TRC Minutes 11.05.26 Page 1 of 6
TECHNICAL REVIEW COMMITTEE MINUTES
Thursday, November 5, 2026 – 10:00 A.M.
Training Room/Zoom
NEW APPLICATIONS
CR-26-55: Courtesy Review – Subdivision Discussion at 4825 Little River Neck Road
Attending
Customer
Representatives:
Thomas Winstead, Applicant
Staff Comments
Public Works: 1. Provide conceptual plan for review.
2. Public water available.
3. Public sewer available with extension by developer. Evaluate extension of
existing gravity sewer or utilize a new pump station/force main.
4. If using a cul-de-sac, minimum hard surface diameter is 96 feet (emergency
vehicle requirement). Refer to Street Planning Manual for approved street
standards and utility placements.
5. SCDOT encroachment permit required for any work within the Little River
Neck Rd. R/W.
6. Must meet stormwater design standards.
7. Additional comments reserved.
Zoning: 8. 10,000 square foot minimum lot size.
9. 80' minimum lot width.
10. Lots on cul-de-sacs, lot width is reduced by 33%, 53.6' width at 25' setback line.
11. Possible three lots with cul-de-sac.
12. Right of way would eat up enough square footage to make 4 lots unfeasible due
to 10,000 lot minimum.
13. Need dimensional subdivision drawing depicting proposed lots and/or
proposed right-of-way and lots.
Building: No comments
Fire: 14. All portions of the building must be within required fire access distance. Revise
the plan to demonstrate compliance.
15. Provide a fire apparatus turning exhibit to confirm that emergency vehicles can
access all areas of the site.
16. Fire hydrants shall be spaced in accordance with City standards (maximum
spacing measured along the roadway). Provide a dimensioned exhibit
demonstrating compliance.
Planning: 17. If the proposed subdivision involves the creation of a new street/right-of-way or
extension of utilities, it will be classified as a major subdivision and will require
submission of a sketch plan, preliminary plat, and final plat for review and
approval by the Planning Commission. If the proposed lots front on an existing
street and do not involve a new street or utility extensions, the subdivision may
qualify as a minor subdivision and be eligible for staff review and approval in
accordance with Section 20-30 of the Land Development Regulations.
TRC Minutes 11.05.26 Page 2 of 6
CR-26-56: Courtesy Review – Addition at Our Lady Star of the Sea Catholic Church at 1108 8th Avenue South
Attending
Customer
Representatives:
Greg Atkinson, Applicant
Staff Comments
Public Works: 1. Over 5- bedrooms. Additional impact fees will be assessed during the building
permit application review process.
2. Per the city’s BMP design manual – “If the redevelopment project area is less
than fifty (50) percent of the existing developed condition area and includes the
addition of impervious area, then all standards of the SWDM apply to the
additional impervious area.” Provide storage for the runoff from the additional
impervious areas. Recommend perc pipe with yard drains with an overflow
catch basin. Storage volume to accommodate the 100-year, 24-hour storm event.
3. Confirm existing meter size is adequate. Add SCDES approved backflow
device.
Zoning: 4. Site plan needed for 6 bedroom/sleeping area home.
5. Off-site parking document needs recorded.
6. Noncontiguous, off-street parking:
The owner of a parcel of land may provide the required automobile storage and
parking spaces on lands on which the use is situated and on levels which are not
contiguous to the lands on which the use is situated, provided that all of the
conditions set forth herein are satisfied.
All residential uses in all zoning districts (except overlay zones) and commercial
uses in the RC (Resort Commercial) district shall have a minimum of seventy-
five (75) percent of all required parking spaces located on lands on which the
use is situated and a maximum of twenty-five (25) percent of such spaces may be
located off-site where the farthest parking space is located no farther than three
hundred (300) feet from the principal sit.
