Ravinia Apartments
4280 S RAVINIA DR, Greenfield, WI 53221 · Milwaukee County
Establishment
- Type
- Pool / recreational water (Pool - Simple)
- Inspected by
- Greenfield Health Department
- License / ID
- HSAT-7QXMHY
- Status
- Suspended
- Phone
- (414) 281-9797
- Official record
- Greenfield Health Department inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 1 | 19 | 3 |
| 2025 | 3 | 45 | 13 |
| 2024 | 3 | 6 | 2 |
| 2023 | 1 | 1 | 0 |
Inspections
-
Aug 25, 2026 Routine · 3 critical, 16 non-critical, 3 repeat
-
Not serious
Non-critical
CURRENT LICENSE
A pool, opened to the public, is located on the premises does not have a current license. The Health Department suspended the license last year, but they opened this year prior to re-inspection.
Correction: The pool must be closed to the public immediately and may not operate until a valid license is issued from the department.
Code ATCP 76.05(1)(a) - LICENSE CURRENT
-
Not serious
Non-critical
SKIMMER COVERS SECURELY SEATED ON DECK
Skimmer covers not securely seated on deck.
Correction: Ensure that skimmer covers are securely seated on deck.
Code ATCP 76.11(2)(b) 3. - SKIMMER COVERS SECURE ON DECK
-
Not serious
Non-critical
Repeat
RECIRCULATION (TURNOVER) RATE NOT MET
No confirmation on whether the recirculation (turnover) rate has not been met. There was no flowmeter to calculate the turnover rate.
Correction: Immediately adjust or repair equipment to operate at a proper turnover rate [Describe].
Code ATCP 76.11(4)(c) - RECIRCULATION RATE
-
Not serious
Non-critical
Repeat
FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED
There is no flowmeter in operating condition.
Correction: Install a flowmeter.
Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED
-
Not serious
Non-critical
PIPING LABELED, TAGGED OR CODED
The piping is not labeled, tagged or color-coded correctly.
Correction: Ensure that the piping is labeled, tagged or color-coded to indicate valves, piping and direction of water flow.
Code ATCP 76.11(5m)(a) - PIPING NOT LABELED,TAGGED, CODED
-
Not serious
Non-critical
BACKWASH PROCEDURES POSTED ON EASILY READ CHART
The backwash procedure is no conspicuously posted on an easily read chart. There was also no record of backwashing or filter inspection. Operator verbally confirmed they do it, but no record was available.
Correction: Post the backwash procedure on an easily read chart.
Code ATCP 76.11(6)(a) 4. - PROCEDURE POSTED
-
Not serious
Non-critical
CYANURIC TEST
Cyanuric acid is used in the pool basin and the cyanuric acid concentration is not tested at least once a week.
Correction: Test water for the cyanuric acid at least once a week.
Code ATCP 76.18(1)(d) - WATER TESTED CYANURIC
-
Not serious
Non-critical
POSTING SIGNAGE-MAX PATRON LOAD
Maximum patron load is not clearly posted.
Correction: Post signage indicating Maximum patron load.
Code ATCP 76.29(1)(e) - MAX PATRON LOAD
-
Not serious
Non-critical
Repeat
POSTING SIGNAGE- NO PROLONGED BREATH HOLDING
Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.
Correction: Provide signage or provide other communication warning against prolonged breath holding.
Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING
-
Not serious
Non-critical
OPERATING REPORTS-BACKWASH
The operator did not record the following on the operating report: The dates on which backwashing was completed.
Correction: Record the following on the operating report, the dates when backwashing was completed.
Code ATCP 76.32(1)(b) - BACKWASH
-
Not serious
Non-critical
FILES MAINTAINED PERMANENT-ATCP 76 CURRENT COPY
A copy of the most current version of ch. ATCP 76 was not permanently maintained on premises.
Correction: Maintain a copy of the most current version of ch. ATCP 76 on premises.
