Historic Preservation Design Review June 25, 2020 HP-20-09, 129 N Washington St. (City) I. THE REQUEST Applicant: Stevens & Wilkinson Status of the Applicant: Project Architects Request: Approval for construction of a +/- 30,000 sq. ft. hospital addition. Location: 129 N Washington St. Present Use/Zoning: Hospital / CBD Tax Map Reference: 228-12-04-001 & 228-12-04-007 Adjacent Property Land Use and Zoning: North – Commercial / CBD South – Commercial/ CBD East – Government Services/ CBD West – Hospital / CBD II. BACKGROUND 129 N. Washi ngton St ., shown in the photograph to the right , is the site of Prisma Health Tuomey Hospital. The development proposal shows a new +/ - 30,000 sq. f t. emergency room ad dition to the eastern portion of the existing structure near the intersection of N. Main St. and Canal St. On the following page is a current photograph of the portion of the structure slated for expansion. 2 Above: View of the eastern portion of the existing emergency room wing from N. Main St. Architectural/Historic Context: The hospital at 1 29 N. Washington St w as not identified in the 1985 Historical Resources Survey . While there has been a hospital use on the site since at least 1940, no portions of the ori ginal structure remain due to piecemeal demolition and redevelopment of the site . Based on information obtained from the Sumter County Assessor’s Office P roperty Cards, the eastern portion of the structure that will be receiving an addition was constructed around 2006. While this use i s vital to the h ealth a nd well-being of the community, it is not considered a contributing structure to the District. Scope of Work: 1. Construction of a +/ - 30,000 sq. f t. emergency room addition with red brick masonry, aluminum windows, and aluminum accents and roofing. Graphic renderings and plans provided by the applicant showing the sco pe of the proposed work are shown on the following page , with the proposed addition highlighted in red. 3 Above: Eastern elevation detailing the view from N. Main St. Above: Southern elevation detailing the view from Canal St. Above: Northern elevation from the hospital access drive 4 Above: Aerial rendering of proposed design; Below: Proposed site landscaping plan 5 Design Review: The Design Review Guidelines Manual states: NEW CONSTRUCTION & ADDITIONS 6.1 Commercial Properties High quality infill construction o n vacant or underutilized lots has the potential to strengthen the vitality of different building types and architectural styles. Most notable of these styles are Richardsonian Romanesque, Neo -Classical Revival, and Main Street Commercial. While downtown b uildings differ in their detailing and level of ornament, certain patterns are consistent among them, such as t heir siting, size, and t he general alignment of storefronts, upper story windows, and cornices. The intent of these guidelines is to encourage new bui ldings that reinforce and respond to the principal design elements of historic commercial buildings in the district, while reflecting their own time in the development of the city. A. Design New Buildings to Reflect Their Own Time.  Avoid the direct imitation of a historic style that would blur the distinction between old and new.  Avoid any reference to historic styles that precede the g rowth and development of the district. Staff Analysis: The existing hospital complex, as well as the proposed addition are architecturally compatible with the rest of the hospital complex, a distinct architectural style which distinguishes it from the existing historic structures in the downtown district. B. Incorporate the P rincipal Elements of T raditional Commercial Façade s into the Designs of New Buildings.  Integrate the design features of contemporary storefronts on the first f loor. Use contemporary materials to avoid creating a false historic appearance.  Delineate between the storefront level and upper floors with elements o f horizontal expression, such as canopy, belt course, steel lintel, or cornice.  Use vertically proportioned upper story windows in a regular pattern an d appropriate ratio of solid wall to window area.  Provide visual termination at the top of the build ing w ith a cornice, parapet, pediment, or other decorative feature. Staff Analysis: While the applicant’s design is modern, it does incorporate some of the same design elements of traditional storefronts. The structure delineates the entrance through a 6 glass and aluminum entranceway which replicate s the visibility of traditional storefronts. Above: Proposed entrance design The design also utilizes a canopy to make the structure more accessible and inviting to pedestrians, however the structure opt s for a modern, flat metal design consistent with other portions of the hospital complex. C. Reinforce the S treet Wall by R elating Setback, Orientation, and S pacing of New Construction to that of Existing Buildings.  Align new commercial construction with the property line w ithout setbacks or side alleys.  