Clement Manor Retirement Community
9405 W HOWARD AVE, Greenfield, WI 53228 · Milwaukee County
Establishment
- Type
- Pool / recreational water (Pool - Simple)
- Inspected by
- Greenfield Health Department
- License / ID
- HSAT-7QX6R2
- Status
- Permitted
- Phone
- (414) 546-7374
- Official record
- Greenfield Health Department inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 1 | 10 | 2 |
| 2025 | 1 | 2 | 0 |
| 2024 | 2 | 2 | 2 |
Inspections
-
Aug 11, 2026 Routine · 2 critical, 8 non-critical
-
Not serious
Non-critical
Corrected on site
SKIMMER POOL RECIRCULATION FLOW
Observed the proportion of water recirculating from skimmer and main drain are both partially like 50 pecrent. Provided education to PIC and PIC adjusted the skimmer valve and it is fully opened and main drainer is partially opened.
Correction: Adjust equipment so that proportion of water recirculating from skimmer and main drain is mostly from skimmer.
Code ATCP 76.11(2)(a) 2. b. - SKIMMER POOL RECIRCULATION FLOW
-
Not serious
Non-critical
SKIMMER COVERS SECURELY SEATED ON DECK
Observed skimmer covers not securely seated on deck. Observed lid is missing screw. Informed PIC and PIC stated they will get the screw in place.
Correction: Ensure that skimmer covers are securely seated on deck.
Code ATCP 76.11(2)(b) 3. - SKIMMER COVERS SECURE ON DECK
-
Not serious
Non-critical
SPARE STRAINER BASKET OR SCREEN AVAILABLE
Observed no spare strainer basket for provided. Instructed PIC to get a spare basket for the pump. PIC stated they will get a spare basket for the pump.
Correction: Provide a spare strainer or screen
Code ATCP 76.11(2)(d) 2. - SPARE STRAINER OR SCREEN
-
Not serious
Non-critical
DOORS
Observed the doors to chemical storage areas are locked but are not marked to indicate entry is for authorized personnel only. Instructed PIC to post a sign stating authorized personnel only.
Correction: Lock doors to chemical storage areas and mark to indicate entry is for authorized personnel only.
Code ATCP 76.12 (2)(i) - DOORS
-
Not serious
Non-critical
TEST KIT APPROVED
Observed the establishment is not using an approved test according to ATCP 76.17 Table A. Establishment is using a Color Q. Provided educationa and will email PIC approved list.
Correction: Establishment must use a approved Test Kit according to ATCP 76.17 Table A.
Code ATCP 76.17 (1) - DEPARTMENT-APPROVED
-
Not serious
Non-critical
POOL DECK-DEPTH MARKINGS MAINTAINED
Observed the pool deck area not maintained so that depth markings along the edge of the pool are clearly visible and readable.Observed the tile for 6 inches is missing from 4ft 6inches. PIC stated they will get the tile back on.
Correction: Maintain pool deck area so that depth markings along the edge of the pool are clearly visible and readable.
Code ATCP 76.33(1)(b)4. - DEPTH MARKINGS
-
Not serious
Non-critical
POOL EQUIPMENT-PROPERLY MAINTAINED
Observed the pool equipment is not properly maintained. Observed sand filter is leaking. Informed PIC and PIC stated they will get a work order in to fix the filter.
Correction: Maintain the pool equipment.
Code ATCP 76.33(1)(e)3. - MAINTENANCE OF POOL EQPT
-
Not serious
Non-critical
ELECTRICAL GOOD REPAIR
Observed the electrical equipment and lighting not maintained in good repair. Observed the pool lights are not operatinal. PIC is aware and is going to fix the burnt out light bulbs.
Correction: Maintain electrical equipment and lighting in good repair and in operating condition.
Code ATCP 76.33(4)(c) - GOOD REPAIR
-
Serious
Critical
Corrected on site
CO ALARM-POOL AREA
Observed there is a fuel-burning device in the equipment room located in the indoor pool area pool but no functional CO alarm is provided in the indoor pool area. Informed PIC and PIC was able to install a new CO alarm.
Correction: Provide a CO alarm in the pool area and install per manufacturer's instructions.
Code ATCP 76.33(4)(d)2- CO ALARM POOL AREA
-
Serious
Critical
Corrected on site
VGBA-EXISTING POOLS, PUMP CURVE AND DRAIN COVER INFO
Observed the operator of an existing pool does not have the pump curve. Look at pump manual and PIC also could not locate pump curve in manual. PIC was able to find the pump curve online.
Correction: Obtain a pump curve and information that describes make, model and gpm rating for the drain covers.
Code ATCP 76.38(1)(b) - PUMP CURVE
-
Not serious
Non-critical
Corrected on site
-
Jul 22, 2025 Routine · 2 non-critical
-
Not serious
Non-critical
CURRENT LICENSE
A pool, opened to the public, is located on the premises does not have a current license.
Correction: The pool must be closed to the public immediately and may not operate until a valid license is issued from the department.
Code ATCP 76.05(1)(a) - LICENSE CURRENT
-
Not serious
Non-critical
POSTING SIGNAGE- NO PROLONGED BREATH HOLDING
Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.
Correction: Provide signage or provide other communication warning against prolonged breath holding.
Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING
-
Not serious
Non-critical
-
Apr 11, 2024 Follow Up · No items found
No violations cited.
-
Apr 10, 2024 Routine · 2 critical
-
Serious
Critical
VARIANCE, APPROVED, FOLLOWED
Conditions for a variance have not been followed. The variance indicated that the PIC would be annually trained but the certificate for CPR and first aid training are inadequate.
Correction: Comply with the terms of the variance.
Code ATCP 76.02(2)(b)1 - VARIANCE, APPROVED, FOLLOWED
-
Serious
Critical
FECAL, VOMIT, BLOOD, FOLLOW CDC GUIDANCE
Following a fecal, blood or vomit incident, current CDC guidance was not documented.
Correction: Close the pool and follow disinfection guidance, available at https://www.cdc.gov/healthywater/swimming/aquatics-professionals/ for a fecal, blood or vomit incident.
Code ATCP 76.31(1) - CDC GUIDANCE FOLLOWED
-
Serious
Critical
Source: Greenfield Health Department. History last read Oct 5, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.