap not provided in permanently-installed dispensing device.
Correction: Provide soap in a permanently-installed dispensing device.
Code ATCP 76.33 (2)(e)1. - SOAP
-
Not serious
Non-critical
POOL BASIN MAINTAINED FREE OF DEFECTS
Pool basin not Maintained free of cracks or other defects and repaired or refinished as necessary to maintain it in a cleanable condition. There are mulitple cracks along the bottom of the pool.
Correction: Maintained the pool basin free of cracks or other defects, and repaired or refinished as necessary to maintain it in a cleanable condition.
Code ATCP 76.33(1)(a)2 - POOL BASIN GOOD REPAIR
-
Not serious
Non-critical
-
Jan 4, 2024 Routine · 2 critical, 17 non-critical
-
Not serious
Non-critical
PIPING LABELED, TAGGED OR CODED
The piping is not fully labelled. There are labels are part of the piping but the newer pipes do not have arrows provided.
Correction: Ensure that the piping is labeled, tagged or color-coded to indicate valves, piping and direction of water flow.
Code ATCP 76.11(5m)(a) - PIPING NOT LABELED,TAGGED, CODED
-
Not serious
Non-critical
BACKWASH PROCEDURES POSTED ON EASILY READ CHART
The backwash procedure is not conspicuously posted on an easily read chart.
Correction: Post the backwash procedure on an easily read chart.
Code ATCP 76.11(6)(a) 4. - PROCEDURE POSTED
-
Not serious
Non-critical
FILTER MEDIA INSPECTED ANNUALLY
Filter media is not being inspected annually.
Correction: Inspect the filters annually and clean and replace media as needed.
Code ATCP 76.11(6)(a) 5. - FILTER MEDIA INSPECTED ANNUALLY
-
Not serious
Non-critical
EMERGENCY CONTACT PHONE NUMBERS
Emergency contact phone numbers are not in the chemical storage area or readily accessible.
Correction: Provide emergency contact numbers in the chemical storage area or readily accessible.
Code ATCP 76.12 (2)(j) - EMERGENCY CONTACT PHONE NUMBERS
-
Not serious
Non-critical
INTERLOCK-LOG KEPT
A log of the monthly interlock tests is not being kept.
Correction: Keep a log of monthly interlock tests.
Code ATCP 76.13 (1)(c)4 - INTERLOCK, LOG KEPT
-
Not serious
Non-critical
COMBINED CHLORINE PLAN PRESENT
Operator has not developed and implemented a plan to minimize comvined chlorine in the pool.
Correction: Develop and implement a combined chlorine action plan. The plan shall contain the following components: a. The combined chlorine action level, taking into account monochloramine in the source water. Note: It is recommended that an action level of 0.4 ppm be used for combined chlorine for either breakpoint chlorination or water replacement or a combination of both to occur. b. Volume of pool. c. Ra
Code ATCP 76.14(5)(e)1. - PLAN PRESENT
-
Not serious
Non-critical
Corrected on site
TELEPHONE-EMERGENCY NUMBERS AND ADDRESS
A list of emergency numbers and facility address not attached or posted near telephone.
Correction: Provide a list of emergency numbers and facility address, attached or posted near telephone or other telecommunication technology device. Corrective action: sign was made with the emergency number and facility address. The sign was posted by the cordless phone in the pool enclosure.
Code ATCP 76.26(2)(d) - TELEPHONE, EMERGENCY NUMBERS POSTED
-
Not serious
Non-critical
FIRST AID KIT -RESUSCITATION POCKET MASK
The first aid kit is missing a resuscitation pocket mask.
Correction: Provide a resuscitation pocket mask for the first aid kit.
Code ATCP 76.27(1)(b)8.- RESUSCITATION MASK
-
Not serious
Non-critical
POSTING SIGNAGE- NO PROLONGED BREATH HOLDING
Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.
Correction: Provide signage or provide other communication warning against prolonged breath holding.
Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING
-
Not serious
Non-critical
OPERATING REPORTS-BACKWASH
The operator did not record the following on the operating report: The dates on which backwashing was completed.
Correction: Record the following on the operating report, the dates when backwashing was completed.
Code ATCP 76.32(1)(b) - BACKWASH
-
Not serious
Non-critical
OPERATING REPORTS-BREAKPOINT CHLORINATION
The operator did not record the following on the operating report: The dates breakpoint chlorination was completed.
Correction: Record the following on the operating report, dates when breakpoint chlorination was completed.
Code ATCP 76.32(1)(c) - BREAKPOINT CHLOR
-
Not serious
Non-critical
OPERATING REPORTS-INTERLOCK TESTING
The operator did not record the following on the operating report: Dates of interlock tests, results and comments.
Correction: Record the following on the operating report, dates of interlock tests, results and comments.
Code ATCP 76.32(1)(d) - INTERLOCK TEST
-
Not serious
Non-critical
OPERATING REPORTS-ANTI-ENTRAPMENT
The operator did not record the following on the operating report: dates of anti-entrapment system testing verification.
Correction: Record the following on the operating report, dates of anti-entrapment system testing verification.
Code ATCP 76.32(1)(e) - ANTIENTRAP TEST
-
Not serious
Non-critical
OPERATING REPORTS-SAFETY AND RESCUE EQUIPMENT
The operator did not record the following on the operating report: Date for verification of safety and rescue equipment maintained.
Correction: Record the following on the operating report: Date for verification of safety and rescue equipment maintained.
Code ATCP 76.32(1)(g) - SAFETY AND RESCUE EQPT
-
Not serious
Non-critical
FILES MAINTAINED PERMANENT-ATCP 76 CURRENT COPY
A copy of the most current version of ch. ATCP 76 was not permanently maintained on premises.
Correction: Maintain a copy of the most current version of ch. ATCP 76 on premises.
Code ATCP 76.32(3)(a)1. - CURRENT ATCP 76 COPY
-
Not serious
Non-critical
SOAP-PROVIDED
Soap not provided in permanently-installed dispensing device.
Correction: Provide soap in a permanently-installed dispensing device.
Code ATCP 76.33 (2)(e)1. - SOAP
-
Not serious
Non-critical
POOL DECK-INDOOR-DISINFECTED
Indoor pool deck area not disinfected at least weekly with disinfecting agents according to the manufacturer’s directions. Deck area is cleaned daily but is not disinfected.
Correction: Disinfect indoor pool deck area at least weekly with disinfecting agents according to the manufacturer’s directions. Note: It is recommended to avoid the use of an ammonia-based disinfectant as this can contribute to an increased level of chloramines in the pool water.
Code ATCP 76.33(1)(b)2. - INDOOR DECK DISINFECTED
-
Serious
Critical
INTERLOCK CHALLENGE TEST
Once monthly challenge testing of the chemical feeder system has not been conducted to assess the interlock.
Correction: Challenge test the chemical feeder system monthly to assess the interlock.
Code ATCP 76.13 (1)(c)3. - INTERLOCK MONTHLY TEST
-
Serious
Critical
Corrected on site
TELEPHONE ACCESSIBLE
A telephone capable of connecting to emergency services is not working.
Correction: Provide a working telephone or other technology capable of connecting with emergency services. Corrective action: cordless phone with constant power supply was placed in the pool enclosure until the landline can be fixed.
Code ATCP 76.26(2)(a) - TELEPHONE ACCESSIBLE
-
Not serious
Non-critical
Source: Barron County Department of Health & Human Services. History last read Oct 2, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.