Hyatt Regency Green Bay - Splashpad
333 MAIN ST, Green Bay, WI 54301 · Brown County
Establishment
- Type
- Pool / recreational water (Pool - Simple with Features)
- Inspected by
- Brown County Health & Human Services
- License / ID
- RQUO-D4NT9Z
- Status
- Permitted
- Phone
- (920) 432-1234
- Official record
- Brown County Health & Human Services inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 1 | 0 | 0 |
| 2025 | 1 | 1 | 1 |
| 2024 | 3 | 5 | 2 |
Inspections
-
Apr 2, 2026 Routine · No items found
No violations cited.
-
Feb 25, 2025 Routine · 1 critical
-
Serious
Critical
Corrected on site
MAXIMUM BROMINE
CRITICAL: The maximum total bromine exceeds 10 ppm. Bromine was measured at 12.0 ppm. The water was run and retested at the end of the inspection. The bromine residual was remeasured at 8.0 ppm.
Correction: Close the pool until the total bromine residual is in compliance with Table ATCP 76.14 Table A.
Code ATCP 76.14(5)(g) -MAXIMUM BROMINE
-
Serious
Critical
Corrected on site
-
Jul 12, 2024 Follow Up · 2 critical, 2 repeat
-
Serious
Critical
Repeat
PH
The pH is 8.0.
Correction: Maintain the pH at 7.2 to 7.8. Note: *it is strongly encouraged to use a pH meter with an accuracy greater than 0.1 or better.
Code ATCP 76.14(5)(c) - PH
-
Serious
Critical
Repeat
MAXIMUM BROMINE
The maximum total bromine exceeds 10 ppm.
Correction: Close the pool until the total bromine residual is in compliance with Table ATCP 76.14 Table A.
Code ATCP 76.14(5)(g) -MAXIMUM BROMINE
-
Serious
Critical
Repeat
-
May 9, 2024 Pre-inspection Follow Up · 1 non-critical, 1 repeat
-
Not serious
Non-critical
Repeat
CERTIFIED OPERATOR REQUIRED AT WATER ATTRACTION
The splash pad/water attraction does not have a certified operator.
Correction: Provide a certified operator for the water attraction within 90 days.
Code ATCP 76.20(2)(a)1 - CERTIFIED OPERATOR REQUIRED, WATER ATTRC
-
Not serious
Non-critical
Repeat
-
Apr 25, 2024 Pre-inspection · 2 non-critical
-
Not serious
Non-critical
FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED
The flowmeter is not being maintained in operating condition. The bobber is missing from the flowmeter.
Correction: Adjust or repair the flowmeter.
Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED
-
Not serious
Non-critical
CERTIFIED OPERATOR REQUIRED AT WATER ATTRACTION
The splash pad/water attraction does not have a certified operator.
Correction: Provide a certified operator for the water attraction within 90 days.
Code ATCP 76.20(2)(a)1 - CERTIFIED OPERATOR REQUIRED, WATER ATTRC
-
Not serious
Non-critical
Source: Brown County Health & Human Services. History last read Oct 5, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.