RecordWell Data

Southtowne Reserve Apts I Pool

333 SOUTHTOWNE DR, South Milwaukee, WI 53172 · Milwaukee County

43cited violations
4serious tier
15inspections

Establishment

Type
Pool / recreational water (Pool - Simple)
Inspected by
Environmental Health Consortium (Cudahy, South Milwaukee, St. Francis)
License / ID
CMAL-CU3JTC
Status
Permitted
Phone
(920) 413-1471
Official record
Environmental Health Consortium (Cudahy, South Milwaukee, St. Francis) inspection reports

Other public records for this business

Year by year

YearInspectionsViolationsSerious
2026221
20254152
20244101
20235160

Inspections

  1. Jun 9, 2026 Follow Up · No items found

    No violations cited.

  2. May 13, 2026 Routine · 1 critical, 1 non-critical
    • Not serious Non-critical

      TELEPHONE-EMERGENCY NUMBERS AND ADDRESS

      An emergency phone number not attached or posted near telephone.

      Correction: Provide an emergency number near telephone.

      Code ATCP 76.26(2)(d) - TELEPHONE, EMERGENCY NUMBERS POSTED

    • Serious Critical

      DRINKING FOUNTAIN PROVIDED

      The drinking fountain is not working.

      Correction: Provide a working drinking fountain within 300 feet walking distance.

      Code ATCP 76.33(1)(g)1. DRINKING FOUNTAIN PROVIDED

  3. Jul 1, 2025 Follow Up · No items found

    No violations cited.

  4. Jun 26, 2025 Follow Up · 1 critical, 6 non-critical, 7 repeat
    • Not serious Non-critical Repeat

      RECIRCULATION (TURNOVER) RATE NOT MET

      Unable to determine pool turnover rate.

      Correction: Immediately adjust or repair equipment to operate at a proper turnover rate.

      Code ATCP 76.11(4)(c) - RECIRCULATION RATE

    • Not serious Non-critical Repeat

      FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED

      The flowmeter is not being maintained in operating condition.

      Correction: Adjust or repair the flowmeter so that it reads 140gpm or above.

      Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED

    • Not serious Non-critical Repeat

      BACKWASH PROCEDURES POSTED ON EASILY READ CHART

      The backwash procedure is not conspicuously posted on an easily read chart.

      Correction: Post the backwash procedure on an easily read chart.

      Code ATCP 76.11(6)(a) 4. - PROCEDURE POSTED

    • Not serious Non-critical Repeat

      BIOHAZARD KIT-AVAILABLE

      A biohazard kit is not available.

      Correction: Provide a biohazard kit for the pool.

      Code ATCP 76.27(2)(a) - BIOHAZ KIT AVAILABLE

    • Not serious Non-critical Repeat

      POOL RULES SIGNAGE-SHOWER

      Pool rules missing rule: Shower immediately before entering the pool and after use of a steam room, sauna, or toilet facilities.

      Correction: Include pool rule on sign: Shower immediately before entering the pool and after use of a steam room, sauna, or toilet facilities.

      Code ATCP 76.29(1)(b)1.c. - SHOWER

    • Not serious Non-critical Repeat

      TOILET ROOMS-CLEAN

      Bathrooms are in need of cleaning.

      Correction: Keep the toilet rooms clean.

      Code ATCP 76.33 (2)(c)1. TOILET ROOM CLEAN

    • Serious Critical Repeat

      PH

      The pH appears to be 7.0.

      Correction: Maintain the pH at 7.2 to 7.8. Note: *it is strongly encouraged to use a pH meter with an accuracy greater than 0.1 or better.

      Code ATCP 76.14(5)(c) - PH

  5. Jun 4, 2025 Follow Up · No items found

    No violations cited.

  6. Jun 3, 2025 Routine · 1 critical, 7 non-critical, 1 repeat
    • Not serious Non-critical Repeat

      RECIRCULATION (TURNOVER) RATE NOT MET

      Unable to determine pool turnover rate.

      Correction: Immediately adjust or repair equipment to operate at a proper turnover rate.

      Code ATCP 76.11(4)(c) - RECIRCULATION RATE

    • Not serious Non-critical

      FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED

      The flowmeter is not being maintained in operating condition.

      Correction: Adjust or repair the flowmeter so that it reads 140gpm or above.

      Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED

    • Not serious Non-critical

      BACKWASH PROCEDURES POSTED ON EASILY READ CHART

      The backwash procedure is not conspicuously posted on an easily read chart.

      Correction: Post the backwash procedure on an easily read chart.

      Code ATCP 76.11(6)(a) 4. - PROCEDURE POSTED

    • Not serious Non-critical

      COMBINED CHLORINE PLAN PRESENT

      There is no combined chlorine plan for facility.

      Correction: Create combined chlorine plan and forward to health department. Keep plan on file.

      Code ATCP 76.14(5)(e)1. - PLAN PRESENT

    • Not serious Non-critical

      BIOHAZARD KIT-AVAILABLE

      A biohazard kit is not available.

      Correction: Provide a biohazard kit for the pool.

