TRC Minutes 04.09.26 Page 1 of 5
TECHNICAL REVIEW COMMITTEE MINUTES
Thursday, April 9, 2026 – 10:00 A.M.
Training Room/Zoom
NEW APPLICATIONS
CR-26-20: Courtesy Review – 15-Sleeping Area Single Family at 2800 N Ocean Boulevard
Attending
Customer
Representatives:
Tim Dunkin, Developer
Staff Comments
Public Works: 1. Re-configure parking area, backing out onto Ocean Boulevard is not
allowed.
2. Add SCDES approved backflow device on customer side of water service.
3. Must meet the 25 year - 24-hour storm event if there is an overflow tie-in
to an existing storm system. Must hold the 100-year - 24-hour storm event
if no overflow is available.
4. Show pervious paver details, including maintenance schedule.
5. Maximum driveway width for a single-family home is 24 feet (within the
public right-of-way).
6. CZC Certification needed for all work beyond the SCDES setback line.
7. Additional comments pending receipt of revised plans.
Zoning: 8. Provide a detailed parking calculation demonstrating compliance with
ordinance requirements.
9. 8 parking spaces are required.
10. 9'X19' spaces and each space shall be able to back into a drive aisle, without
moving any other vehicle, and head out onto the street.
Building: 11. Install temporary covered walkway over public beach access.
12. Structure must meet all current City/FEMA flood zone ordinances and
requirements.
Fire: 13. The underground details for the fire lane need to be added to the plans and
indicate the following:
- Underground piping NFPA 24
- Piping to meet standards (See City of North Myrtle Beach Public Utilities
Guidebook)
- Fittings to meet standards (See City of North Myrtle Beach Public Utilities
Guidebook)
- Bituminous coating applied (NFPA 24)
- 36 in. Burial depth (NFPA 24)
- Trace wire for CPVC piping
- Visual inspection before covering
- Proper thrust blocking (See City of North Myrtle Beach Public Utilities
Guidebook)
- Hydro test 200 psi/2hrs (NFPA 24)
- Flush pipe (NFPA 24)
- NFPA 24 certificate (NFPA 24)
TRC Minutes 04.09.26 Page 2 of 5
Planning: No comments
CR-26-21: Courtesy Review – 15-Sleeping Area Single Family at 2802 N Ocean Boulevard
Attending
Customer
Representatives:
Tim Dunkin, Developer
Staff Comments
Public Works: 1. Re-configure parking area, backing out onto Ocean Boulevard is not
allowed.
2. Add SCDES approved backflow device on customer side of water service.
3. Must meet the 25 year - 24-hour storm event if there is an overflow tie-in
to an existing storm system. Must hold the 100 year - 24-hour storm event
if no overflow is available.
4. Show pervious paver details, including maintenance schedule.
5. Maximum driveway width for a single-family home is 24 feet (within the
public right-of-way).
6. CZC Certification needed for all work beyond the SCDES setback line.
7. Additional comments pending receipt of revised plans.
Zoning: 8. Provide a detailed parking calculation demonstrating compliance with
ordinance requirements.
9. 8 parking spaces are required.
10. 9'X19' spaces and each space shall be able to back into a drive aisle, without
moving any other vehicle, and head out onto the street.
Building: 11. Install temporary covered walkway over public beach access.
12. Structure must meet all current City/FEMA flood zone ordinances and
requirements.
Fire: 13. The underground details for the fire lane need to be added to the plans and
indicate the following:
- Underground piping NFPA 24
- Piping to meet standards (See City of North Myrtle Beach Public Utilities
Guidebook)
- Fittings to meet standards (See City of North Myrtle Beach Public Utilities
Guidebook)
- Bituminous coating applied (NFPA 24)
- 36 in. Burial depth (NFPA 24)
- Trace wire for CPVC piping
- Visual inspection before covering
- Proper thrust blocking (See City of North Myrtle Beach Public Utilities
Guidebook)
- Hydro test 200 psi/2hrs (NFPA 24)
- Flush pipe (NFPA 24)
- NFPA 24 certificate (NFPA 24)
Planning: No comments
CR-26-22: Courtesy Review – Amenity Site Plan at Grande Dunes North
TRC Minutes 04.09.26 Page 3 of 5
Attending
Customer
Representatives:
Drew Flynn, Engineer
Staff Comments
Public Works: 1. Provide a stormwater/grading/erosion control plan for the pavilion area.
2. Show sight triangles on landscape plan.
3. Additional comments pending receipt of revised plans.
Zoning: 4. Minor amendment to PDD.
Building: No comments
Fire: 5. No landscaping within 3 feet circumference of any fire hydrant and all fire
hydrants to be visible and accessible.
