Delta Hotels By Marriott Green Bay-plunge Pool

None, WI · Brown County

5cited violations
1serious tier
3inspections

Establishment

Type
Pool / recreational water (Pool - Moderate with Features)
Inspected by
Brown County Health & Human Services
Status
Permitted
Official record
Brown County Health & Human Services inspection reports

Other public records for this business

Year by year

YearInspectionsViolationsSerious
2026110
2025120
2024121

Inspections

  1. Feb 6, 2026 Routine · 1 non-critical
    • Not serious Non-critical

      POOL DECK-GOOD REPAIR

      The ladder on the west side of the plunge pool is loose.

      Correction: Maintain pool deck area in good repair.

      Code ATCP 76.33(1)(b)1.a. - DECK GOOD REPAIR

  2. Jan 8, 2025 Routine · 2 non-critical, 1 repeat
    • Not serious Non-critical Repeat

      RECIRCULATION (TURNOVER) RATE NOT MET

      REPEAT: The recirculation turnover rate has not been met. The turnover rate is 1.18hrs which is above the 1hr requirement for a plunge pool.

      Correction: Immediately adjust or repair equipment to operate at a proper turnover rate [Describe].

      Code ATCP 76.11(4)(c) - RECIRCULATION RATE

    • Not serious Non-critical

      POOL EQUIPMENT-PROPERLY MAINTAINED

      The ladder to the plunge pool is loose and can be pulled out on one side. The bolt will need to be tightened to ensure it is properly secured.

      Correction: Maintain the pool equipment.

      Code ATCP 76.33(1)(e)3. - MAINTENANCE OF POOL EQPT

  3. Jan 16, 2024 Routine · 1 critical, 1 non-critical
    • Not serious Non-critical

      RECIRCULATION (TURNOVER) RATE NOT MET

      The recirculation (turnover) rate has not been met. The current turnover rate is 1.29 hours and 1 hour is required for the plunge pool. When reviewing the pool construction plan it states that a turnover rate of 294 gpm is required to maintain proper turnover rates. The plunge pool is currently at 230 gpm.

      Correction: Immediately adjust or repair equipment to operate at a proper turnover rate.

      Code ATCP 76.11(4)(c) - RECIRCULATION RATE

    • Serious Critical

      WATER ATTRACTIONS-WATERSLIDES 6 FEET OR HIGHER, INSPECTION

      A waterslide 6 feet or higher has not been inspected by an engineer or the signed report from the engineer is missing.

      Correction: Have an engineer evaluate the waterslide for the structural stability and integrity of the slide and platform and maintain the signed report from the engineer.

      Code ATCP 76.37(2)(c) - WATERSLIDE INSPECTED BY ENGINEER

Source: Brown County Health & Human Services. History last read Oct 4, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.