YMCA Broadview - Swimming/diving Pool

380 BROADVIEW, Green Bay, WI 54301 · Brown County

11cited violations
3serious tier
3inspections

Establishment

Type
Pool / recreational water (Combination)
Inspected by
Brown County Health & Human Services
License / ID
HSAT-7QX3YF
Status
Permitted
Phone
(920) 436-9601
Official record
Brown County Health & Human Services inspection reports

Other public records for this business

Year by year

YearInspectionsViolationsSerious
2026152
2025110
2023151

Inspections

  1. Jun 10, 2026 Routine · 2 critical, 3 non-critical
    • Not serious Non-critical

      ALKALINITY

      The total alkalinity is 40ppm.

      Correction: Maintain the total alkalinity of the water between 60 and 180 ppm as calcium carbonate or be able to demonstrate to the department or its agent that another level of total alkalinity produces chemically balanced water.

      Code ATCP 76.14(5)(d) - ALKALINITY

    • Not serious Non-critical Corrected on site

      REAGENTS REPLACED

      Facility was using expired reagents prior to the inspection. Reagents were discarded as they already had new ones at the facility.

      Correction: Discard expired reagents. Replace test kit reagents as recommended by the manufacturer.

      Code ATCP 76.17 (2)(b) - REAGENTS REPLACED

    • Not serious Non-critical

      OPERATING REPORTS-CHEMICAL TESTING

      Chemical testing is being completed as required but corrective actions are not being recoreded when disinfectant levels are out of compliance. The pool is being noted as closed properly but the levels are not being recoreded again once opened.

      Correction: Mark corrective action taken and if the pool is reopened after closing it the disinfectant and pH levels should be recorded.

      Code ATCP 76.32(1)(a) - CHEMICAL TESTING

    • Serious Critical

      SPINE BOARD

      Spinal board only has one set of straps.

      Correction: Provide a spinal board with all the strap attached to the board.

      Code ATCP 76.26(1)(d) - SPINE BOARD

    • Serious Critical

      WATER ATTRACTOIN MAINTENANCE AND REPAIR SAFE PRACTICE

      Diving board is starting to peel in several area.

      Correction: The diving board should be resurfaced eventually as the problem with continue to get worse.

      Code ATCP 76.37(1)(a) - MAINTAINED

  2. Jun 2, 2025 Routine · 1 non-critical
    • Not serious Non-critical

      DOORS

      Doors to chemical storage areas not locked.

      Correction: Lock doors to chemical storage areas and mark to indicate entry is for authorized personnel only.

      Code ATCP 76.12 (2)(i) - DOORS

  3. Dec 21, 2023 Routine · 1 critical, 4 non-critical
    • Not serious Non-critical

      INTERLOCK-LOG KEPT

      A log of the monthly interlock tests is not being kept.

      Correction: Keep a log of monthly interlock tests.

      Code ATCP 76.13 (1)(c)4 - INTERLOCK, LOG KEPT

    • Not serious Non-critical

      COMBINED CHLORINE PLAN PRESENT

      No comined clorine plan present.

      Correction: Create a combined clorine plan.

      Code ATCP 76.14(5)(e)1. - PLAN PRESENT

    • Not serious Non-critical

      POSTING SIGNAGE- NO PROLONGED BREATH HOLDING

      Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.

      Correction: Provide signage or provide other communication warning against prolonged breath holding. Signage is on order and will be installed.

      Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING

    • Not serious Non-critical

      DEATH, INJURY, ILLNESS REPORTS

      An incident requiring EMS service on 1/26/2023 was documented in the facility binder, it is unclear if the incident was reported to DATCP due to staffing changes.

      Correction: Report any incident resulting in death, serious injury, or illness that requires assistance from emergency medical personnel, by the end of the next working day following the incident by phone, email, or fax to the department or its agent.

      Code ATCP 76.32(2) - DII REPORTS

    • Serious Critical

      CO ALARM-POOL EQUIPMENT ROOM

      There is a fuel-burning device in the equipment room but no functional CO alarm in the equipment room.

      Correction: Provide a CO alarm in the equipment room and install per manufacturer's instructions.

      Code ATCP 76.33(4)(d)1. -CO ALARM EQPT ROOM

Source: Brown County Health & Human Services. History last read Oct 5, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.