Code ATCP 76.32(3)(a)1. - CURRENT ATCP 76 COPY
-
Not serious
Non-critical
FILES MAINTAINED PERMANENT-CDC FECAL INCIDENTS
The most recent United States centers for disease control and prevention recommendations for fecal accidents or another plan in response to fecal accidents was not permanently maintained on premises:
Correction: Maintain a copy of the most recent United States centers for disease control and prevention recommendations for fecal accidents or another plan in response to fecal accidents that is consistent with the United States centers for disease control and prevention’s fecal accident response recommendations on the premises.
Code ATCP 76.32(3)(a)8. - CDC FECAL RESPONSE GUIDELINES
-
Not serious
Non-critical
FILES RETAINED 2 YEARS-FECAL ACCIDENT REPORT
Fecal accident report (s) not maintained on premises for 2 years.
Correction: Maintain on premises for 2 years any fecal accident report made.
Code ATCP 76.32(3)(b)3. - FECAL INCIDENT RESPONSE
-
Not serious
Non-critical
POOL BASIN MAINTAINED FREE OF DEFECTS
Pool basin not Maintained free of cracks or other defects and repaired or refinished as necessary to maintain it in a cleanable condition. The rim of the basin by the stairs is broken.
Correction: Maintained the pool basin free of cracks or other defects, and repaired or refinished as necessary to maintain it in a cleanable condition.
Code ATCP 76.33(1)(a)2 - POOL BASIN GOOD REPAIR
-
Not serious
Non-critical
DRINKING FOUNTAIN MAINTAINED
The drinking fountain is not working.
Correction: Maintain the drinking fountain in clean and sanitary condition.
Code ATCP 76.33(1)(g)2.-DRINKING FOUNTAIN CLEAN
-
Not serious
Non-critical
VGBA DRAIN COVER INFO-INSTALLATION DATE
The VGBA log or other proof does not indicate drain cover installation date.
Correction: Indicate in the log of drain cover installation date.
Code ATCP 76.38(2)(b)5. - INSTALL DATE
-
Serious
Critical
RECIRCULATION SYSTEM CONTINUOUS OPERATION
The pool recirculation system is not operational or not continuously operated. The incoming water pipe showed no sign of water movement. Operator was not able to confirm movement either.
Correction: The pool must be closed immediately until the recirculation system is in place and in continuous operation.
Code ATCP 76.11(1) - RECIRCULATION SYSTEM PRESENT, CONTINUOUSLY O
-
Serious
Critical
MAXIMUM CHLORINE
The maximum chlorine residual exceeds 10 ppm.
Correction: Close the pool until the chlorine residual is in compliance with ATCP 76.14 Table A.
Code ATCP 76.14(5)(f) - MAXIMUM FREE CHLORINE
-
Serious
Critical
FREE OF CHEMICAL, PHYSICAL, AND MICROBIAL SUBSTANCES
There was residue of algae inside the skimmer walls. The water is also looking cloudy.
Correction: Close the pool until the water is free of chemical, physical, and microbial substances known to be, or suspected of being, capable of creating toxic reactions or skin or membrane irritations.
Code ATCP 76.16 (1) - WATER FREE OF PHYSICAL, MICROBIAL
-
Not serious
Non-critical
-
Aug 29, 2025 Re-inspection · 2 critical, 10 non-critical, 12 repeat
-
Not serious
Non-critical
Repeat
SKIMMERS REPAIRED OR REPLACED AS NEEDED
Skimmers has cracked wall. There are also no weir doors.
Correction: Repair or replace skimmer, weirs or gutters as needed.
Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED
-
Not serious
Non-critical
Repeat
RECIRCULATION (TURNOVER) RATE NOT MET
The recirculation (turnover) rate cannot be determined due to the non existance of the flow meter.
Correction: Immediately adjust or repair equipment to operate at a proper turnover rate.
Code ATCP 76.11(4)(c) - RECIRCULATION RATE
-
Not serious
Non-critical
Repeat
FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED
There is no flowmeter in the pump room.
Correction: Install a flow meter.
Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED
-
Not serious
Non-critical
Repeat
FLOWMETER, VALVE OR GAUGE NOT INSTALLED PER MANUFACTURER OR AS VERIFIED BY PUMP CURVE
One of the two equilizers is not installed according to manufacturer instructions and the other is missing from the pool completely.
