Blackhorse Terrace Condos

9300 W FOREST HOME AVE, Greenfield, WI 53228 · Milwaukee County

45cited violations
6serious tier
4inspections

Establishment

Type
Pool / recreational water (Pool - Moderate)
Inspected by
Greenfield Health Department
License / ID
HSAT-7QXLU5
Status
Permitted
Phone
(262) 238-1480
Official record
Greenfield Health Department inspection reports

Other public records for this business

Year by year

YearInspectionsViolationsSerious
20263375
2025181

Inspections

  1. Aug 20, 2026 Re-inspection · 5 non-critical, 5 repeat
    • Not serious Non-critical Repeat

      CURRENT LICENSE

      Observed the pool, opened to the public, is located on the premises does not have a current license. Observed license from 2022 is posted. Isntructed PIC to post current license.

      Correction: The pool must be closed to the public immediately and may not operate until a valid license is issued from the department.

      Code ATCP 76.05(1)(a) - LICENSE CURRENT

    • Not serious Non-critical Repeat

      SKIMMERS REPAIRED OR REPLACED AS NEEDED

      Observed all 4 skimers are missing weir doors. Instructed PIC to install weir doors or floating weirs.

      Correction: Repair or replace skimmer, weirs or gutters as needed.

      Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED

    • Not serious Non-critical Repeat

      SPARE STRAINER BASKET OR SCREEN AVAILABLE

      Observed there is no spare strainer basket for skimmers. Instructed PIC to have a spare skimer basket

      Correction: Provide a spare strainer or screen

      Code ATCP 76.11(2)(d) 2. - SPARE STRAINER OR SCREEN

    • Not serious Non-critical Repeat

      POSTING SIGNAGE- NO PROLONGED BREATH HOLDING

      Observed the signage or other communication warning against prolonged breath-holding is not posted or otherwise provided. Instructed PIC to post the no breath holding contest sign.

      Correction: Provide signage or provide other communication warning against prolonged breath holding.

      Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING

    • Not serious Non-critical Repeat

      POOL DECK-GOOD REPAIR

      Observed some area of the pool deck area not maintained in good repair. Observed some of the conrete has chipping and cracks. Instructed PIC to repair the affected areas of the concrete.

      Correction: Maintain pool deck area in good repair.

      Code ATCP 76.33(1)(b)1.a. - DECK GOOD REPAIR

  2. Aug 19, 2026 Re-inspection · 1 critical, 12 non-critical, 13 repeat
    • Not serious Non-critical Repeat

      SKIMMER COVERS SECURELY SEATED ON DECK

      Observed the skimmer covers not securely seated on deck. All observed all 4 skimmers are missing screws. Instructed PIC to place screws into the lids. Returned on 8/19/26 for reinspection. Observed covers do not have screws in them. This is the second repeat violation.

      Correction: Ensure that skimmer covers are securely seated on deck.

      Code ATCP 76.11(2)(b) 3. - SKIMMER COVERS SECURE ON DECK

    • Not serious Non-critical Repeat

      POOL WATER TESTED PEAK PATRON LOAD, PH AND SANITIZER

      Observed the pool water not tested for pH and disinfectant at least one other time during the day’s peak patron load. Observed the system does not have the controller is only being tested once a day. Instructed PIC it needs to be tested twice a day. Returned on 8/19/2026 for the reinspection. Observed that pH and chlorine is only being tested once a day. Informed PIC that it needs to be tested twice a day. This is the second repeat violation.

      Correction: Test pool water for pH and disinfectant at least one time during the day’s peak patron load.

      Code ATCP 76.18(1)(a)2 - WATER TESTED, SANITIZER, PH, PEAK LOAD P

    • Not serious Non-critical Repeat

      POOL EQUIPMENT-PROPERLY MAINTAINED

      Observed the drinking fountain has low pressure. Instructed PIC to repair the drinking fountain. Returnd on 8/19/26 for reinspection observed drinking is not fixed. This is the second repeat violation.

      Correction: Maintain the drinking fountain

      Code ATCP 76.33(1)(e)3. - MAINTENANCE OF POOL EQPT

    • Not serious Non-critical Repeat

      CURRENT LICENSE

      Observed the pool, opened to the public, is located on the premises does not have a current license. Observed license from 2022 is posted. Isntructed PIC to post current license.