The owner shall impose restrictions on such non-contiguous parking lands by a
recorded declaration which shall require written consent of the city to release
such lands from restriction. Such recorded declaration shall run with the land
and shall provide that so long as the use exists, the lands shall be utilized
exclusively as a parking area serving the use except as follows:
No non-contiguous parking lands shall be located in any zone other than one (1)
for which the use is permitted.
Paved sidewalks, as per City of North Myrtle Beach specifications, from the
noncontiguous lot to the principal development shall be provided at the owner's
expense.
The noncontiguous parking lands shall be clearly marked by appropriate signage
indicating that such lands are devoted to parking area serving the use and such
signage shall be maintained in good state of repair.
The non-contiguous parking lands shall be physically improved, landscaped, and
surfaced in the same manner as the parking area located on the lands on which
the use is situated. All surface water must be retained on-site or drained into
public storm water drainage ways in accordance with accepted engineering
practices as approved by the city engineer.
TRC Minutes 11.05.26 Page 3 of 6
Each parking space shall be unobstructed and shall be so arranged that any
vehicle may be moved into and out of each space without moving any other
vehicle.
No certificates of occupancy shall be issued for any units until the required
number of parking spaces, with ingress and egress, are fully constructed for the
number of units for which certificates of occupancy are requested. In the event
any of the required parking spaces for units for which certificates of occupancy
are requested are provided on non-contiguous parking lands, such lands shall be
fully constructed and restricted by deed in accordance with all of the standards
of this chapter before the certificates of occupancy shall be issued.
Off-site parking areas shall be cleared and graded within ninety (90) days of
issuance of a building permit. The off-site parking area shall then be reserved for
employee parking until the project receives a certificate of occupancy or is
released at the discretion of the chief building inspector.
All parking on noncontiguous lots shall be in accordance with section 23-42,
parking design criteria.
Building: 7. Submit required architectural and engineered plans when applying for permits.
Fire: No comments
Planning: No comments
TRC-26-39: Site-Specific Development Plan –820 Bently Lane
Attending
Customer
Representatives:
No representative
Staff Comments
Public Works: 1. A grading and drainage plan is required for this site since the proposed driveway
crosses a significant wetland and drainageway that conveys runoff from
upstream properties and the existing retention pond. Appropriately sized
culvert(s) must be designed and installed beneath the proposed driveway to
safely convey anticipated stormwater flows and prevent adverse impacts to both
upstream properties and to the subject property. Note twin 48” RCPs are
located just downstream within this drainage way crossing Inlet View Drive.
2. Provide storm drainage report. A licensed professional engineer shall evaluate
the contributing drainage area, calculate the anticipated stormwater flows
crossing the property, and determine the appropriate size and configuration of
the required culvert(s).
3. Provide ACOE wetland impact permit or letter from the ACOE stating no
permit is required. All wetland impacts must be evaluated by the Army Corps
of Engineers. Current wetland delineation/survey/JD determination may be
required by the Corps.
4. The drainage calculations and grading & drainage plan must be signed and
sealed by South Carolina registered professional engineer.
5. Provide erosion and sediment control plan. Provide double row silt fence along
wetland areas to remain.
6. No water and sewer taps were installed for this parcel during original
construction. Show location of new water and sewer taps.
7. Provide retaining wall structural details.
TRC Minutes 11.05.26 Page 4 of 6
8. Additional comments may be forthcoming pending further review or receipt of
revised documents.
Zoning: 9. Please overlay trees on a clean version of the plot plan so we can see proposed
removals.
Building: No comments
Fire: No comments
Planning: No comments
TRC-26-41: Site-Specific Development Plan – Six Sleeping Area Home at 500 South Ocean Boulevard
Attending
Customer
Representatives:
Mark Donovant, Engineer
Staff Comments
Public Works: 1. Provide stormwater/pipe sizing calculations.
2. Must meet 25 year – 24-hour storm event if there is a tie-in to an existing storm
system.
3. Must be able to hold the 100 year – 24-hour storm event if there is no tie-in to
an existing storm system.
