Hampton Inn Green Bay Downtown
201 MAIN ST, Green Bay, WI 54301 · Brown County
Establishment
- Type
- Pool / recreational water (Swimming)
- Inspected by
- Brown County Health & Human Services
- License / ID
- RQUO-AR6HLA
- Status
- Permitted
- Phone
- (920) 437-5900
- Official record
- Brown County Health & Human Services inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 1 | 0 | 0 |
| 2025 | 3 | 35 | 5 |
| 2024 | 2 | 9 | 0 |
| 2023 | 3 | 25 | 3 |
Inspections
-
Jun 30, 2026 Follow Up · No items found
No violations cited.
-
Oct 2, 2025 Follow Up · 10 non-critical, 10 repeat
-
Not serious
Non-critical
Repeat
RECIRCULATION (TURNOVER) RATE NOT MET
The recirculation (turnover) rate has not been met. The turnover rate at 65 GPM flow as measured is 6.4 hours.
Correction: Immediately adjust or repair equipment to operate at a proper turnover rate of no greater than 6 hours.
Code ATCP 76.11(4)(c) - RECIRCULATION RATE
-
Not serious
Non-critical
Repeat
RESPONSIBLE SUPERVISOR INTERLOCK TESTING
Responsible supervisor is not ensuring that monthly interlock testing is done.
Correction: Have the responsible supervisor ensure that monthly interlock tests are done.
Code ATCP 76.21 (1)(c)5.- INTERLOCK TESTING
-
Not serious
Non-critical
Repeat
TELEPHONE-EMERGENCY NUMBERS AND ADDRESS
A list of emergency numbers and facility address not attached or posted near telephone. The facility's address is not posted in the pool area.
Correction: Provide a list of emergency numbers and facility address, attached or posted near telephone or other telecommunication technology device.
Code ATCP 76.26(2)(d) - TELEPHONE, EMERGENCY NUMBERS POSTED
-
Not serious
Non-critical
Repeat
EMERGENCY BLANKETS
3 YEAR REPEAT: Two emergency blankets in good condition are not available in the pool area.
Correction: Provide two emergency blankets in good condition in the pool area.
Code ATCP 76.27(3) - EMERGENCY BLANKETS
-
Not serious
Non-critical
Repeat
POSTING SIGNAGE- NO PROLONGED BREATH HOLDING
Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.
Correction: Provide signage or provide other communication warning against prolonged breath holding.
Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING
-
Not serious
Non-critical
Repeat
FILES MAINTAINED PERMANENT-ATCP 76 CURRENT COPY
REPEAT: A copy of the most current version of ch. ATCP 76 was not permanently maintained on premises:
Correction: Maintain a copy of the most current version of ch. ATCP 76 on premises.
Code ATCP 76.32(3)(a)1. - CURRENT ATCP 76 COPY
-
Not serious
Non-critical
Repeat
FILES MAINTAINED PERMANENT-PUMP CURVE
REPEAT: The manufacturer’s pump performance curve diagram was not permanently maintained on premises:
Correction: Maintain a copy of the manufacturer’s pump performance curve diagram on the premises.
Code ATCP 76.32(3)(a)3. - PUMP CURVE
-
Not serious
Non-critical
Repeat
FILES MAINTAINED PERMANENT-CDC FECAL INCIDENTS
REPEAT: The most recent United States centers for disease control and prevention recommendations for fecal accidents or another plan in response to fecal accidents was not permanently maintained on premises:
Correction: Maintain a copy of the most recent United States centers for disease control and prevention recommendations for fecal accidents or another plan in response to fecal accidents that is consistent with the United States centers for disease control and prevention’s fecal accident response recommendations on the premises.
Code ATCP 76.32(3)(a)8. - CDC FECAL RESPONSE GUIDELINES
-
Not serious
Non-critical
Repeat
FILES MAINTAINED PERMANENT-VGBA DRAIN COVER DOCUMENTATION
The Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation was not permanently maintained on premises.
Correction: Maintain Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation on the premises.
Code ATCP 76.32(3)(a)9. - VGBA DRAIN COVER
-
Not serious
Non-critical
Repeat
SOAP-DISPENSERS OPERABLE
Soap dispenser not maintained in operable condition. There is no soap in the mens restroom.
Correction: Maintain the soap dispenser in operable condition.