      Code ATCP 76.27(2)(a) - BIOHAZ KIT AVAILABLE

    • Not serious Non-critical

      POOL RULES SIGNAGE-SHOWER

      Pool rules missing rule: Shower immediately before entering the pool and after use of a steam room, sauna, or toilet facilities.

      Correction: Include pool rule on sign: Shower immediately before entering the pool and after use of a steam room, sauna, or toilet facilities.

      Code ATCP 76.29(1)(b)1.c. - SHOWER

    • Not serious Non-critical

      TOILET ROOMS-CLEAN

      Bathrooms are in need of cleaning.

      Correction: Keep the toilet rooms clean.

      Code ATCP 76.33 (2)(c)1. TOILET ROOM CLEAN

    • Serious Critical

      PH

      The pH appears to be 7.0.

      Correction: Maintain the pH at 7.2 to 7.8. Note: *it is strongly encouraged to use a pH meter with an accuracy greater than 0.1 or better.

      Code ATCP 76.14(5)(c) - PH

  7. Aug 27, 2024 Re-inspection 2 · 1 non-critical
    • Not serious Non-critical

      CERTIFIED OPERATOR REQUIRED AFTER 2 OR MORE REINSPECTIONS IN 3 YEARS

      A pool that is required to have a certified operator does not have one.

      Correction: Provide a certified operator for the pool.

      Code ATCP 76.20(2)(a)2 - CERTIFIED OPERATOR REQUIRED, REINSPECTIO

  8. Jun 20, 2024 Re-inspection · 1 non-critical, 1 repeat
    • Not serious Non-critical Repeat

      RECIRCULATION (TURNOVER) RATE NOT MET

      The flow meter is reading about 65 gpm. The recirculation (turnover) rate is 13 hours which means that the water is not circulating fast enough.

      Correction: Immediately adjust or repair equipment to operate at a proper turnover rate of 6 hours. Flow meter be reading around 140 gpm.

      Code ATCP 76.11(4)(c) - RECIRCULATION RATE

  9. May 31, 2024 Follow Up · 3 non-critical, 3 repeat
    • Not serious Non-critical Repeat

      RECIRCULATION (TURNOVER) RATE NOT MET

      The flow meter is reading about 70 gpm. The recirculation (turnover) rate is 12 hours which means that the water is not circulating fast enough.

      Correction: Immediately adjust or repair equipment to operate at a proper turnover rate of 6 hours. Flow meter be reading around 140 gpm.

      Code ATCP 76.11(4)(c) - RECIRCULATION RATE

    • Not serious Non-critical Repeat

      FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED

      One filter pressure gauge is reading 0psi and is not being maintained in operating condition.

      Correction: Adjust or repair the filter pressure gauge that is reading 0 psi

      Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED

    • Not serious Non-critical Repeat

      VGBA-DRAIN COVER INFO-DOCUMENTS-DRAIN COVER LOG PRESENT

      The operator does not have a log that can be used to evaluate the drain covers, and there is no alternative form of proof available about drain cover replacement. Main drain and eqaulizer covers expired April 2024.

      Correction: Maintain a log that can be used to evaluate the drain covers, or keep receipts or affidavits that show make and model of drain cover.

      Code ATCP 76.38(2)(a) - DRAIN COVER LOG

  10. May 23, 2024 Routine · 1 critical, 4 non-critical
    • Not serious Non-critical

      SKIMMERS MAINTAINED CLEAN

      Skimmer baskets are full of leaves and debris.

      Correction: Maintain the skimmers in clean condition.

      Code ATCP 76.11(2)(b) 1. - SKIMMERS CLEAN

    • Not serious Non-critical

      RECIRCULATION (TURNOVER) RATE NOT MET

      The flow meter is reading about 70 gpm. The recirculation (turnover) rate is 12 hours which means that the water is not circulating fast enough.

      Correction: Immediately adjust or repair equipment to operate at a proper turnover rate of 6 hours. Flow meter should be reading around 140 gpm.

      Code ATCP 76.11(4)(c) - RECIRCULATION RATE

    • Not serious Non-critical

      FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED

      One filter pressure gauge is reading 0psi and is not being maintained in operating condition.

      Correction: Adjust or repair the filter pressure gauge that is reading 0 psi

      Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED

    • Not serious Non-critical

      VGBA-DRAIN COVER INFO-DOCUMENTS-DRAIN COVER LOG PRESENT

      The operator does not have a log that can be used to evaluate the drain covers, and there is no alternative form of proof available about drain cover replacement. Main drain and eqaulizer covers expired April 2024.

      Correction: Maintain a log that can be used to evaluate the drain covers, or keep receipts or affidavits that show make and model of drain cover.

      Code ATCP 76.38(2)(a) - DRAIN COVER LOG

    • Serious Critical

      TELEPHONE ACCESSIBLE

      A telephone or other approved communication technology capable of connecting to emergency services is not working.

      Correction: Provide a working telephone or other technology capable of connecting with emergency services. Someone must be in the office in case an emergency occurrs if pool wants to be open without properly funcitoning emergency phone. Put a note up so swimmers know where to go to utilize emergency phone.

