TRC Minutes 10.08.26 Page 1 of 2
TECHNICAL REVIEW COMMITTEE MINUTES
Thursday, October 8, 2026 – 10:00 A.M.
Training Room/Zoom
NEW APPLICATIONS
TRC-26-30: Site-Specific Development Plan – 7-Elevan at 70 Highway 17 South
Attending
Customer
Representatives:
Kevin Pulis, Applicant
Staff Comments
Public Works: 1. Relocate fuel tanks. Maximize distance from the existing 8” PVC water main
along Hwy 17 per courtesy review comments. Where the existing water line is
PVC and not cast iron, a min. of 50’ separation is preferred.
2. Add an oil/water separator before the water drains to the back pond/swale.
3. SCDOT encroachment permit is required for work in the Hwy 17 R/W.
4. Front load dumpsters will require a private hauler.
5. Additional comments may be forthcoming pending further review and/or
receipt of revised documents.
Zoning: 6. Sight triangle, 20'X10'
7. No trees in right of way
8. Provide a tapered landscape buffer on Hwy 17 side.
9. Lighting plan needed.
Building: 10. Separate permits required for canopy and trash enclosure.
Fire: 11. Provide a fire apparatus turning exhibit to confirm that emergency vehicles can
access all areas of the site.
Planning: No comments
TRC-26-34: Site-Specific Development Plan – North Myrtle Beach Dealership at 3484 Sandler Boulevard
Attending
Customer
Representatives:
Mark Stoughton, Engineer
Staff Comments
Public Works: 1. Entrance on Sandler Blvd. should line up with entrance across the street.
2. 70’ radius on the entrance tie-ins need to be changed to max. 40’ for medium
volume sites per SCDOT ARMS manual.
3. Front load dumpsters will require a private hauler.
4. Tie-in angle from parking area to the main loop around the building has poor
visibility (service center side).
5. An oil/ water separator may be required.
6. Coordinate water & sewer service with Grand Strand Water & Sewer Authority.
7. Additional comments may be forthcoming pending further review and/ or
submittal of revised.
Zoning: 8. 5 additional parking spaces per rack/lift.
9. Automobile storage exempted from outdoor display ordinance.
TRC Minutes 10.08.26 Page 2 of 2
10. Please assure that vehicles will not be parked in required buffers and end
islands.
11. Sight triangles ok?
Building: 12. Separate permit required for trash enclosure.
Fire: 13. Provide a fire apparatus turning exhibit to confirm that emergency vehicles can
access all areas of the site.
14. Fire hydrants shall be spaced in accordance with City standards (maximum
spacing measured along the roadway). Provide a dimensioned exhibit
demonstrating compliance.
15. Based on the proposed occupancy/load, additional fire protection systems (e.g.,
sprinklers, fire alarm) may be required. Revise plans to demonstrate compliance
with applicable code provisions.
16. The FDC details need to be on the plans.
17. Piping to meet standards (See City of North Myrtle Beach Public Utilities
Guidebook)
18. Fittings to meet standards (See City of North Myrtle Beach Public Utilities
Guidebook)
19. Bituminous coating applied (NFPA 24)
20. 36 in. Burial depth (NFPA 24)
21. Trace wire for CPVC piping
22. Visual inspection before covering
23. Proper thrust blocking (See City of North Myrtle Beach Public Utilities
Guidebook)
24. Hydro test 200 psi/2hrs (NFPA 24)
25. Flush pipe (NFPA 24)
26. NFPA 24 certificate (NFPA 24)
27. Show details for all piping including fire department connections
28. A permit is required by the utility contractor for underground fire lines.
Planning: 29. Provide a continuous, accessible pedestrian connection between the public
sidewalk and the primary building entrance. Revise the site plan to clearly show
the route and associated improvements.
SUB-26-55: Major Final Subdivision Plat – Dockside Preserve Phase 1A on Bowline Boulevard
Attending
Customer
Representatives:
Philip Hornbeck, Engineer
Staff Comments
Public Works: No comments
Zoning: 1. Overlay tree saves with tree protection on plat.
Building: No comments
Fire: No comments
Planning: 2. Add legend to cover page as well.
3. Multiple pages have blank labels. Was that intentional?
4. PIN 350-00-00-0085 has more recent DB 3578/1663.
5. I will put in comments regarding FG in the separate step as soon as they are
available.