Code ATCP 76.33 (2)(e)2. - SOAP DISPENSER
-
Not serious
Non-critical
Repeat
-
Oct 1, 2025 Follow Up · 1 critical, 10 non-critical, 11 repeat
-
Not serious
Non-critical
Repeat
RECIRCULATION (TURNOVER) RATE NOT MET
The recirculation (turnover) rate has not been met. The turnover rate at 65 GPM flow as measured is 6.4 hours.
Correction: Immediately adjust or repair equipment to operate at a proper turnover rate of no greater than 6 hours.
Code ATCP 76.11(4)(c) - RECIRCULATION RATE
-
Not serious
Non-critical
Repeat
RESPONSIBLE SUPERVISOR INTERLOCK TESTING
Responsible supervisor is not ensuring that monthly interlock testing is done.
Correction: Have the responsible supervisor ensure that monthly interlock tests are done.
Code ATCP 76.21 (1)(c)5.- INTERLOCK TESTING
-
Not serious
Non-critical
Repeat
TELEPHONE-EMERGENCY NUMBERS AND ADDRESS
A list of emergency numbers and facility address not attached or posted near telephone. The facility's address is not posted in the pool area.
Correction: Provide a list of emergency numbers and facility address, attached or posted near telephone or other telecommunication technology device.
Code ATCP 76.26(2)(d) - TELEPHONE, EMERGENCY NUMBERS POSTED
-
Not serious
Non-critical
Repeat
EMERGENCY BLANKETS
3 YEAR REPEAT: Two emergency blankets in good condition are not available in the pool area.
Correction: Provide two emergency blankets in good condition in the pool area.
Code ATCP 76.27(3) - EMERGENCY BLANKETS
-
Not serious
Non-critical
Repeat
POSTING SIGNAGE- NO PROLONGED BREATH HOLDING
Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.
Correction: Provide signage or provide other communication warning against prolonged breath holding.
Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING
-
Not serious
Non-critical
Repeat
FILES MAINTAINED PERMANENT-ATCP 76 CURRENT COPY
REPEAT: A copy of the most current version of ch. ATCP 76 was not permanently maintained on premises:
Correction: Maintain a copy of the most current version of ch. ATCP 76 on premises.
Code ATCP 76.32(3)(a)1. - CURRENT ATCP 76 COPY
-
Not serious
Non-critical
Repeat
FILES MAINTAINED PERMANENT-PUMP CURVE
REPEAT: The manufacturer’s pump performance curve diagram was not permanently maintained on premises:
Correction: Maintain a copy of the manufacturer’s pump performance curve diagram on the premises.
Code ATCP 76.32(3)(a)3. - PUMP CURVE
-
Not serious
Non-critical
Repeat
FILES MAINTAINED PERMANENT-CDC FECAL INCIDENTS
REPEAT: The most recent United States centers for disease control and prevention recommendations for fecal accidents or another plan in response to fecal accidents was not permanently maintained on premises:
Correction: Maintain a copy of the most recent United States centers for disease control and prevention recommendations for fecal accidents or another plan in response to fecal accidents that is consistent with the United States centers for disease control and prevention’s fecal accident response recommendations on the premises.
Code ATCP 76.32(3)(a)8. - CDC FECAL RESPONSE GUIDELINES
-
Not serious
Non-critical
Repeat
FILES MAINTAINED PERMANENT-VGBA DRAIN COVER DOCUMENTATION
The Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation was not permanently maintained on premises.
Correction: Maintain Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation on the premises.
Code ATCP 76.32(3)(a)9. - VGBA DRAIN COVER
-
Not serious
Non-critical
Repeat
SOAP-DISPENSERS OPERABLE
Soap dispenser not maintained in operable condition. There is no soap in the mens restroom.
Correction: Maintain the soap dispenser in operable condition.
Code ATCP 76.33 (2)(e)2. - SOAP DISPENSER
-
Serious
Critical
Repeat
CO ALARM-POOL EQUIPMENT ROOM
CRITICAL: There is a fuel-burning device in the equipment room but no functional CO alarm in the equipment room.
Correction: Provide a CO alarm in the equipment room and install per manufacturer's instructions.
Code ATCP 76.33(4)(d)1. -CO ALARM EQPT ROOM
-
Not serious
Non-critical
Repeat
-
Sep 23, 2025 Routine · 4 critical, 10 non-critical, 4 repeat
-
Not serious
Non-critical
RECIRCULATION (TURNOVER) RATE NOT MET
The recirculation (turnover) rate has not been met. The turnover rate at 65 GPM flow as measured is 6.4 hours.