Correction: Install the equilizers according to manufacturer instructions or as verified by pump curve.
Code ATCP 76.11(5)(b) - FLOWMETER, VALVE, GAUGE NOT INSTALLED PRO
-
Not serious
Non-critical
Repeat
OPERATOR RESPONSIBILITIES
The operator has not been responsible for equipment shut-down, backwashing, daily maintenance and vacuuming, and maintenance of water quality pursuant. The phone was not working yesterday (stated by maintenance), but choosed to open the pool anyway.
Correction: Provide a pool operator who is responsible and providing active managerial control for equipment shut-down, backwashing, daily maintenance and vacuuming, and maintenance of water quality.
Code ATCP 76.20(1)(b) - OPERATOR RESPONSIBILITIES
-
Not serious
Non-critical
Repeat
RESCUE EQUIPMENT ACCESSIBLE
The rescue equipment is not in a conspicuous place and readily accessible. The shepherd crook is located above the doors and is inaccessible.
Correction: Maintain rescue equipment in a conspicuous and accessible location.
Code ATCP 76.26(1)(a)2. - RESCUE EQPT ACCESSIBLE
-
Not serious
Non-critical
Repeat
FIRST AID KIT-EYE WASH SOLUTION
The first aid kit is missing eye wash solution. The current one expired and was discarded during inspection.
Correction: Provide eye wash solution for the first aid kit.
Code ATCP 76.27(1)(b)5. - EYE WASH SOLUTION
-
Not serious
Non-critical
Repeat
BIOHAZARD KIT-AVAILABLE
A biohazard kit is not available.
Correction: Provide a biohazard kit for the pool.
Code ATCP 76.27(2)(a) - BIOHAZ KIT AVAILABLE
-
Not serious
Non-critical
Repeat
POSTING SIGNAGE- NO PROLONGED BREATH HOLDING
Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.
Correction: Provide signage or provide other communication warning against prolonged breath holding.
Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING
-
Not serious
Non-critical
Repeat
POOL DECK-GOOD REPAIR
Pool deck area not maintained in good repair. There are cracked concretes along the pool rim and the deck area.
Correction: Maintain pool deck area in good repair.
Code ATCP 76.33(1)(b)1.a. - DECK GOOD REPAIR
-
Serious
Critical
Repeat
RESPONSIBLE SUPERVISOR POOL CLOSED
Responsible supervisor is not ensuring that pool is closed pursuant to ATCP 76.30, closing criteria. The emergency phone was not working yesterday but pool was opened to residents.
Correction: Have the responsible supervisor ensure that the pool is closed pursuant to ATCP 76.30, closing criteria.
Code ATCP 76.21 (1)(c)10. - CLOSE POOL
-
Serious
Critical
Repeat
DRINKING FOUNTAIN PROVIDED
The drinking water fountain is not working.
Correction: Provide a drinking fountain within 300 feet walking distance.
Code ATCP 76.33(1)(g)1. DRINKING FOUNTAIN PROVIDED
-
Not serious
Non-critical
Repeat
-
Aug 27, 2025 Follow Up · 5 critical, 10 non-critical, 15 repeat
-
Not serious
Non-critical
Repeat
SKIMMERS REPAIRED OR REPLACED AS NEEDED
Skimmers has cracked wall. There are also no weir doors.
Correction: Repair or replace skimmer, weirs or gutters as needed.
Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED
-
Not serious
Non-critical
Repeat
RECIRCULATION (TURNOVER) RATE NOT MET
The recirculation (turnover) rate cannot be determined due to the non existance of the flow meter.
Correction: Immediately adjust or repair equipment to operate at a proper turnover rate.
Code ATCP 76.11(4)(c) - RECIRCULATION RATE
-
Not serious
Non-critical
Repeat
FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED
There is no flowmeter in the pump room.
Correction: Install a flow meter.
Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED
-
Not serious
Non-critical
Repeat
FLOWMETER, VALVE OR GAUGE NOT INSTALLED PER MANUFACTURER OR AS VERIFIED BY PUMP CURVE
One of the two equilizers is not installed according to manufacturer instructions and the other is missing from the pool completely.
