RecordWell Data

The Abbey LLC

2911 BLUE ASTER BLVD, Sun Prairie, WI 53590 · Dane County

15cited violations
0serious tier
7inspections

Establishment

Type
Pool / recreational water (Swimming Pool)
Inspected by
Public Health Madison & Dane County
License / ID
LICSWD-2018-00398
Official record
Public Health Madison & Dane County inspection reports

Other public records for this business

Year by year

YearInspectionsViolationsSerious
2026130
2025130
2024120
2023170
2021100
2019100
2018100

Inspections

  1. Aug 25, 2026 Routine Inspection · No Reinspection Required
    • Not serious Action taken:

      13d - INTERLOCK DEMONSTRATION OF KNOWLEDGE AND DOCUMENTS (P)

      Operator cannot demostrate provide documentation of interlock system per requirements in ATCP 76.13(1)(c).

      Correction: Operator must be able to demostrate knowledge and provide documentation of interlock system.

      Code ATCP 76.13(1)(c)

    • Not serious Action taken: Operator installed a backf Corrected on site

      21b - BACKFLOW - HOSE BIBBS (P)

      The hose bibb by the leasing office's gate is not protected against backsiphonage.

      Correction: Install a hose bibb atmospheric vacuum breaker that meets the ASSE 1011 standard on the hose bibb.

      Code ATCP 76.33(1)(d)

    • Not serious Other Corrected on site

      34f - VGBA COVERS DOCUMENTATION (Pf)

      No documentation is available on site for VGBA main drain and/or equalizer covers showing make, model, gallons per minute rating, life span, and installation date.

      Correction: Maintain documentation (log, receipts, or affidavits from a pool service company) of VGBA covers for main drain and equalizers on site and available for review during inspection. Documentation shall include the following: 1. Make 2. Model 3. Gallons per minute rating. 4. Life span. 5. Installation date.

      Code ATCP 76.38

  2. Aug 19, 2025 Routine Inspection · No Reinspection Required
    • Not serious Action taken:

      14e - WATER POTENTIAL ORP (Pf)

      The controller is operational but the water potential could not be determined at the time of the inspection.

      Correction: Manually test the pool water and recalibrate the oxidation potential controller if needed to maintain the water potential between 650 to 850 mV.

      Code ATCP 76.14(5)(a)

    • Not serious Action taken:

      20c - WATER TESTING - POOLS (Pf)

      The water testing frequency for pH and chlorine is not in compliance with ATCP 76.18(1).

      Correction: Perform water testing in accordance with ATCP 76.18(1). Until the ORP meter is in operation, testing for pH and chlorine must be done 2 times per day.

      Code ATCP 76.18(1)

    • Not serious Other

      34f - VGBA COVERS DOCUMENTATION (Pf)

      No documentation is available on site for VGBA main drain and/or equalizer covers showing make, model, gallons per minute rating, life span, and installation date.

      Correction: Maintain documentation (log, receipts, or affidavits from a pool service company) of VGBA covers for main drain and equalizers on site and available for review during inspection. Documentation shall include the following: 1. Make 2. Model 3. Gallons per minute rating. 4. Life span. 5. Installation date.

      Code ATCP 76.38

  3. Jun 4, 2024 Re-Inspection · No Reinspection Required
    • Not serious Action taken:

      14e - WATER POTENTIAL ORP - Not Corrected

      The controller was operational but the water potential could not be read at the time of the inspection.

      Correction: Manually test the pool water and recalibrate the oxidation potential controller if needed to maintain the water potential between 650 to 850 mV.

      Code ATCP 76.14(5)(a)

    • Not serious Action taken:

      29g - DRINKING FOUNTAIN - Not Corrected

      No drinking fountain is present in the immediate pool area.

      Correction: Provide a drinking fountain or provide signage in the pool enclosure that indicates the exact location of the drinking fountain in lettering that is a minimum of 1 inch in height.

      Code ATCP 76.33(1)(g)

  4. Aug 21, 2023 Routine Inspection · Reinspection Required
    • Not serious Action taken:

      14e - WATER POTENTIAL ORP

      The controller was operational but the water potential could not be read at the time of the inspection.

      Correction: Manually test the pool water and recalibrate the oxidation potential controller if needed to maintain the water potential between 650 to 850 mV.

      Code ATCP 76.14(5)(a)

    • Not serious Action taken:

      20c - WATER TESTING - POOLS

      The water testing frequency for pH and chlorine is not in compliance with ATCP 76.18(1).

      Correction: Perform water testing in accordance with ATCP 76.18(1). Until the ORP meter is in operation, testing for pH and chlorine must be done 2 times per day.

      Code ATCP 76.18(1)

    • Not serious Action taken:

      26m - TELEPHONE - NOT WORKING

      The emergency telephone does not work properly. The 911 operator acknowledge the call but mentioned that the address and phone number was not the one in the sign.

      Correction: Provide a functional emergency telephone immediately.

      Code ATCP 76.26(2)

    • Not serious Action taken:

      26o - EMERGENCY NUMBERS AND ADDRESS

      The emergency numbers and/or the facility's location are not posted near the designated emergency phone.

      Correction: Post the emergency numbers near the designated emergency phone.

      Code ATCP 76.26(2)

    • Not serious Action taken:

      26q - FIRST AID KIT - SUPPLIES MISSING

      Several items are missing from the first aid kit.

      Correction: The first aid kit shall contain all of the following items: (a) Gauze pads ? 4x4, (b) Gauze pads – 8x10, (c) Adhesive bandages, (d) Triangular bandages, (e) Scissors, (f) Gauze roller bandage, (g) Tweezers, (h) Adhesive tape, (i) Eye wash, (j) Elastic bandage, (k) Disposable surgical gloves, (l) Resuscitation pocket face mask, (m) Instant cold packs.

      Code ATCP 76.27(1)

    • Not serious Action taken:

      26s - BIOHAZARD SAFETY KIT

      The biohazard safety kit located on the premises is damaged.

      Correction: Provide a biohazard safety kit at the first aid station.

      Code ATCP 76.27(2)

    • Not serious Action taken:

      29g - DRINKING FOUNTAIN

      No drinking fountain is present in the immediate pool area.

      Correction: Provide a drinking fountain or provide signage in the pool enclosure that indicates the exact location of the drinking fountain in lettering that is a minimum of 1 inch in height.

      Code ATCP 76.33(1)(g)

  5. Jun 28, 2021 Routine Inspection · No Reinspection Required

    No violations cited.

  6. Aug 20, 2019 Routine Inspection · No Reinspection Required

    No violations cited.

  7. Jul 2, 2018 Pre-Inspection · No Reinspection Required

    No violations cited.

Source: Public Health Madison & Dane County. History last read Oct 1, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.