      Code ATCP 76.26(2)(a) - TELEPHONE ACCESSIBLE

  11. Aug 28, 2023 Follow Up · 2 non-critical, 1 repeat
    • Not serious Non-critical Repeat

      RECIRCULATION RATE NOT MET - POOLS

      The flowmeter is reading 60 gpm meaning the pool has a turnover rate of 14 hrs. The max for a swimming pool is supposed to be 6 hours.

      Correction: Immediately adjust or repair the equipment to operate at a proper turnover rate.

      Code ATCP 76.11(4)(a)

    • Not serious Non-critical

      SKIMMER BASKET OR WEIR MISSING

      The pool is missing two weir doors.

      Correction: Replace the missing equipment.

      Code [B] ATCP 76.11(2)(b)

  12. Aug 24, 2023 Follow Up · 2 non-critical, 2 repeat
    • Not serious Non-critical Repeat

      RECIRCULATION RATE NOT MET - POOLS

      The flowmeter is reading 60 gpm meaning the pool has a turnover rate of 14 hrs. The max for a swimming pool is supposed to be 6 hours.

      Correction: Immediately adjust or repair the equipment to operate at a proper turnover rate.

      Code ATCP 76.11(4)(a)

    • Not serious Non-critical Repeat

      SKIMMER BASKET OR WEIR MISSING

      The pool is missing two weir doors.

      Correction: Replace the missing equipment.

      Code [B] ATCP 76.11(2)(b)

  13. Aug 3, 2023 Follow Up · 2 non-critical, 1 repeat
    • Not serious Non-critical

      RECIRCULATION RATE NOT MET - POOLS

      The flowmeter is reading 60 gpm meaning the pool has a turnover rate of 14 hrs. The max for a swimming pool is supposed to be 6 hours.

      Correction: Immediately adjust or repair the equipment to operate at a proper turnover rate.

      Code ATCP 76.11(4)(a)

    • Not serious Non-critical Repeat

      SKIMMER BASKET OR WEIR MISSING

      The pool is missing two weir doors.

      Correction: Replace the missing equipment.

      Code [B] ATCP 76.11(2)(b)

  14. Jul 19, 2023 Follow Up · 5 non-critical, 5 repeat
    • Not serious Non-critical Repeat

      PERMIT DOES NOT REFLECT CURRENT OWNERSHIP

      The permit does not reflect the current ownership.

      Correction: The operator must acquire a valid permit. Submit application and fees for pool license.

      Code ATCP 76.05(1)(b)(2)

    • Not serious Non-critical Repeat

      RECIRCULATION RATE NOT MET - POOLS

      Unable to calculate turnover rate for pool.

      Correction: Immediately adjust or repair the equipment to operate at a proper turnover rate.

      Code ATCP 76.11(4)(a)

    • Not serious Non-critical Repeat

      FLOWMETER, VALVES AND GAUGES NOT FUNCTIONAL

      The flowmeter is not in working condition

      Correction: Repair or replace the specified equipment so an accurate reading can be recorded.

      Code ATCP 76.11(5)

    • Not serious Non-critical Repeat

      SKIMMER BASKET OR WEIR MISSING

      The pool is missing two weir doors.

      Correction: Replace the missing equipment.

      Code [B] ATCP 76.11(2)(b)

    • Not serious Non-critical Repeat

      EMERGENCY CONTACT PHONE NUMBERS NOT POSTED

      The emergency numbers or facility address are not posted near the designated emergency phone.

      Correction: Post the emergency numbers and facility address near the designated emergency phone.

      Code [C] ATCP 76.26(2)

  15. Jun 21, 2023 Pre-inspection · 5 non-critical
    • Not serious Non-critical

      PERMIT DOES NOT REFLECT CURRENT OWNERSHIP

      The permit does not reflect the current ownership.

      Correction: The operator must acquire a valid permit. Submit application and fees for pool license.

      Code ATCP 76.05(1)(b)(2)

    • Not serious Non-critical

      RECIRCULATION RATE NOT MET - POOLS

      Unable to calculate turnover rate for pool.

      Correction: Immediately adjust or repair the equipment to operate at a proper turnover rate.

      Code ATCP 76.11(4)(a)

    • Not serious Non-critical

      FLOWMETER, VALVES AND GAUGES NOT FUNCTIONAL

      The flowmeter is not in working condition

      Correction: Repair or replace the specified equipment so an accurate reading can be recorded.

      Code ATCP 76.11(5)

    • Not serious Non-critical

      SKIMMER BASKET OR WEIR MISSING

      The pool is missing two weir doors.

      Correction: Replace the missing equipment.

      Code [B] ATCP 76.11(2)(b)

    • Not serious Non-critical

      EMERGENCY CONTACT PHONE NUMBERS NOT POSTED

      The emergency numbers or facility address are not posted near the designated emergency phone.

      Correction: Post the emergency numbers and facility address near the designated emergency phone.

      Code [C] ATCP 76.26(2)

Source: Environmental Health Consortium (Cudahy, South Milwaukee, St. Francis). History last read Oct 5, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.