Correction: Install the equilizers according to manufacturer instructions or as verified by pump curve.
Code ATCP 76.11(5)(b) - FLOWMETER, VALVE, GAUGE NOT INSTALLED PRO
-
Not serious
Non-critical
Repeat
OPERATOR RESPONSIBILITIES
The operator has not been responsible for equipment shut-down, backwashing, daily maintenance and vacuuming, and maintenance of water quality pursuant. The phone was not working yesterday (stated by maintenance), but choosed to open the pool anyway.
Correction: Provide a pool operator who is responsible and providing active managerial control for equipment shut-down, backwashing, daily maintenance and vacuuming, and maintenance of water quality.
Code ATCP 76.20(1)(b) - OPERATOR RESPONSIBILITIES
-
Not serious
Non-critical
Repeat
RESCUE EQUIPMENT ACCESSIBLE
The rescue equipment is not in a conspicuous place and readily accessible. The shepherd crook is located above the doors and is inaccessible.
Correction: Maintain rescue equipment in a conspicuous and accessible location.
Code ATCP 76.26(1)(a)2. - RESCUE EQPT ACCESSIBLE
-
Not serious
Non-critical
Repeat
FIRST AID KIT-EYE WASH SOLUTION
The first aid kit is missing eye wash solution. The current one expired and was discarded during inspection.
Correction: Provide eye wash solution for the first aid kit.
Code ATCP 76.27(1)(b)5. - EYE WASH SOLUTION
-
Not serious
Non-critical
Repeat
BIOHAZARD KIT-AVAILABLE
A biohazard kit is not available.
Correction: Provide a biohazard kit for the pool.
Code ATCP 76.27(2)(a) - BIOHAZ KIT AVAILABLE
-
Not serious
Non-critical
Repeat
POSTING SIGNAGE- NO PROLONGED BREATH HOLDING
Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.
Correction: Provide signage or provide other communication warning against prolonged breath holding.
Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING
-
Not serious
Non-critical
Repeat
POOL DECK-GOOD REPAIR
Pool deck area not maintained in good repair. There are cracked concretes along the pool rim and the deck area.
Correction: Maintain pool deck area in good repair.
Code ATCP 76.33(1)(b)1.a. - DECK GOOD REPAIR
-
Serious
Critical
Repeat
CYANURATES 30 PPM LIMIT
The cyanuric acid concentration is at 50ppm.
Correction: Lower the water cyanuric acid concentration to 30 ppm or lower.
Code ATCP 76.14(5)(b)1 - MAXIMUM CYANURIC
-
Serious
Critical
Repeat
PH
The pH is <7.2
Correction: Maintain the pH at 7.2 to 7.8. Note: *it is strongly encouraged to use a pH meter with an accuracy greater than 0.1 or better.
Code ATCP 76.14(5)(c) - PH
-
Serious
Critical
Repeat
RESPONSIBLE SUPERVISOR POOL CLOSED
Responsible supervisor is not ensuring that pool is closed pursuant to ATCP 76.30, closing criteria. The emergency phone was not working yesterday but pool was opened to residents.
Correction: Have the responsible supervisor ensure that the pool is closed pursuant to ATCP 76.30, closing criteria.
Code ATCP 76.21 (1)(c)10. - CLOSE POOL
-
Serious
Critical
Repeat
RESPONSIBLE SUPERVISOR RECORDS MAINTAIN
Responsible supervisor is not ensuring that records are maintained. The chemical log is missing Cyanyric Acid level.
Correction: Have the responsible supervisor ensure that records are maintained.
Code ATCP 76.21 (1)(c)7. - RECORDS MAINTENANCE
-
Serious
Critical
Repeat
DRINKING FOUNTAIN PROVIDED
The drinking water fountain is not working.
Correction: Provide a drinking fountain within 300 feet walking distance.
