COMMONWEALTH OF VIRGINIA
COUNTY OF HENRICO
DEPARTMENT OF BUILDING CONSTRUCTION AND INSPECTIONS
NOTICE
TO: Residential Contractors and Permit Holders
FROM: Building Official
SUBJECT: Interior Braced Wall Inspections
DATE: October 28, 2024
Section 113.3 of the Virginia Uniform Statewide Building Code requires the inspection of all
structural members and fasteners prior to concealment. Section R602.10 of the International
Residential Code establishes the criteria for the design and construction of braced wall
panels. Braced wall panels are typically composed of exterior sheathing, fasteners and
components that are inspected at the time of the veneer inspection. The use of interior wall panels
to satisfy the bracing required by IRC Section 601.10 has created the potential for
confusion. Specifically, failure to coordinate the inspection of the interior braced walls can lead
to costly delays with the approval of the final inspection and issuance of the Certificate of
Occupancy. The Department of Building Construction and Inspections has developed procedural
changes to the residential plan review and inspections processes to help avoid these potential
problems.
Effective July 1, 2007 the Residential Plan Review Engineers will begin affixing a stamp on all
residential building plans that incorporate the use of interior braced wall panels. This stamp will
serve as an indicator that a separate Interior Braced Wall Inspection must be requested prior to
concealment of the fasteners and sheathing with wall finishes (including tape or joint
compounds). The Residential Building Inspectors will make a notation on the approved framing
and insulation inspection tickets to remind the applicant to request a separate Interior Braced Wall
Inspection prior to concealing the fasteners and sheathing with wall finishes. A new inspection
code (025:Interior Braced Wall Inspection) has been created for this purpose. Effective July 1,
2007 this inspection is required whenever the interior braced wall design relies on the use of
interior sheathing panels. The Residential Building Inspectors will verify the proper location of
the braced wall panels as well as the proper use of the fasteners specified by the braced wall
design. The Residential Building Inspectors will continue to confirm compliance of the exterior
braced wall panels as part of the veneer inspection.
Please note that a separate Interior Braced Wall inspection is NOT required for interior braced wall
designs that rely on let-in bracing or other framing components. These bracing designs will be
inspected and approved as part of the framing inspection.
Please call Senior Building Inspector, Richard Moore, or Senior Plans Review Engineer, Corina
Liddle, at (804) 501-4360 if you have any questions regarding the proper installation or inspection
of braced wall panels.
H. Bolman Bowles, PE, CBO
Building Official