Comfort Inn & Suites
2850 S ONEIDA ST, Green Bay, WI 54304 · Brown County
Establishment
- Type
- Pool / recreational water (Pool - Moderate)
- Inspected by
- Brown County Health & Human Services
- License / ID
- MCUY-D8LLSV
- Status
- Permitted
- Phone
- (920) 497-1010
- Official record
- Brown County Health & Human Services inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 3 | 18 | 4 |
| 2025 | 1 | 1 | 1 |
| 2024 | 2 | 2 | 0 |
Inspections
-
Aug 13, 2026 Follow Up · No items found
No violations cited.
-
Jan 20, 2026 Follow Up · 1 critical, 7 non-critical, 8 repeat
-
Not serious
Non-critical
Repeat
INLETS CHECKED AND ADJUSTED
Inlets have not been checked and adjusted to ensure a uniform distribution pattern and effective skimming. The inlets are all pointed in different directions and not ensuring a uniform flow.
Correction: Check and adjust inlets to ensure a uniform distribution pattern and effective skimming as needed.
Code ATCP 76.11(2)(c) - INLETS POSITIONED
-
Not serious
Non-critical
Repeat
REAGENTS REPLACED
Test kit reagents not replaced as recommended by the manufacturer. R-0007 expired 7/25.
Correction: Discard expired reagents. Replace test kit reagents as recommended by the manufacturer.
Code ATCP 76.17 (2)(b) - REAGENTS REPLACED
-
Not serious
Non-critical
Repeat
WHIRLPOOL, THERAPY POOL, EXERCISE POOL,COMBINED CHLORINE
Chlorine is used in a swimming pool and pool water is not tested at least twice a week for the combined chlorine level. The combined chlorine level was 5.6 ppm.
Correction: Test pool water at least twice a week for the combined chlorine level. Drain pool and clean prior to reopening to patrons.
Code ATCP 76.18(2)(b) - COMBINED CHLORINE, WHIRLPOOL, EX, THERAPY
-
Not serious
Non-critical
Repeat
OPERATOR RESPONSIBILITIES
The operator has not been responsible for equipment pool maintenance / closure daily when required, proper documentation and maintenance of water quality pursuant.
Correction: Provide a pool operator who is responsible and providing active managerial control for pool maintenance / closure daily when required, proper documentation, and maintenance of water quality.
Code ATCP 76.20(1)(b) - OPERATOR RESPONSIBILITIES
-
Not serious
Non-critical
Repeat
FIRST AID KIT-EYE WASH SOLUTION
The first aid kit eye wash solution expired 5/2025.
Correction: Provide eye wash solution for the first aid kit.
Code ATCP 76.27(1)(b)5. - EYE WASH SOLUTION
-
Not serious
Non-critical
Repeat
FILES MAINTAINED PERMANENT-VGBA DRAIN COVER DOCUMENTATION
The Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation was not permanently maintained on premises. This document was not available for review during inspection. Maintenance staff had no knowledge regarding the whereabouts of this document.
Correction: Maintain Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation on the premises.
Code ATCP 76.32(3)(a)9. - VGBA DRAIN COVER
-
Not serious
Non-critical
Repeat
WATER ATTRACTOIN MAINTENANCE AND REPLACE OR REPAIR
Defective, improper, worn, or missing parts have not been replaced or repaired. The light fixture in the swimming pool is detached on one side of the pool and not safely secured from the interior wall of the pool. The fixture is also observed with a wire that is hanging from the side of the light fixture. The light bulb is dead and not functional.
Correction: Replace or repair defective, improper, worn, or missing parts.
Code ATCP 76.37(1)(c)1. - PARTS REPLACED
-
Serious
Critical
Repeat
WATER SUPPLY PROTECTION
CRITICAL HAZARD - Approved backflow or backsiphonage protection does not exist between potable water supply inlet and the overflow point of pool, makeup tank, surge tank or slurry tank and another approved device does not exist.
Correction: Provide approved backflow and backsiphonage protection between the water supply and the overflow point of any pool, makeup tank, surge tank, solution tank, or slurry tank.
Code ATCP 76.19(1) - PROTECTION
-
Not serious
Non-critical
Repeat
-
Jan 16, 2026 Routine · 3 critical, 7 non-critical
-
Not serious
Non-critical
INLETS CHECKED AND ADJUSTED
Inlets have not been checked and adjusted to ensure a uniform distribution pattern and effective skimming. The inlets are all pointed in different directions and not ensuring a uniform flow.
Correction: Check and adjust inlets to ensure a uniform distribution pattern and effective skimming as needed.
Code ATCP 76.11(2)(c) - INLETS POSITIONED
-
Not serious
Non-critical
REAGENTS REPLACED
Test kit reagents not replaced as recommended by the manufacturer. R-0007 expired 7/25.
Correction: Discard expired reagents. Replace test kit reagents as recommended by the manufacturer.