Code ATCP 76.33(1)(g)1. DRINKING FOUNTAIN PROVIDED
-
Not serious
Non-critical
Repeat
-
Aug 26, 2025 Routine · 6 critical, 12 non-critical, 1 repeat
-
Not serious
Non-critical
SKIMMERS REPAIRED OR REPLACED AS NEEDED
Skimmers has cracked wall. There are also no weir doors.
Correction: Repair or replace skimmer, weirs or gutters as needed.
Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED
-
Not serious
Non-critical
RECIRCULATION (TURNOVER) RATE NOT MET
The recirculation (turnover) rate cannot be determined due to the non existance of the flow meter.
Correction: Immediately adjust or repair equipment to operate at a proper turnover rate.
Code ATCP 76.11(4)(c) - RECIRCULATION RATE
-
Not serious
Non-critical
FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED
There is no flowmeter in the pump room.
Correction: Install a flow meter.
Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED
-
Not serious
Non-critical
FLOWMETER, VALVE OR GAUGE NOT INSTALLED PER MANUFACTURER OR AS VERIFIED BY PUMP CURVE
One of the two equilizers is not installed according to manufacturer instructions and the other is missing from the pool completely.
Correction: Install the equilizers according to manufacturer instructions or as verified by pump curve.
Code ATCP 76.11(5)(b) - FLOWMETER, VALVE, GAUGE NOT INSTALLED PRO
-
Not serious
Non-critical
OPERATOR RESPONSIBILITIES
The operator has not been responsible for equipment shut-down, backwashing, daily maintenance and vacuuming, and maintenance of water quality pursuant. The phone was not working yesterday (stated by maintenance), but choosed to open the pool anyway.
Correction: Provide a pool operator who is responsible and providing active managerial control for equipment shut-down, backwashing, daily maintenance and vacuuming, and maintenance of water quality.
Code ATCP 76.20(1)(b) - OPERATOR RESPONSIBILITIES
-
Not serious
Non-critical
RESCUE EQUIPMENT ACCESSIBLE
The rescue equipment is not in a conspicuous place and readily accessible. The shepherd crook is located above the doors and is inaccessible.
Correction: Maintain rescue equipment in a conspicuous and accessible location.
Code ATCP 76.26(1)(a)2. - RESCUE EQPT ACCESSIBLE
-
Not serious
Non-critical
FIRST AID KIT-EYE WASH SOLUTION
The first aid kit is missing eye wash solution. The current one expired and was discarded during inspection.
Correction: Provide eye wash solution for the first aid kit.
Code ATCP 76.27(1)(b)5. - EYE WASH SOLUTION
-
Not serious
Non-critical
BIOHAZARD KIT-AVAILABLE
A biohazard kit is not available.
Correction: Provide a biohazard kit for the pool.
Code ATCP 76.27(2)(a) - BIOHAZ KIT AVAILABLE
-
Not serious
Non-critical
Corrected on site
EMERGENCY BLANKETS
Two emergency blankets in good condition are not available in the pool area.
Correction: Provide two emergency blankets in good condition in the pool area.
Code ATCP 76.27(3) - EMERGENCY BLANKETS
-
Not serious
Non-critical
POSTING SIGNAGE- NO PROLONGED BREATH HOLDING
Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.
Correction: Provide signage or provide other communication warning against prolonged breath holding.
Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING
-
Not serious
Non-critical
POOL DECK-GOOD REPAIR
Pool deck area not maintained in good repair. There are cracked concretes along the pool rim and the deck area.
Correction: Maintain pool deck area in good repair.
Code ATCP 76.33(1)(b)1.a. - DECK GOOD REPAIR
-
Not serious
Non-critical
POOL CLOSED SIGN
The pool area is closed but there is no 'closed' sign posted.
Correction: Provide a sign that indicates the pool area is closed.
Code ATCP 76.34(5) - 'CLOSED' SIGN
-
Serious
Critical
CYANURATES 30 PPM LIMIT
The cyanuric acid concentration is at 50ppm.
Correction: Lower the water cyanuric acid concentration to 30 ppm or lower.