Planning: 6. This item will require Planning Commission review prior to approval.
SUB-26-14: Major Preliminary – Indigo at the Preserve – PIN: 38905020010
Attending
Customer
Representatives:
Matthew Norris, Engineer
Staff Comments
Public Works: No comments
Zoning: No comments
Building: No comments
Fire: No comments
Planning: 1. For site plan approval with construction drawings, driveways must be shown and
comply with city standards.
2. On PC agenda for 4/21.
TRC-24-34: Site Plan – Storage Facility - PIN: 35011010138
Attending
Customer
Representatives:
Matt Norris, Engineer
Staff Comments
Public Works: 1. Show the extension of Wyndell Drive as being paved.
Zoning: 2. Buildings shall be earth tones. Condition of BZA approval.
Building: No comments
Fire: 3. Previous comments have not been addressed. See my comments from
4/9/2026:
4. The plan should show designated access lanes around the building to ensure
proper emergency vehicle access.
5. The proposed two fire hydrants do not appear sufficient to meet fire flow
requirements; additional hydrants may be necessary.
Planning: 6. Minor subdivision plat required prior to site plan approval.
CR-25-69: Courtesy Review – Ocean & Oak at 4403 Highway 17 South
Attending
Customer
Representatives:
Matt Norris, Engineer
TRC Minutes 04.09.26 Page 4 of 5
Staff Comments
Public Works: 1. Show water service & water meter size, and location.
2. Records show water meter is 1". Verify size and have engineer verify that the
water line and meter size is adequate for the new building use.
3. Add an SCDES approved backflow device on the customer side of the water
service, if there is not one currently installed.
4. Dumpster needs to be relocated so that it can be serviced from within your
parcel (currently shown having to be accessed from an adjacent parcel).
5. If relocating dumpster behind building, provide a place for the garbage trucks to
turn around, no backing out into public right-of-ways.
6. Any work done in the Highway 17 right-of-way will require an SCDOT
encroachment permit.
7. Additional comments pending receipt of revised plans and technical review.
Zoning: 8. Add the driveway and show additional parking in the rear on the plans.
9. Clarify how far back from the entrance parking is permitted to be installed.
Building: No comments
Fire: 10. Occupancy load of 100 or more will require sprinklers. Will need sealed plans
for the interior up fit.
Planning: 11. Pedestrian connection from building entrance to public sidewalk required.
CR-26-6: Courtesy Review – Compass Resort / Margaritaville -1717 S Ocean Boulevard
Attending
Customer
Representatives:
No Representative
Staff Comments
Public Works: 1. Note the City will not take ownership of the parcel until propane tanks are
removed/relocated off parcel.
Zoning: 2. Variance for zero lot line setback (bathrooms) will be needed for this plan to
work.
3. Lighting plan with photometrics needed.
Building: 4. See fire Marshall note on label tank and maintain distance from tank to
building per IFC.
Fire: 5. Need 12 ft. width for FD access.
6. On grade sidewalk.
7. Need to label LP tanks temporary locations and maintain clearances of LP tanks
from the building per IFC and NFPA 58.
Planning: No comments
CR-26-13: Courtesy Review – Pay Parking Lot at 2004 North Ocean Boulevard
Attending
Customer
Representatives:
No Representative
Staff Comments
Public Works: 1. Show directional signage for one-way drive.
2. Need a 40' paved entrance into the site (measured back from existing road tie-in)
Per city ordinance Article IV, section 23-42, (4)(d)6.
3. Remove parking space #3, interferes with entrance throat length.
TRC Minutes 04.09.26 Page 5 of 5
4. Parking stall #26 appears to be less than 19 feet in depth, extend end island to
make 19 feet.
5. Handicap parking area (stall and striped area) needs to be pavement or concrete.
6. Parking stalls appear to be at 45 degrees, show an angular dimension to verify.
7. SCDOT encroachment permit(s) will be required for any work in the Ocean
Boulevard right-of-way.
Zoning: No comments.
Building: 8. Any portable restrooms must be removed prior to a storm/flooding event.
9. Per previous comment. ADA parking to be surfaced and sidewalk connection.
Fire: No comments.
Planning: 10. This site is governed by a Planned Development District (PDD), which was
originally approved with an emphasis on coordinated design, streetscape, and
overall site aesthetics. Given the prominence of this oceanfront location and its
visibility from Ocean Boulevard and adjacent properties, the inclusion of
landscaping elements would be consistent with the intent of the PDD. The
current submittal does not include landscape details. Providing a landscape plan
that addresses perimeter treatment, buffering, and visual screening would better
align the proposal with the design framework established in the original PDD.
11. Recommend directional signage to beach access.
12. Provide pedestrian connection to beach access points.