Code ATCP 76.17 (2)(b) - REAGENTS REPLACED
-
Not serious
Non-critical
WHIRLPOOL, THERAPY POOL, EXERCISE POOL,COMBINED CHLORINE
Chlorine is used in a swimming pool and pool water is not tested at least twice a week for the combined chlorine level. The combined chlorine level was 5.6 ppm.
Correction: Test pool water at least twice a week for the combined chlorine level. Drain pool and clean prior to reopening to patrons.
Code ATCP 76.18(2)(b) - COMBINED CHLORINE, WHIRLPOOL, EX, THERAPY
-
Not serious
Non-critical
OPERATOR RESPONSIBILITIES
The operator has not been responsible for equipment pool maintenance / closure daily when required, proper documentation and maintenance of water quality pursuant.
Correction: Provide a pool operator who is responsible and providing active managerial control for pool maintenance / closure daily when required, proper documentation, and maintenance of water quality.
Code ATCP 76.20(1)(b) - OPERATOR RESPONSIBILITIES
-
Not serious
Non-critical
FIRST AID KIT-EYE WASH SOLUTION
The first aid kit eye wash solution expired 5/2025.
Correction: Provide eye wash solution for the first aid kit.
Code ATCP 76.27(1)(b)5. - EYE WASH SOLUTION
-
Not serious
Non-critical
FILES MAINTAINED PERMANENT-VGBA DRAIN COVER DOCUMENTATION
The Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation was not permanently maintained on premises. This document was not available for review during inspection. Maintenance staff had no knowledge regarding the whereabouts of this document.
Correction: Maintain Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation on the premises.
Code ATCP 76.32(3)(a)9. - VGBA DRAIN COVER
-
Not serious
Non-critical
WATER ATTRACTOIN MAINTENANCE AND REPLACE OR REPAIR
Defective, improper, worn, or missing parts have not been replaced or repaired. The light fixture in the swimming pool is detached on one side of the pool and not safely secured from the interior wall of the pool. The fixture is also observed with a wire that is hanging from the side of the light fixture. The light bulb is dead and not functional.
Correction: Replace or repair defective, improper, worn, or missing parts.
Code ATCP 76.37(1)(c)1. - PARTS REPLACED
-
Serious
Critical
MINIMUM DISINFECTANT RESIDUAL
Minimum disinfectant or sanitizer level is 0.6 for chlorine.
Correction: Close the pool until disinfectant level is in compliance with ATCP 76.14 Table A.
Code ATCP 76.14(5)(a) - MINIMUM DISINFECTANT RESIDUAL
-
Serious
Critical
WATER SUPPLY PROTECTION
CRITICAL HAZARD - Approved backflow or backsiphonage protection does not exist between potable water supply inlet and the overflow point of pool, makeup tank, surge tank or slurry tank and another approved device does not exist.
Correction: Provide approved backflow and backsiphonage protection between the water supply and the overflow point of any pool, makeup tank, surge tank, solution tank, or slurry tank.
Code ATCP 76.19(1) - PROTECTION
-
Serious
Critical
Corrected on site
CLOSING CRITERIA-FAILURE TO MEET 76.16
CRITICAL HAZARD - The Responsible Supervisor or operator has not closed the pool after failure to comply with the water quality requirements. The pool disinfectant levels were below the required limits for weeks as well as on the day of the inspection but operator failed to close the pool for maintenance. Pool was closed during inspection.
Correction: Close the pool in the event of failure to comply with the water quality requirements pursuant to s. ATCP 76.16.
Code ATCP 76.30 (1)(b) - FAILURE TO MEET ATCP 76.16
-
Not serious
Non-critical
-
Mar 13, 2025 Follow Up · 1 critical, 1 repeat
-
Serious
Critical
Repeat
MINIMUM DISINFECTANT RESIDUAL
Minimum disinfectant or sanitizer level is 1.0 for chlorine.
Correction: Close the pool until disinfectant level is in compliance with ATCP 76.14 Table A.
Code ATCP 76.14(5)(a) - MINIMUM DISINFECTANT RESIDUAL
-
Serious
Critical
Repeat
-
Sep 16, 2024 Follow Up · No items found
No violations cited.
-
Sep 5, 2024 Pre-inspection · 2 non-critical
-
Not serious
Non-critical
FIRST AID KIT ITEMS
The first aid kit is present but missing items.
Correction: Replace the missing items in the first aid kit.
Code ATCP 76.27(1)(b) - FIRST AID KIT ITEMS
-
Not serious
Non-critical
WHIRLPOOLS-SIGNAGE POSTED
Whirlpool emergency shut off sign is faded and hard to read.
Correction: Replace the sign to ensure guest are able to find the shut off easily.
Code ATCP 76.29(3) - WHIRLPOOL RULES POSTED
-
Not serious
Non-critical
Source: Brown County Health & Human Services. History last read Oct 5, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.