Correction: Immediately adjust or repair equipment to operate at a proper turnover rate of no greater than 6 hours.
Code ATCP 76.11(4)(c) - RECIRCULATION RATE
-
Not serious
Non-critical
RESPONSIBLE SUPERVISOR INTERLOCK TESTING
Responsible supervisor is not ensuring that monthly interlock testing is done.
Correction: Have the responsible supervisor ensure that monthly interlock tests are done.
Code ATCP 76.21 (1)(c)5.- INTERLOCK TESTING
-
Not serious
Non-critical
TELEPHONE-EMERGENCY NUMBERS AND ADDRESS
A list of emergency numbers and facility address not attached or posted near telephone. The facility's address is not posted in the pool area.
Correction: Provide a list of emergency numbers and facility address, attached or posted near telephone or other telecommunication technology device.
Code ATCP 76.26(2)(d) - TELEPHONE, EMERGENCY NUMBERS POSTED
-
Not serious
Non-critical
Repeat
EMERGENCY BLANKETS
3 YEAR REPEAT: Two emergency blankets in good condition are not available in the pool area.
Correction: Provide two emergency blankets in good condition in the pool area.
Code ATCP 76.27(3) - EMERGENCY BLANKETS
-
Not serious
Non-critical
POSTING SIGNAGE- NO PROLONGED BREATH HOLDING
Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.
Correction: Provide signage or provide other communication warning against prolonged breath holding.
Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING
-
Not serious
Non-critical
Repeat
FILES MAINTAINED PERMANENT-ATCP 76 CURRENT COPY
REPEAT: A copy of the most current version of ch. ATCP 76 was not permanently maintained on premises:
Correction: Maintain a copy of the most current version of ch. ATCP 76 on premises.
Code ATCP 76.32(3)(a)1. - CURRENT ATCP 76 COPY
-
Not serious
Non-critical
Repeat
FILES MAINTAINED PERMANENT-PUMP CURVE
REPEAT: The manufacturer’s pump performance curve diagram was not permanently maintained on premises:
Correction: Maintain a copy of the manufacturer’s pump performance curve diagram on the premises.
Code ATCP 76.32(3)(a)3. - PUMP CURVE
-
Not serious
Non-critical
Repeat
FILES MAINTAINED PERMANENT-CDC FECAL INCIDENTS
REPEAT: The most recent United States centers for disease control and prevention recommendations for fecal accidents or another plan in response to fecal accidents was not permanently maintained on premises:
Correction: Maintain a copy of the most recent United States centers for disease control and prevention recommendations for fecal accidents or another plan in response to fecal accidents that is consistent with the United States centers for disease control and prevention’s fecal accident response recommendations on the premises.
Code ATCP 76.32(3)(a)8. - CDC FECAL RESPONSE GUIDELINES
-
Not serious
Non-critical
FILES MAINTAINED PERMANENT-VGBA DRAIN COVER DOCUMENTATION
The Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation was not permanently maintained on premises.
Correction: Maintain Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation on the premises.
Code ATCP 76.32(3)(a)9. - VGBA DRAIN COVER
-
Not serious
Non-critical
SOAP-DISPENSERS OPERABLE
Soap dispenser not maintained in operable condition. There is no soap in the mens restroom.
Correction: Maintain the soap dispenser in operable condition.
Code ATCP 76.33 (2)(e)2. - SOAP DISPENSER
-
Serious
Critical
Corrected on site
PH
CRITICAL: The pH is 8.0. The acid container was empty at the time of the inspection. The operator replaced the acid and the pH decreased to 7.7 during the inspection.
Correction: Maintain the pH at 7.2 to 7.8. Note: *it is strongly encouraged to use a pH meter with an accuracy greater than 0.1 or better.
Code ATCP 76.14(5)(c) - PH
-
Serious
Critical
RESCUE EQUIPMENT GOOD REPAIR
CRITICAL: The rescue equipment is not in good repair. A piece of the ring buoy is peeling off.
Correction: Maintain all rescue equipment in good repair.
Code ATCP 76.26(1)(a)1. - RESCUE EQPT GOOD REPAIR
-
Serious
Critical
CO ALARM-POOL EQUIPMENT ROOM
CRITICAL: There is a fuel-burning device in the equipment room but no functional CO alarm in the equipment room.
Correction: Provide a CO alarm in the equipment room and install per manufacturer's instructions.