      Correction: The pool must be closed to the public immediately and may not operate until a valid license is issued from the department.

      Code ATCP 76.05(1)(a) - LICENSE CURRENT

    • Not serious Non-critical Repeat

      SKIMMERS REPAIRED OR REPLACED AS NEEDED

      Observed all 4 skimers are missing weir doors. Instructed PIC to install weir doors or floating weirs.

      Correction: Repair or replace skimmer, weirs or gutters as needed.

      Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED

    • Not serious Non-critical Repeat

      SPARE STRAINER BASKET OR SCREEN AVAILABLE

      Observed there is no spare strainer basket for skimmers. Instructed PIC to have a spare skimer basket

      Correction: Provide a spare strainer or screen

      Code ATCP 76.11(2)(d) 2. - SPARE STRAINER OR SCREEN

    • Not serious Non-critical Repeat

      FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED

      Observed the affluent flowmeter is not being maintained in operating condition. Observed the float is stuck and not moving. Instructed PIC to repair the float in the flowmeter..

      Correction: Adjust or repair the float in the flow meter

      Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED

    • Not serious Non-critical Repeat

      BACKWASH PROCEDURES POSTED ON EASILY READ CHART

      Observed the backwash procedure is no conspicuously posted on an easily read chart in filter room. Instructed PIC to post the backwash filter procedures in filter room.

      Correction: Post the backwash procedure on an easily read chart.

      Code ATCP 76.11(6)(a) 4. - PROCEDURE POSTED

    • Not serious Non-critical Repeat

      DOORS

      Observed the doors to chemical storage areas are locked but are not marked to indicate entry is for authorized personnel only. Instructed PIC to post a sign that says authorized personnel only.

      Correction: Lock doors to chemical storage areas and mark to indicate entry is for authorized personnel only.

      Code ATCP 76.12 (2)(i) - DOORS

    • Not serious Non-critical Repeat

      POSTING SIGNAGE-MAX PATRON LOAD

      Observed the maximum patron load is not posted. Instructed PIC to post the maxium patron load on sign.

      Correction: Post signage indicating Maximum patron load.

      Code ATCP 76.29(1)(e) - MAX PATRON LOAD

    • Not serious Non-critical Repeat

      POSTING SIGNAGE- NO PROLONGED BREATH HOLDING

      Observed the signage or other communication warning against prolonged breath-holding is not posted or otherwise provided. Instructed PIC to post the no breath holding contest sign.

      Correction: Provide signage or provide other communication warning against prolonged breath holding.

      Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING

    • Not serious Non-critical Repeat

      POOL DECK-GOOD REPAIR

      Observed some area of the pool deck area not maintained in good repair. Observed some of the conrete has chipping and cracks. Instructed PIC to repair the affected areas of the concrete.

      Correction: Maintain pool deck area in good repair.

      Code ATCP 76.33(1)(b)1.a. - DECK GOOD REPAIR

    • Serious Critical Repeat

      TELEPHONE ACCESSIBLE

      Observed telephone or other approved communication technology capable of connecting to emergency services is not working. Tried testing the phone and the phone does not call out. Informed PIC and PIC had maintenace worker working on the phone currently. Returned on 8/19/26 for reinspection and phone is not currently working. This is second repeat violation.

      Correction: Provide a working telephone or other technology capable of connecting with emergency services.

      Code ATCP 76.26(2)(a) - TELEPHONE ACCESSIBLE

  3. Aug 13, 2026 Routine · 4 critical, 15 non-critical, 2 repeat
    • Not serious Non-critical

      CURRENT LICENSE

      Observed the pool, opened to the public, is located on the premises does not have a current license. Observed license from 2022 is posted. Isntructed PIC to post current license.

      Correction: The pool must be closed to the public immediately and may not operate until a valid license is issued from the department.

      Code ATCP 76.05(1)(a) - LICENSE CURRENT

    • Not serious Non-critical Repeat

      SKIMMERS REPAIRED OR REPLACED AS NEEDED

      Observed all 4 skimers are missing weir doors. Instructed PIC to install weir doors or floating weirs.

      Correction: Repair or replace skimmer, weirs or gutters as needed.

      Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED

    • Not serious Non-critical

      SKIMMER COVERS SECURELY SEATED ON DECK

      Observed the skimmer covers not securely seated on deck. All observed all 4 skimmers are missing screws. Instructed PIC to place screws into the lids.

      Correction: Ensure that skimmer covers are securely seated on deck.

      Code ATCP 76.11(2)(b) 3. - SKIMMER COVERS SECURE ON DECK

    • Not serious Non-critical

      SPARE STRAINER BASKET OR SCREEN AVAILABLE

      Observed there is no spare strainer basket for skimmers. Instructed PIC to have a spare skimer basket

      Correction: Provide a spare strainer or screen

      Code ATCP 76.11(2)(d) 2. - SPARE STRAINER OR SCREEN

    • Not serious Non-critical

      FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED

      Observed the affluent flowmeter is not being maintained in operating condition. Observed the float is stuck and not moving. Instructed PIC to repair the float in the flowmeter..

      Correction: Adjust or repair the float in the flow meter

      Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED

    • Not serious Non-critical

      BACKWASH PROCEDURES POSTED ON EASILY READ CHART

      Observed the backwash procedure is no conspicuously posted on an easily read chart in filter room. Instructed PIC to post the backwash filter procedures in filter room.

      Correction: Post the backwash procedure on an easily read chart.

      Code ATCP 76.11(6)(a) 4. - PROCEDURE POSTED

    • Not serious Non-critical

      DOORS

      Observed the doors to chemical storage areas are locked but are not marked to indicate entry is for authorized personnel only. Instructed PIC to post a sign that says authorized personnel only.

      Correction: Lock doors to chemical storage areas and mark to indicate entry is for authorized personnel only.

      Code ATCP 76.12 (2)(i) - DOORS

    • Not serious Non-critical

      SAFETY DATA SHEET

      Observed the safety data sheet was not available for all chemicals being used. Instructed PIC to keep a copy onsite of all SDS for all chemicals being used.

      Correction: Maintain a safety data sheet for each chemical on site.

      Code ATCP 76.12 (4)(b)1. - SAFETY DATA SHEETS

    • Not serious Non-critical

      INTERLOCK-LOG KEPT

      Observed a log of the monthly interlock tests is not being kept. Instructed PIC to keep log of chemical interlock test.

      Correction: Keep a log of monthly interlock tests.

      Code ATCP 76.13 (1)(c)4 - INTERLOCK, LOG KEPT

    • Not serious Non-critical

      COMBINED CHLORINE PLAN PRESENT

      Observed the operator has not developed and implemented a plan to minimize combined chlorine in the pool. Discussed with Aqua Tech and they will get a combined chlorine management plan for the PIC.

      Correction: Develop and implement a plan to minimize combined chlorine in the pool.

      Code ATCP 76.14(5)(e)1. - PLAN PRESENT

    • Not serious Non-critical

      POOL WATER TESTED PEAK PATRON LOAD, PH AND SANITIZER

      Observed the pool water not tested for pH and disinfectant at least one other time during the day’s peak patron load. Observed the system does not have the controller is only being tested once a day. Instructed PIC it needs to be tested twice a day.

      Correction: Test pool water for pH and disinfectant at least one time during the day’s peak patron load.

      Code ATCP 76.18(1)(a)2 - WATER TESTED, SANITIZER, PH, PEAK LOAD P

    • Not serious Non-critical

      POSTING SIGNAGE-MAX PATRON LOAD

      Observed the maximum patron load is not posted. Instructed PIC to post the maxium patron load on sign.

      Correction: Post signage indicating Maximum patron load.

      Code ATCP 76.29(1)(e) - MAX PATRON LOAD

    • Not serious Non-critical Repeat

      POSTING SIGNAGE- NO PROLONGED BREATH HOLDING

      Observed the signage or other communication warning against prolonged breath-holding is not posted or otherwise provided. Instructed PIC to post the no breath holding contest sign.

      Correction: Provide signage or provide other communication warning against prolonged breath holding.

      Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING

    • Not serious Non-critical

      POOL DECK-GOOD REPAIR

      Observed some area of the pool deck area not maintained in good repair. Observed some of the conrete has chipping and cracks. Instructed PIC to repair the affected areas of the concrete.

      Correction: Maintain pool deck area in good repair.