Minimize gaps in the street wall. Staff Analysis: Unlike the vast majority of development within the Downtown Design district , the Hospital was not developed at the front setback area and is set back approximately 200 ft. from the N. Main St. property li ne. This recessed pattern of development is dictated by the unique nature of the hospital use , which requires dedicated parking and has specific requirements for emergency vehicle access. While the structure will not be located at street level, the submitted plans inc lude details to reinforce the streetscape th rough the preservation of existing street trees, and the incorporation of additional tree and shrub plantings along N. Main St. 7 D. Develop Respectful Relationships in Terms o f Size, Scale, and Massing to Adjacent Historic Buildings.  Construct new buildings that are similar in height and width to adjacent buildings.  Step back or cascade portions of new buildings that are taller than adjacent buildings away from the stre et front to maintain the t raditional range of heights along the street edge.  Preserve view sheds for significant local focal p oints as well as major streets and pedestrian pathways. Staff Analysis: The existing eastern portion of the hospital structure is three stories in size, and is set back significantly from the rest of the N. Main St. The proposed addition will be one story in size and will extend closer towards Main S t, resulting in a cascading effect which will bring the structure down to a m ore pedestrian scale. This proposed expansion will be located far enough away from the taller commercial devel opment to the south that the height differences between the differ ing patterns of development will not be immediately apparent. E. Establish an Appropriate Scale for New Buildings that is Compatible with the Character of the District.  Reflect the widths and bay divisions of other historic buildings along the block.  Incorporate evenly spaced vertical div isions to divide a wide building into bays of appropriate widths to reduce the scale.  Create visual interest at the ground level to emphasize the human scale of the building by incor porating functional elements like traditional storefronts and entrances. Staff Analysis: The proposed expansion will match the width of the existing emergency room bay and will incorporate a glass entranceway and landscaping in o rder to generate visual interest at the ground level. F. Choose a Roof F orm that is S imilar to Those of T raditional Commercial Buildings in the District.  Avoid roof types that become prominent visual features for the building  Use a parapet to screen satellite dishes or rooftop mechanical equipment 8 Staff Analysis: The proposed plans detail a flat aluminum roof to match the appearance of roo f elements throughout the hospital complex. The rear portions of the roof area will be used t o house utility and mechanic al equipment but will n ot be visi ble from the right of way on W. Canal St. or N. Main St due to the implementation of rooftop parapet walls. G. Arrange Windows and Doors to R eflect the T raditional Size, Proportion, Spacing, Rhythm and Alignment of Others in the District.  Keep the proportion of window to wall area for both upper and lower façades compatible to that of existing buildings.  Incorporate a ground floor storefront into the design of a new building. A contemporary design may be appropriate if based on traditional storefront features and if it is compatible with the visual character of the district.  Orient the primary entrance to the street.  Continue the general alignment spacing, size, profile, and proportion of the upper floor of adjacent buildings.  Use traditional styles found in the district as the basis for new doors and windows. Staff Analysis: The submitted plans detail numerous first floor windows, matching the design and aluminum material of existing windo ws on th e original structure . This r equest utilizes evenly spaced vertical windo ws in order to break up s ections of otherwise unarticulated façade along the eastern, southern, and northern facades. As stated earlier in the report, storefront style window elements have been incorporated into the design to delineate the emergency room entranceway. H. Reinterpret Traditional Decorative Elements in a Contemporary Manner.  Incorporate simplified architectural features that reflect, but do not duplicate, similar features found on existing historic b uildings in the district  Concentrate architectural detail in areas that traditionally featured detail , such as floor transitions, window surrounds, and cornices or pediments  Use detail that is three dimensional to add visual interest and texture to the facade Staff Analysis: The original structure being expanded is minimally ornamented. The plans for the new structure continue this mini malist aesthetic with cl ean lines, and architectural/visual interest being created through materials transition resulting 9 in a more modern aesthetic. I. Chose Materials that are H armonious with T raditional M aterials F ound in the Historic District.  Select materials that are visually compatible with and complementary to the existing architectural character of the district.  Choose materials with simil ar scales, color, texture, and finish as those used historically in the district.  