Code ATCP 76.33(4)(d)1. -CO ALARM EQPT ROOM
-
Serious
Critical
HAZARDOUS CONDITION
CRITICAL: There is a hazardous condition at the pool. The deep end stairs are loose and present a hazard.
Correction: Correct the hazardous condition. Repair the stairs.
Code ATCP 76.34(1) - HAZARDOUS CONDITION AT POOL AREA
-
Not serious
Non-critical
-
Oct 24, 2024 Routine · 9 non-critical, 1 repeat
-
Not serious
Non-critical
LICENSE NOT POSTED
The license is not posted for public view.
Correction: Post the license where it can be viewed by the public.
Code ATCP 76.05(7) - LICENSE POSTED
-
Not serious
Non-critical
FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED
The flowmeter is not being maintained in operating condition. The flowmeter bobber is stuck and does not accurately measure the flow rate. Pool turnover rate is unable to be measured.
Correction: Adjust or repair the flowmeter.
Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED
-
Not serious
Non-critical
INTERLOCK-LOG KEPT
A log of the monthly interlock tests is not being kept.
Correction: Keep a log of monthly interlock tests.
Code ATCP 76.13 (1)(c)4 - INTERLOCK, LOG KEPT
-
Not serious
Non-critical
Repeat
EMERGENCY BLANKETS
REPEAT: Two emergency blankets in good condition are not available in the pool area.
Correction: Provide two emergency blankets in good condition in the pool area.
Code ATCP 76.27(3) - EMERGENCY BLANKETS
-
Not serious
Non-critical
OPERATING REPORTS-ANTI-ENTRAPMENT
The operator did not record the following on the operating report: dates of anti-entrapment system testing verification.
Correction: Record the following on the operating report, dates of anti-entrapment system testing verification.
Code ATCP 76.32(1)(e) - ANTIENTRAP TEST
-
Not serious
Non-critical
FILES MAINTAINED PERMANENT-ATCP 76 CURRENT COPY
A copy of the most current version of ch. ATCP 76 was not permanently maintained on premises:
Correction: Maintain a copy of the most current version of ch. ATCP 76 on premises.
Code ATCP 76.32(3)(a)1. - CURRENT ATCP 76 COPY
-
Not serious
Non-critical
FILES MAINTAINED PERMANENT-PUMP CURVE
The manufacturer’s pump performance curve diagram was not permanently maintained on premises:
Correction: Maintain a copy of the manufacturer’s pump performance curve diagram on the premises.
Code ATCP 76.32(3)(a)3. - PUMP CURVE
-
Not serious
Non-critical
FILES MAINTAINED PERMANENT-CDC FECAL INCIDENTS
The most recent United States centers for disease control and prevention recommendations for fecal accidents or another plan in response to fecal accidents was not permanently maintained on premises:
Correction: Maintain a copy of the most recent United States centers for disease control and prevention recommendations for fecal accidents or another plan in response to fecal accidents that is consistent with the United States centers for disease control and prevention’s fecal accident response recommendations on the premises.
Code ATCP 76.32(3)(a)8. - CDC FECAL RESPONSE GUIDELINES
-
Not serious
Non-critical
POOL EQUIPMENT-PROPERLY MAINTAINED
The pool equipment is not properly maintained. ORP sensor is not functioning properly and read '-088'.
Correction: Maintain the pool equipment in good repair. Record chemical test results twice per day until the ORP sensor is fixed.
Code ATCP 76.33(1)(e)3. - MAINTENANCE OF POOL EQPT
-
Not serious
Non-critical
-
May 16, 2024 Follow Up · No items found
No violations cited.
-
Dec 11, 2023 Follow Up · 7 non-critical, 7 repeat
-
Not serious
Non-critical
Repeat
SPARE STRAINER BASKET OR SCREEN AVAILABLE
Spare strainer or screen not available.
Correction: Provide a spare strainer or screen.
Code ATCP 76.11(2)(d) 2. - SPARE STRAINER OR SCREEN
-
Not serious
Non-critical
Repeat
RECIRCULATION (TURNOVER) RATE NOT MET
The recirculation (turnover) rate has not been met. Turnover rate was calculated at 6.4 hours.
Correction: Immediately adjust or repair equipment to operate at a proper turnover rate of no more than 6.0 hours.
Code ATCP 76.11(4)(c) - RECIRCULATION RATE
-
Not serious
Non-critical
Repeat
POOL WATER TESTED BEFORE OPENING, PH AND SANITIZER
Pool water is not tested for pH and disinfectant or sanitizer residual daily before the pool is open to the public or before the pool is in use. Chemical testing is not done on the weekends.
