| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 1 | 1 | 0 |
| 2025 | 1 | 2 | 0 |
| 2024 | 1 | 2 | 1 |
Inspections
-
Feb 6, 2026 Routine · 1 non-critical
-
Not serious
Non-critical
POOL DECK-GOOD REPAIR
The ladder on the west side of the plunge pool is loose.
Correction: Maintain pool deck area in good repair.
Code ATCP 76.33(1)(b)1.a. - DECK GOOD REPAIR
-
Not serious
Non-critical
-
Jan 8, 2025 Routine · 2 non-critical, 1 repeat
-
Not serious
Non-critical
Repeat
RECIRCULATION (TURNOVER) RATE NOT MET
REPEAT: The recirculation turnover rate has not been met. The turnover rate is 1.18hrs which is above the 1hr requirement for a plunge pool.
Correction: Immediately adjust or repair equipment to operate at a proper turnover rate [Describe].
Code ATCP 76.11(4)(c) - RECIRCULATION RATE
-
Not serious
Non-critical
POOL EQUIPMENT-PROPERLY MAINTAINED
The ladder to the plunge pool is loose and can be pulled out on one side. The bolt will need to be tightened to ensure it is properly secured.
Correction: Maintain the pool equipment.
Code ATCP 76.33(1)(e)3. - MAINTENANCE OF POOL EQPT
-
Not serious
Non-critical
Repeat
-
Jan 16, 2024 Routine · 1 critical, 1 non-critical
-
Not serious
Non-critical
RECIRCULATION (TURNOVER) RATE NOT MET
The recirculation (turnover) rate has not been met. The current turnover rate is 1.29 hours and 1 hour is required for the plunge pool. When reviewing the pool construction plan it states that a turnover rate of 294 gpm is required to maintain proper turnover rates. The plunge pool is currently at 230 gpm.
Correction: Immediately adjust or repair equipment to operate at a proper turnover rate.
Code ATCP 76.11(4)(c) - RECIRCULATION RATE
-
Serious
Critical
WATER ATTRACTIONS-WATERSLIDES 6 FEET OR HIGHER, INSPECTION
A waterslide 6 feet or higher has not been inspected by an engineer or the signed report from the engineer is missing.
Correction: Have an engineer evaluate the waterslide for the structural stability and integrity of the slide and platform and maintain the signed report from the engineer.
Code ATCP 76.37(2)(c) - WATERSLIDE INSPECTED BY ENGINEER
-