      Code ATCP 76.33(1)(b)1.a. - DECK GOOD REPAIR

    • Not serious Non-critical

      POOL EQUIPMENT-PROPERLY MAINTAINED

      Observed the drinking fountain has low pressure. Instructed PIC to repair the drinking fountain.

      Correction: Maintain the drinking fountain

      Code ATCP 76.33(1)(e)3. - MAINTENANCE OF POOL EQPT

    • Serious Critical

      TELEPHONE ACCESSIBLE

      Observed telephone or other approved communication technology capable of connecting to emergency services is not working. Tried testing the phone and the phone does not call out. Informed PIC and PIC had maintenace worker working on the phone currently.

      Correction: Provide a working telephone or other technology capable of connecting with emergency services.

      Code ATCP 76.26(2)(a) - TELEPHONE ACCESSIBLE

    • Serious Critical

      HOSING - BACKFLOW PREVENTION DEVICE

      Observed the hose bib next to drinking fountain does not have a backflow preventor and a hose is connected to it. Instructed PIC to install a backflow preventor device.

      Correction: All hose bib must have a backflow preventor device if a hose is connected to it.

      Code ATCP 76.33(1)(d)2. - BACKFLOW PREVENTION

    • Serious Critical Corrected on site

      GATES AND DOORS-LATCHING

      Observed the side gate to the pool does not latch. Informed PIC and PIC had maintenance worker fix the gate.

      Correction: Provide a latching door.

      Code ATCP 76.34(4)(a)(1m)(b)- LATCHING

    • Serious Critical

      VGBA-EXISTING POOLS, PUMP CURVE AND DRAIN COVER INFO

      Obervef the operator of an existing pool does not have the pump curve and is missing the gpm for the drain cover. Spoke with Brad from Aqua Tech and Brad stated they will find that information for the PIC.

      Correction: Obtain a pump curve and information that describes make, model and gpm rating for the drain covers.

      Code ATCP 76.38(1)(b) - PUMP CURVE

  4. Jul 22, 2025 Routine · 1 critical, 7 non-critical
    • Not serious Non-critical

      LICENSE NOT POSTED

      The license is not posted for public view.

      Correction: Post the license where it can be viewed by the public.

      Code ATCP 76.05(7) - LICENSE POSTED

    • Not serious Non-critical

      SKIMMERS REPAIRED OR REPLACED AS NEEDED

      Weir doors are missing.

      Correction: Repair or replace skimmer, weirs or gutters as needed.

      Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED

    • Not serious Non-critical

      RECIRCULATION (TURNOVER) RATE NOT MET

      The recirculation (turnover) rate could not be measured due to the unknown pool volume by operator.

      Correction: Immediately adjust or repair equipment to operate at a proper turnover rate.

      Code ATCP 76.11(4)(c) - RECIRCULATION RATE

    • Not serious Non-critical

      MAX PATRON LOAD POOL

      The maximum patron load is not posted.

      Correction: Calculate the maximum patron load to provide at least 15 square feet per patron in the shallow portion and 25 square feet per patron in the deep portion and do not allow maximum patron load to be exceeded.

      Code ATCP 76.25(2)(a) - POOL

    • Not serious Non-critical

      FIRST AID KIT-EYE WASH SOLUTION

      The first aid kit has expired eye wash solution.

      Correction: Provide eye wash solution for the first aid kit.

      Code ATCP 76.27(1)(b)5. - EYE WASH SOLUTION

    • Not serious Non-critical

      POSTING SIGNAGE- NO PROLONGED BREATH HOLDING

      Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.

      Correction: Provide signage or provide other communication warning against prolonged breath holding.

      Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING

    • Not serious Non-critical

      VGBA DRAIN COVER INFO-INSTALLATION DATE

      The VGBA log or other proof does not indicate drain cover installation date.

      Correction: Indicate in the log of drain cover installation date.

      Code ATCP 76.38(2)(b)5. - INSTALL DATE

    • Serious Critical

      DRINKING FOUNTAIN PROVIDED

      There is no drinking fountain provided.

      Correction: Provide a drinking fountain within 300 feet walking distance.

      Code ATCP 76.33(1)(g)1. DRINKING FOUNTAIN PROVIDED

Source: Greenfield Health Department. History last read Oct 5, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.