Department of Building Construction and Inspections
Henrico County, Virginia
TO: Residential Contractors
SUBJECT: STC/Firewall Inspections
FROM: Henrico County Building Official
DATE: July 1, 2024
Section 113.3 of the Virginia Residential Code requires framing and insulation inspections for Sound
Transmission Classification (STC)/Firewalls that separate attached dwelling units prior to installing
any concealing materials. The inspections may be requested via the Build Henrico Customer Portal
at Build Henrico. Both the Firewall Framing and the Firewall Insulation inspections require that the
complete set of approved construction plans be on-site for use by the inspector.
A third -party “special inspection” may also be used to satisfy the required Firewall Framing and
Firewall Insulation inspections. The following conditions shall apply when using third-party special
inspections.
1. The special inspections must be performed by, or under the supervision of, a Virginia
registered design professional (i.e. Professional Engineer or Architect).
2. A Firewall Framing and Firewall Insulation inspection shall be requested by the permit holder
or the registered design professional no later than 7 a.m. on the day that the inspections are
to be performed. A message shall be entered on the inspection request to indicate that the
framing and insulation inspections are being performed by the registered design professional
and the approximate time of their inspection. Both the Firewall Framing and Firewall
Insulation inspections require that the complete set of approved construction plans be on
site for use by the registered design professional. A Residential Building Inspector or Plan
Review Engineer may visit the site to audit the special inspection.
3. The registered design professional’s report of the completed special inspection shall be
filed with the Department of Building Construction and Inspections prior to obtaining a
final inspection for either of the dwelling units served by the STC/Firewall. A .pdf version
of the inspection report shall be uploaded to the building permit as a supplemental
document on the Build Henrico Portal. An email shall be sent
to STC.FirewallReports@henrico.gov confirming that the report has been uploaded to
the permit. The department will not accept photocopy or faxed reproductions of
completed inspection forms.
4. The registered design professional and contractor will be notified if the inspection report is
rejected. The registered design professional’s report shall indicate the date, start and end
times of the inspections. The report shall also verify the materials used to construct the wall
(e.g. studs, insulation, sheathing, fasteners, etc.), the method of construction applicable to
the specified design, and confirmation that the wall was observed to conform with the
approved plans.
Any STC/Firewall design that was required to be specified prior to issuance of the building permit and
was completed prior to obtaining the Firewall Framing and Firewall Insulation inspections, shall be
subject to a field sound transmission test conducted in accordance with ASTM E336. The test shall
be conducted by, or under the supervision of, a Virginia registered design professional. The test
results shall confirm compliance with the STC rating specified in the approved construction
documents and the P lan of Development/Subdivision approval. The field test report shall be
submitted to the Residential Building Inspections Supervisor and be approved prior to obtaining an
approved final building inspection and issuance of the Certificate of Occupancy. The ASTM E336 test
procedure will not be accepted as an alternative to the required Firewall Framing and Firewall
Insulation inspections for any building permit application filed on or after June 1, 2005.
Fire-rated and Sound Transmission classified floor -ceiling assemblies that are located between
dwelling units will continue to be inspected during the routine framing and insulation inspections
requested for each respective dwelling unit.
Please call our offices at (804) 501-4360 between 8:00 a.m. and 4:30 p.m. if you have any questions
regarding these inspection procedures.