4. Address sheet flow to DOT right-of-way. Capture sheet flow with additional
perc pipe as needed. Provide perc pipe along western property line within the
building setback area. Contain runoff on-site; eliminate common lot line swale.
5. Erosion control plan needed.
6. City to make taps and install new water and sewer services to the property line.
Revise note accordingly.
7. Provide SCDOT encroachment for driveway on S. Ocean Blvd and storm drain
tie-in on 5th Ave S. (required prior to sign-off on construction plans).
Zoning: No comments
Building: 8. Must meet all current City flood zone ordinances including the 1ft freeboard
requirement.
Fire: No comments
Planning: 9. Provide sidewalk along Ocean Blvd. right-of-way.
TRC-26-40: Site-Specific Development Plan – Six Sleeping Area Home at 500 South Ocean Boulevard
Attending
Customer
Representatives:
Mark Donovant, Engineer
Staff Comments
Public Works: 1. Provide stormwater/pipe sizing calculations.
2. Must meet 25 year – 24-hour storm event if there is a tie-in to an existing storm
system.
3. Must be able to hold the 100 year – 24-hour storm event if there is no tie-in to
an existing storm system.
4. Address sheet flow to DOT right-of-way. Capture sheet flow with additional
perc pipe as needed. Provide perc pipe along western property line within the
building setback area. Contain runoff on-site; eliminate common lot line swale.
5. Erosion control plan needed.
TRC Minutes 11.05.26 Page 5 of 6
6. City to make taps and install new water and sewer services to the property line.
Revise note accordingly.
7. Provide SCDOT encroachment for driveway on S. Ocean Blvd and storm drain
tie-in on 5th Ave S. (required prior to sign-off on construction plans).
Zoning: No comments
Building: 8. Must meet all current City flood zone ordinances including the 1ft freeboard
requirement.
Fire: No comments
Planning: 9. Provide sidewalk along Ocean Blvd. right-of-way.
TRC-26-37: Site-Specific Development Plan – Eight Sleeping Area Single-Family Home at 2503 Holly Drive
Attending
Customer
Representatives:
Tucker Davis, Applicant
Staff Comments
Public Works: No comments
Zoning: 1. No parking space shall have direct access to a street, and no vehicle shall extend
into a public right-of-way. Each parking space shall be unobstructed and shall be
so arranged that any vehicle may be moved into and out of such space without
moving another vehicle.
2. Any room or space that provides privacy and separation from common living
areas and could function as a sleeping space. Rooms labeled as offices, dens,
bonus rooms, or similar shall be considered sleeping areas where the design
includes features consistent with sleeping use, such as: Enclosure with walls and
a door or defined separation or layout and dimensions consistent with habitable
space.
3. Parking shall be located on the property.
4. Reducing to 7 bedrooms/sleeping areas. New parking requirement of 4 spaces
is approvable as depicted.
Building: No comments
Fire: 5. If this addition is per the IRC, no specific fire code requirements are needed.
Planning: No comments
Z-26-20: Major Planned Development District Amendment – Vehicle Storage and Clubhouse at 8417 Water Tower
Road
Attending
Customer
Representatives:
Ed McDowell, Owner
Staff Comments
Public Works: No comments
Zoning: No comments
Building: No comments
Fire: No comments
Planning: No comments
TRC Minutes 11.05.26 Page 6 of 6
BLD-26-5263: Building Permit – Discussion on Barefoot Resort Outfall #2 Repairs
Attending
Customer
Representatives:
Edward Porcher, Engineer and HOA Members
Staff Comments
Public Works: No comments
Zoning: No comments
Building: No comments
Fire: No comments
Planning: No comments
BLD-26-5343: Building Permit – Discussion for 410 Hillside Drive South
Attending
Customer
Representatives:
No representative
Staff Comments
Public Works: No comments
Zoning: No comments
Building: No comments
Fire: No comments
Planning: No comments