Correction: Test pool water for pH and disinfectant or sanitizer residual daily before the pool is open to the public or before the pool is in use.
Code ATCP 76.18(1)(a)1 - POOL TESTED SANITIZER AND PH, BEFORE OPE
-
Not serious
Non-critical
Repeat
ELECTRONIC MONITORING MAINTENANCE
The electronic monitoring device has not been periodically monitored for proper functioning. ORP is currently reading at 220. pH is reading at 8.4. GM indicated that the pH sensor is reading 0.6 higher than the actual value.
Correction: Periodically monitor the electronic monitoring device to determine if it is functioning correctly, and maintain and test as appropriate.
Code ATCP 76.18(3)(b) - ELECTRONIC MONITORING DEVICE MAINTAINED
-
Not serious
Non-critical
Repeat
EMERGENCY BLANKETS
Two emergency blankets in good condition are not available in the pool area.
Correction: Provide two emergency blankets in good condition in the pool area.
Code ATCP 76.27(3) - EMERGENCY BLANKETS
-
Not serious
Non-critical
Repeat
OPERATING REPORTS-CHEMICAL TESTING
The operator did not record the following on the operating report: Results for chemical testing. Chemical testing logs are missing several weeks of chemical testing results. Chemicals are not tested on the weekends.
Correction: Record the following on the operating report, results for chemical testing.
Code ATCP 76.32(1)(a) - CHEMICAL TESTING
-
Not serious
Non-critical
Repeat
TOILET ROOMS-GOOD REPAIR
Women's restroom paper towel dispenser is not functioning and has a large crack in the exterior plastic.
Correction: Maintain toilet rooms in good repair.
Code ATCP 76.33 (2)(c)2. - TOILET ROOM GOOD REPAIR
-
Not serious
Non-critical
Repeat
-
Oct 20, 2023 Follow Up · 1 critical, 7 non-critical, 8 repeat
-
Not serious
Non-critical
Repeat
SPARE STRAINER BASKET OR SCREEN AVAILABLE
Spare strainer or screen not available.
Correction: Provide a spare strainer or screen.
Code ATCP 76.11(2)(d) 2. - SPARE STRAINER OR SCREEN
-
Not serious
Non-critical
Repeat
RECIRCULATION (TURNOVER) RATE NOT MET
The recirculation (turnover) rate has not been met. Turnover rate was calculated at 6.4 hours.
Correction: Immediately adjust or repair equipment to operate at a proper turnover rate of no more than 6.0 hours.
Code ATCP 76.11(4)(c) - RECIRCULATION RATE
-
Not serious
Non-critical
Repeat
POOL WATER TESTED BEFORE OPENING, PH AND SANITIZER
Pool water is not tested for pH and disinfectant or sanitizer residual daily before the pool is open to the public or before the pool is in use. Chemical testing is not done on the weekends.
Correction: Test pool water for pH and disinfectant or sanitizer residual daily before the pool is open to the public or before the pool is in use.
Code ATCP 76.18(1)(a)1 - POOL TESTED SANITIZER AND PH, BEFORE OPE
-
Not serious
Non-critical
Repeat
ELECTRONIC MONITORING MAINTENANCE
The electronic monitoring device has not been periodically monitored for proper functioning. ORP is currently reading at 220. pH is reading at 8.4. GM indicated that the pH sensor is reading 0.6 higher than the actual value.
Correction: Periodically monitor the electronic monitoring device to determine if it is functioning correctly, and maintain and test as appropriate.
Code ATCP 76.18(3)(b) - ELECTRONIC MONITORING DEVICE MAINTAINED
-
Not serious
Non-critical
Repeat
EMERGENCY BLANKETS
Two emergency blankets in good condition are not available in the pool area.
Correction: Provide two emergency blankets in good condition in the pool area.
Code ATCP 76.27(3) - EMERGENCY BLANKETS
-
Not serious
Non-critical
Repeat
OPERATING REPORTS-CHEMICAL TESTING
The operator did not record the following on the operating report: Results for chemical testing. Chemical testing logs are missing several weeks of chemical testing results. Chemicals are not tested on the weekends.
Correction: Record the following on the operating report, results for chemical testing.
Code ATCP 76.32(1)(a) - CHEMICAL TESTING
-
Not serious
Non-critical
Repeat
TOILET ROOMS-GOOD REPAIR
Women's restroom paper towel dispenser is not functioning and has a large crack in the exterior plastic.
