1311 S MAPLE AVE, Green Bay, WI 54304 · Brown County

9cited violations
2serious tier
3inspections

Establishment

Type
Lodging (Tourist Rooming House - 1 TRH)
Inspected by
Brown County Health & Human Services
License / ID
RQUO-BBU5HA
Status
Permitted
Phone
(920) 713-0800
Official record
Brown County Health & Human Services inspection reports

Other public records for this business

Year by year

YearInspectionsViolationsSerious
2026172
2025110
2024110

Inspections

  1. Feb 18, 2026 Routine · 7 non-critical
    • Serious Critical

      Smoke alarms provided

      Smoke alarms are not provided as required.

      Correction: Provide smoke alarms within each individually keyed unit at the locations specified in rule.

      Code ATCP 72.18(11)(a)

    • Serious Critical

      Carbon monoxide alarms provided

      A carbon monoxide alarm is not provided as required.

      Correction: Provide carbon monoxide alarms at the locations specified in rule.

      Code ATCP 72.18(12)(a)

    • Not serious Priority Foundation

      Smoke alarm installed on each floor

      A smoke alarm is not provided on each floor level. Three levels do not have a smoke alarm.

      Correction: Provide a smoke alarm on each floor level to include a basement or ground floor and at the top of any stairway but excluding crawl spaces and unfinished attics.

      Code ATCP 72.18(11)(b)1.

    • Not serious Priority Foundation

      Smoke alarm installed outside each separate sleeping area

      A smoke alarm is not provided outside of each separate sleeping area, within 21 feet of any door to a sleeping room. The main floor and basement do not have a smoke alarm.

      Correction: Provide a smoke alarm outside of each separate sleeping area, within 21 feet of any door to a sleeping room- one outside of bedrooms on the main floor and one in the basement.

      Code ATCP 72.18(11)(b)2.

    • Not serious Priority Foundation

      Smoke alarm installed in each sleeping room

      A smoke alarm is not within each sleeping room. 5 bedrooms do not have smoke alarms within the rooms.

      Correction: Provide a smoke alarm within each sleeping room- two bedrooms on the main floor and three in the basement.

      Code ATCP 72.18(11)(b)3.

    • Not serious Priority Foundation

      Carbon monoxide alarm installation - FBA outside IKU

      A carbon monoxide alarm is not provided outside of each separate sleeping area within the individually keyed units- on the main floor and in the basement.

      Correction: Provide carbon monoxide alarm on the main floor within 21 ft of sleeping area and in basement within 21 ft of sleeping area.

      Code ATCP 72.18(12)(c)

    • Not serious Priority Foundation

      Building evacuation diagram (TRH) - posted or provided

      The building evacuation diagram is not conspicuously posted in each sleeping room or is not provided in the check-in materials.

      Correction: Post the building evacuation diagram in each sleeping room or provide in the check-in materials given to guests.

      Code ATCP 72.18(6)(b)1.

  2. Jan 28, 2025 Routine · 1 non-critical, 1 repeat
    • Not serious Non-critical Repeat

      PERMIT NOT DISPLAYED IN PUBLIC VIEW

      Current permit is not displayed conspicuously to the public.

      Correction: Post the permit in a conspicuous location to the public.

      Code ATCP 72.04 (7)

  3. Jan 5, 2024 Routine · 1 non-critical
    • Not serious Non-critical

      PERMIT NOT DISPLAYED IN PUBLIC VIEW

      Permit is not displayed conspicuously to the public.

      Correction: Post the permit in a conspicuous location to the public.

      Code ATCP 72.04 (7)

Source: Brown County Health & Human Services. History last read Oct 5, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.