Contemporary materials that are compatible with his toric materials may be acceptable if the material conveys the visual qualities of traditional materials  Employ uniform primary wall materials on all sides of the building. Staff Analysis: The materials and design of t his emergency room expansion are designed to match the appearance of the existing struc ture in order to create a seamless expansion to the building. The colo r of the masonry, window material and finish , and finish of metal tr im will be coo rdinated with the ex isting st ructure, whi ch will resu lt in a modern look that does not attempt to convey false historic character. J. Select a Coordinated Color P alette Informed by H istoric Precedent and Compatible with Adjacent Buildings and the District as a Whole. Staff Analysis: The selected masonry will match the hospital’s existing red brick and stone and is not proposed to be painte d. The aluminum windows and trim will also m atch the light finish of the al uminum systems th roughout the existing building. The result will be a neut ral colored structure that appears to be a continuat ion of the existing structure. 4.12 Signs and Awnings A. Place Signs in a M anner that is Complementary, or S ubordinate to, t he Architecture of the Building.  Locate signs on flat, unadorned areas, such as hori zontal sign bands, existing signboards, or vertical piers.  Place signs at or below the storefront cornice for a ground level business.  Position permissible portable signs so that they do not interfere with pedestrians or traffic sight lines at intersections.  Pylon, monume nt, and other freestanding signs are generally not appropriate in the Downtown Historic District. Wher e determined appropriate, freestanding signs shall be monument style. 10 C. Limit the Size and Number of Signs per Building.  Limit sign area to less than 25 percent of the building front wall.  Relate sign proportions to the element on which it is placed.  Size the lettering and graphics of window signs to be clearly legible, but not block views into or from display windows.  Limit the si ze of transom signs to avoid blocking light to the interior or obscuring the transom glazing.  Use signs that are pedestrian oriented and of a scale comfortable for a walking customer. D. Use Appropriate Materials t hat Complement the S tyle and M aterials of the Building.  Use traditional sign materials (finished wood, glass, metal, brass letters) or contemporary products that have the same visual characteristics.  Finish sign edges to provide character and durability.  Limit the use of neon signs to the i nterior of b uildings. Ne on signs on building exteriors are not appropriate.  Shiny plastic products, including internally -illuminated, plastic box signs are not appropriate.  Avoid painting signs directly on unpainted masonry walls.  Use colors that complemen t the b uilding, including accent and trim colors.  A maximum of three colors is recommended per sign, although more may be appropriate in some cases.  Use colors that relate to the overall color scheme of the building.  Use light or neutral colors on window signs—such as white or gold leaf— that are easy to read.  Minimize solid painted background behind window lettering, as it reduces transparency. F. Design Signs to be Simple and Legible.  Keep sign message simple, easy to read, and in scale with the building and elements on which it is placed.  Avoid lettering that is difficult to read or overly intricate.  Use no greater than two or three distinct typefaces.  Consider the use of a symbol and logo rather than words. J. Choose Simple, Compatible Lighting Fixtures to Illuminate Signs  Illuminate signs indirectly with a shielded light source 11  Install fixtures and associated wiring inconspicuously to avoid detracting from the appearance of the building and without obscuring or damaging historic materials and features  Limit internal illumination to a system that backlights individual letters only. Staff Analysis: At this t ime, the only signage proposed for the si te is an aluminum wall sign on the eastern façade denoting the entrance to the emergency room area. This will be similar in material and appearance as the existing sign, shown in the photo to the right. The p roposed si gnage w ill be internally illuminated, and is consistent with the design review guidelines. Any subsequent signage will require further Historic Preservation Design Review. III. STAFF RECOMMENDATION Staff recommends approval of this request. Prisma Health Tuome y Hospital is a specialized use separate from but compatible with the development occurring in the res t of the downtown district. The structu re being modified is not hist oric in nature, and the proposed a ddition is compatible with the design of the current structure. IV. DRAFT MOTION 1.) I move that the Sumter Historic Preservation Desi gn Review Committee approve HP -20-09 in accordance wi th the m aterials, photographs, and construction det ails submitted an d referenced in the Staff Report based on compliance with Design Review Guidelines. 2.) I move that the Sumter Historic Preservation Design Review Committee deny HP-20-09 3.) I move that the Sumter Hist oric Preservation Design Review Committee enter an alternative motion. 12 V. HISTORIC PRESERVATION- MARCH 26, 2020 The scheduled March 26, 2020 Histo ric Preservation Design Revi ew Committee meeting was postponed by order of City C ouncil, in keeping with Centers for Disease Control (CDC) guidelines related to the COVID-19 virus. VI. HISTORIC PRESERVATION – JUNE 25, 2020

Source: City of Sumter website. First collected Nov 14, 2026.