Correction: Maintain toilet rooms in good repair.
Code ATCP 76.33 (2)(c)2. - TOILET ROOM GOOD REPAIR
-
Serious
Critical
Repeat
RESCUE EQUIPMENT GOOD REPAIR
CRITICAL: The rescue equipment is not in good repair. One ring buoy has a large tear on the ring. The other ring buoy has a severly frayed rope.
Correction: Maintain all rescue equipment in good repair.
Code ATCP 76.26(1)(a)1. - RESCUE EQPT GOOD REPAIR
-
Not serious
Non-critical
Repeat
-
Oct 19, 2023 Routine · 2 critical, 7 non-critical
-
Not serious
Non-critical
SPARE STRAINER BASKET OR SCREEN AVAILABLE
Spare strainer or screen not available.
Correction: Provide a spare strainer or screen.
Code ATCP 76.11(2)(d) 2. - SPARE STRAINER OR SCREEN
-
Not serious
Non-critical
RECIRCULATION (TURNOVER) RATE NOT MET
The recirculation (turnover) rate has not been met. Turnover rate was calculated at 6.4 hours.
Correction: Immediately adjust or repair equipment to operate at a proper turnover rate of no more than 6.0 hours.
Code ATCP 76.11(4)(c) - RECIRCULATION RATE
-
Not serious
Non-critical
POOL WATER TESTED BEFORE OPENING, PH AND SANITIZER
Pool water is not tested for pH and disinfectant or sanitizer residual daily before the pool is open to the public or before the pool is in use. Chemical testing is not done on the weekends.
Correction: Test pool water for pH and disinfectant or sanitizer residual daily before the pool is open to the public or before the pool is in use.
Code ATCP 76.18(1)(a)1 - POOL TESTED SANITIZER AND PH, BEFORE OPE
-
Not serious
Non-critical
ELECTRONIC MONITORING MAINTENANCE
The electronic monitoring device has not been periodically monitored for proper functioning. ORP is currently reading at 220. pH is reading at 8.4. GM indicated that the pH sensor is reading 0.6 higher than the actual value.
Correction: Periodically monitor the electronic monitoring device to determine if it is functioning correctly, and maintain and test as appropriate.
Code ATCP 76.18(3)(b) - ELECTRONIC MONITORING DEVICE MAINTAINED
-
Not serious
Non-critical
EMERGENCY BLANKETS
Two emergency blankets in good condition are not available in the pool area.
Correction: Provide two emergency blankets in good condition in the pool area.
Code ATCP 76.27(3) - EMERGENCY BLANKETS
-
Not serious
Non-critical
OPERATING REPORTS-CHEMICAL TESTING
The operator did not record the following on the operating report: Results for chemical testing. Chemical testing logs are missing several weeks of chemical testing results. Chemicals are not tested on the weekends.
Correction: Record the following on the operating report, results for chemical testing.
Code ATCP 76.32(1)(a) - CHEMICAL TESTING
-
Not serious
Non-critical
TOILET ROOMS-GOOD REPAIR
Women's restroom paper towel dispenser is not functioning and has a large crack in the exterior plastic.
Correction: Maintain toilet rooms in good repair.
Code ATCP 76.33 (2)(c)2. - TOILET ROOM GOOD REPAIR
-
Not serious
Non-critical
TOILET ROOMS-GOOD REPAIR
Toilet room not maintained in good repair. Women's restroom floor is covered in a significant amount of water from the pool drain.
Correction: Maintain toilet rooms in good repair.
Code ATCP 76.33 (2)(c)2. - TOILET ROOM GOOD REPAIR
-
Serious
Critical
MAXIMUM BROMINE
CRITICAL: The maximum total bromine exceeds 10 ppm. Bromine was measured at 25.5 PPM.
Correction: Close the pool until the total bromine residual is in compliance with Table ATCP 76.14 Table A.
Code ATCP 76.14(5)(g) -MAXIMUM BROMINE
-
Serious
Critical
RESCUE EQUIPMENT GOOD REPAIR
CRITICAL: The rescue equipment is not in good repair. One ring buoy has a large tear on the ring. The other ring buoy has a severly frayed rope.
Correction: Maintain all rescue equipment in good repair.
Code ATCP 76.26(1)(a)1. - RESCUE EQPT GOOD REPAIR
-
Not serious
Non-critical
Source: Brown County Health & Human Services. History last read Oct 5, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.