Code ATCP 76.14(5)(b)1 - MAXIMUM CYANURIC
-
Serious
Critical
Repeat
PH
The pH is <7.2
Correction: Maintain the pH at 7.2 to 7.8. Note: *it is strongly encouraged to use a pH meter with an accuracy greater than 0.1 or better.
Code ATCP 76.14(5)(c) - PH
-
Serious
Critical
RESPONSIBLE SUPERVISOR POOL CLOSED
Responsible supervisor is not ensuring that pool is closed pursuant to ATCP 76.30, closing criteria. The emergency phone was not working yesterday but pool was opened to residents.
Correction: Have the responsible supervisor ensure that the pool is closed pursuant to ATCP 76.30, closing criteria.
Code ATCP 76.21 (1)(c)10. - CLOSE POOL
-
Serious
Critical
RESPONSIBLE SUPERVISOR RECORDS MAINTAIN
Responsible supervisor is not ensuring that records are maintained. The chemical log is missing Cyanyric Acid level.
Correction: Have the responsible supervisor ensure that records are maintained.
Code ATCP 76.21 (1)(c)7. - RECORDS MAINTENANCE
-
Serious
Critical
Corrected on site
TELEPHONE-OTHER TECHNOLOGIES,RELIABLE SERVICE CONNECTION
Emergency phone does not have reliable service connection. Correction: the facility was able to reconnect the service line during the inspection.
Correction: Provide a reliable service connection for the communication technology.
Code ATCP 76.26(2)(b)2. - TELEPHONE, OTHER TECHNOLOGIES, CONNECTI
-
Serious
Critical
DRINKING FOUNTAIN PROVIDED
The drinking water fountain is not working.
Correction: Provide a drinking fountain within 300 feet walking distance.
Code ATCP 76.33(1)(g)1. DRINKING FOUNTAIN PROVIDED
-
Not serious
Non-critical
-
Jun 14, 2024 Follow Up · 1 non-critical, 1 repeat
-
Not serious
Non-critical
Repeat
TEST KIT APPROVED
Facility is not using an approved test kit.
Correction: State approved test kit must be used to text water chemical.
Code ATCP 76.17 (1) - DEPARTMENT-APPROVED
-
Not serious
Non-critical
Repeat
-
Jun 10, 2024 Follow Up · 1 non-critical, 1 repeat
-
Not serious
Non-critical
Repeat
TEST KIT APPROVED
Facility is not using an approved test kit.
Correction: State approved test kit must be used to text water chemical.
Code ATCP 76.17 (1) - DEPARTMENT-APPROVED
-
Not serious
Non-critical
Repeat
-
Jun 7, 2024 Routine · 2 critical, 2 non-critical
-
Not serious
Non-critical
TEST KIT APPROVED
Facility is not using an approved test kit.
Correction: State approved test kit must be used to text water chemical.
Code ATCP 76.17 (1) - DEPARTMENT-APPROVED
-
Not serious
Non-critical
VGBA DRAIN COVER INFO-INSTALLATION DATE
The VGBA log or other proof does not indicate drain cover installation date for the equalizer.
Correction: Indicate in the log of drain cover installation date.
Code ATCP 76.38(2)(b)5. - INSTALL DATE
-
Serious
Critical
PH
The pH is 7.0.
Correction: Maintain the pH at 7.2 to 7.8. Note: *it is strongly encouraged to use a pH meter with an accuracy greater than 0.1 or better.
Code ATCP 76.14(5)(c) - PH
-
Serious
Critical
WATER CLARITY
Pool water not transparent and free from cloudiness. Main drain grating and outline not readily visible from pool deck.
Correction: Close the pool until the pool water is transparent and free from cloudiness and so that main drain grating and outline are readily visible from pool deck.
Code ATCP 76.16 (2) - CLARITY
-
Not serious
Non-critical
-
Jun 29, 2023 Routine · 1 non-critical, 1 repeat
-
Not serious
Non-critical
Repeat
BLANKETS MISSING
2 durable blankets are not available in the pool area.
Correction: Provide 2 durable blankets in the pool area.
Code [B] ATCP 76.27(1)
-
Not serious
Non-critical
Repeat
Source: Greenfield Health Department. History last read Oct 5, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.