Hyatt Regency Green Bay - Swim
333 MAIN ST, Green Bay, WI 54301 · Brown County
Establishment
- Type
- Pool / recreational water (Pool - Simple)
- Inspected by
- Brown County Health & Human Services
- License / ID
- RQUO-D4NT9P
- Status
- Permitted
- Phone
- (920) 432-1234
- Official record
- Brown County Health & Human Services inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 3 | 8 | 2 |
| 2025 | 1 | 4 | 1 |
| 2024 | 3 | 3 | 3 |
Inspections
-
Apr 10, 2026 Admin Follow Up · 2 non-critical, 2 repeat
-
Not serious
Non-critical
Repeat
RECIRCULATION (TURNOVER) RATE NOT MET
The recirculation (turnover) rate has not been met. The turnover rate is 6.7 hours which does not meet the requirement of 6 hours or less for a swimming pool.
Correction: Immediately adjust or repair equipment to operate at a proper turnover rate of no more than 6.0 hours. Increase flowrate to 95 GPM and backwash the filter as needed.
Code ATCP 76.11(4)(c) - RECIRCULATION RATE
-
Not serious
Non-critical
Repeat
POSTING SIGNAGE- NO PROLONGED BREATH HOLDING
REPEAT: Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.
Correction: Provide signage or provide other communication warning against prolonged breath holding.
Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING
-
Not serious
Non-critical
Repeat
-
Apr 9, 2026 Follow Up · 1 critical, 2 non-critical, 3 repeat
-
Not serious
Non-critical
Repeat
RECIRCULATION (TURNOVER) RATE NOT MET
The recirculation (turnover) rate has not been met. The turnover rate is 6.7 hours which does not meet the requirement of 6 hours or less for a swimming pool.
Correction: Immediately adjust or repair equipment to operate at a proper turnover rate of no more than 6.0 hours. Increase flowrate to 95 GPM and backwash the filter as needed.
Code ATCP 76.11(4)(c) - RECIRCULATION RATE
-
Not serious
Non-critical
Repeat
POSTING SIGNAGE- NO PROLONGED BREATH HOLDING
REPEAT: Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.
Correction: Provide signage or provide other communication warning against prolonged breath holding.
Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING
-
Serious
Critical
Repeat
HAZARDOUS CONDITION
CRITICAL: REPEAT: There is a hazardous condition at the pool. The deep end stair railing nearest the door to the pool enclosure is loose and may be difficult for a swimmer to use.
Correction: Correct the hazardous condition. Tighten the railing.
Code ATCP 76.34(1) - HAZARDOUS CONDITION AT POOL AREA
-
Not serious
Non-critical
Repeat
-
Apr 2, 2026 Routine · 1 critical, 2 non-critical, 2 repeat
-
Not serious
Non-critical
RECIRCULATION (TURNOVER) RATE NOT MET
The recirculation (turnover) rate has not been met. The turnover rate is 6.7 hours which does not meet the requirement of 6 hours or less for a swimming pool.
Correction: Immediately adjust or repair equipment to operate at a proper turnover rate of no more than 6.0 hours. Increase flowrate to 95 GPM and backwash the filter as needed.
Code ATCP 76.11(4)(c) - RECIRCULATION RATE
-
Not serious
Non-critical
Repeat
POSTING SIGNAGE- NO PROLONGED BREATH HOLDING
REPEAT: Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.
Correction: Provide signage or provide other communication warning against prolonged breath holding.
Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING
-
Serious
Critical
Repeat
HAZARDOUS CONDITION
CRITICAL: REPEAT: There is a hazardous condition at the pool. The deep end stair railing nearest the door to the pool enclosure is loose and may be difficult for a swimmer to use.
Correction: Correct the hazardous condition. Tighten the railing.
Code ATCP 76.34(1) - HAZARDOUS CONDITION AT POOL AREA
-
Not serious
Non-critical
-
Feb 25, 2025 Routine · 1 critical, 3 non-critical
-
Not serious
Non-critical
ELECTRONIC MONITORING WATER POTENTIAL
The water potential ("ORP") is 367mV and water has not been tested manually. The ORP sensor is not in good repair.
Correction: Maintain water potential between 650−900 mV, and manually test the water if the water potential reads below 650 mV or above 900 mV. Maintain the ORP sensor in good repair.
Code ATCP 76.14(6)(a) - OXIDATION POTENTIAL
-
Not serious
Non-critical
POSTING SIGNAGE- NO PROLONGED BREATH HOLDING
Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.
Correction: Provide signage or provide other communication warning against prolonged breath holding.
Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING
-
Not serious
Non-critical
FILES MAINTAINED PERMANENT-ATCP 76 CURRENT COPY
A copy of the most current version of ch. ATCP 76 was not permanently maintained on premises:
Correction: Maintain a copy of the most current version of ch. ATCP 76 on premises.
Code ATCP 76.32(3)(a)1. - CURRENT ATCP 76 COPY
-
Serious
Critical
Corrected on site
HAZARDOUS CONDITION
There is a hazardous condition at the pool. The pool stair railings in the deep end are loose. The railing was tightened during the inspection.
Correction: Correct the hazardous condition.
Code ATCP 76.34(1) - HAZARDOUS CONDITION AT POOL AREA
-
Not serious
Non-critical
-
Jul 12, 2024 Follow Up · 2 critical, 2 repeat
-
Serious
Critical
Repeat
MINIMUM DISINFECTANT RESIDUAL
Minimum disinfectant or sanitizer level is 2.0 for bromine.
Correction: Close the pool until disinfectant level is in compliance with ATCP 76.14 Table A.
Code ATCP 76.14(5)(a) - MINIMUM DISINFECTANT RESIDUAL
-
Serious
Critical
Repeat
WATER CLARITY
Pool water not transparent and free from cloudiness. Main drain grating and outline not readily visible from pool deck
Correction: Close the pool until the pool water is transparent and free from cloudiness and so that main drain grating and outline are readily visible from pool deck.
Code ATCP 76.16 (2) - CLARITY
-
Serious
Critical
Repeat
-
May 9, 2024 Pre-inspection Follow Up · No items found
No violations cited.
-
Apr 25, 2024 Pre-inspection · 1 critical
-
Serious
Critical
HAZARDOUS CONDITION
CRITICAL: There is a hazardous condition at the pool. Four tiles which are adjacent to the main drain cover are missing. The surface is not smooth and prevents a hazard to swimmers.
Correction: Correct the hazardous condition. Replace missing tiles in the pool.
Code ATCP 76.34(1) - HAZARDOUS CONDITION AT POOL AREA
-
Serious
Critical
Source: Brown County Health & Human Services. History last read Oct 4, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.