City of Stevens Point
Board of Water and Sewerage Commissioners
January 12, 2026 - 12:00 PM
Stevens Point Public Utilities
300 Bliss Avenue, Stevens Point, WI
OR
Zoom Teleconferencing
Meeting ID: 820 26885705
By Computer: https://us02web.zoom.us/j/82026885705
By Phone: (303) 715-8592
AGENDA
Discussion and Possible Action on:
1. Roll Call.
2. Approval of Minutes
3. Approval of Department Claims
4. Public Hearing/Input on NR 854 document related to Water Supply Service
Area Plans - Joel Lemke
5. Water Supply and Distribution Reports - Eric Southworth
6. Sewage Treatment Operations Report - Chris Lefebvre
7. Construction and Maintenance Report - Shane Kohnen
8. Directors Report - Joel Lemke
9. Adjournment.
The next Water and Sewerage Commission meeting will be Monday, February 9, 2026 at noon.
Any person who has special needs while attending this meeting or needing agenda materials for this
meeting should contact the Director as soon as possible to ensure a reasonable accommodation can be
made. The Director can be reached by telephone at (715) 345-5260, or by mail at 300 Bliss Avenue, P.O.
Box 243 Stevens Point, WI.
Copies of resolutions, reports and minutes of the Board of Water & Sewerage Commission Meetings are on
file at the Admin Office of the Water & Sewage Departments for inspection during normal business hours
from 7:30 A.M. to 4:00 P.M.
Page 1 of 58
City of Stevens Point
Board of Water and Sewerage Commissioners
December 8, 2025 - 12:00 PM
Stevens Point Public Utilities
300 Bliss Avenue, Stevens Point, WI
OR
Zoom Teleconferencing
Meeting ID: 820 26885705
By Computer: https://us02web.zoom.us/j/82026885705
By Phone: (303) 715-8592
MINUTES
Discussion and Possible Action on:
1. Roll Call.
PRESENT: Paul Adamski, Mae Nachman, Carl Rasmussen, Anna Haines and Ray
Schmidt
ALSO PRESENT: Joel Lemke, Eric Southworth, Chris Lefebvre, Shane Kohnen, Jason
Draheim, Jaime Zdroik and resident-Jeff Bushman
2. Approval of Minutes
Motion made by Anna Haines, seconded by Ray Schmidt to approve the November 10,
2025, meeting minutes of the Board of Water & Sewerage Commission.
Ayes all. Nays none. Motion carried.
3. Approval of Department Claims
Motion made by Ray Schmidt, seconded by Carl Rasmussen to approve the
department's claims for the month of November 2025 as audited and read.
Ayes all. Nays none. Motion carried.
4. Commissioner compensation - Joel Lemke
Joel's memo in the packet showed what the Commissioners have been paid in previous
years and what the pay would be for 2026 with the 2.64% COLA that has been
established City-wide.
The Commission's compensation was not always reviewed regularly, so years went by
without increases. In approximately 2020, we reviewed it again, comparing it to what
other City boards make, like Common Council. That helped us come up to where the
pay should be, and we have been applying the cost of living annually since then.
Page 2 of 58
Motion made by Carl Rasmussen, seconded by Anna Haines to approve the 2026
Commissioner's compensation with 2.64% cost of living (COLA) increase.
Ayes all. Nays none. Motion carried.
5. Water Supply and Distribution Reports - Eric Southworth
Eric stated he would look into why the kilowatts were up with pumpage being down
slightly on the reports. Other than that, he had nothing else to add.
6. Sewage Treatment Operations Report - Chris Lefebvre
Chris stated the WWTP met all permit limits for the month of November. He stated the
biosolids dryer is up and running. He also explained that the ammonia level is up
because they can't biologically remove both ammonia and phosphorus at the same
time. Ammonia level is still within permit limits.
7. Construction and Maintenance Report - Shane Kohnen
The Commission reviewed the monthly report. Shane stated he had nothing else to
add. We are currently in winter operation.
8. Directors Report - Joel Lemke
Joel explained to the Commission that he has a memo in the Public Works packet for
the meeting tonight regarding an ordinance amendment that would clarify future utility
extension projects in the Village of Park Ridge. More details regarding this will be
brought back to the Commission next month.
9. Adjournment.
Motion made by Ray Schmidt to adjourn the meeting.
Ayes all. Nays none. Motion carried.
Meeting Adourned: 12:18 P.M.
Page 3 of 58
FINANCES:
Bank balance as of December 1, 2025 2,811,121.57$
Bank deposits recorded in December 2025 5,523,491.25$
8,334,612.82$
CHECKS ISSUED DECEMBER 2025:
60742 Mae Nachman Salary 64.41
60743 Community Foundation of Central WI Employee Contribution 10.00
60744 United Way Of Portage County United Way 63.69
60746 Baker Tilly Virchow Krause LLP Rate Study 4,590.00
60747 Central States H & W Fund Health Insurance Premiums 46,787.17
60748 Vestis Rugs 46.82
60749 AnSer After hours answering services 195.00
60751 Aspirus Medical Group, Inc. Wellness Program 109.00
60754 Baker Tilly Virchow Krause LLP 2025 Audit 204.91
60755 Capital OneTrade Credit Supplies #1666325984 403.12
60756 City Of Stevens Point Retirement, insurance, phone & fuel, workers comp
premiums
22,411.63
60759 Employee Resource Center Inc Monthly EAP Fees 50.83
60761 H&S Protection Systems Inc Annual Alarm Monitoring-Water Office 683.16
60765 Metron-Farnier LLC Meters & shipping 35,913.54
60766 NAPA Cleaning squeegee for truck #1 21.99
60769 Plaski Disposal Dumpster Services 150.00
60772 Springbrook Holding Company LLC Civic pay transaction fees 1.00
60773 Summit Fire Protection Annual fire extinguisher inspection 677.85
60774 U.S. Postal Service Annual Rental PO Box 242 244.00
60775 WI Rural Water Assoc Membership Renewal 50.00
60779 INFOSEND INC Statement & notice printing 2,696.15
60780 Lou's Gloves Nitrile Gloves 424.00
60783 Mastercard Charger, office supplies, Well 11 maintenance,
Conference expenses
2,289.25
60784 Point Supply Shop supplies 86.85
60786 Vestis Rugs 46.82
60788 WI Central Water pipe line lease 100.00
60791 Ferguson Waterworks #1476 Meter gaskets 90.00
60792 First Supply LLC -Plover Inventory 137.64
60793 Community Foundation of Central WI Green Circle Joel Lemke 10.00
60794 United Way Of Portage County United Way 63.69
60797 H&S Protection Systems Inc Remove P. Filtz from alarm panel 72.00
60800 Securian Financial MN Life Insurance Policy #002832L 187.73
60802 Stevens Point Treasurer 2025 Property Taxes 1909 Cypress, #2408.32.3004.02 2,930.90
60803 Teamsters Union Local 662 Union dues 1,731.00
60804 Angela Whelan Refund Check 004740-000, 2101-A Wyatt Ave 72.22
60805 City Of Stevens Point Sept 2025 Concrete, December Asphalt, December
Concrete
6,992.00
60807 Dolce Digital Imaging Meter cards 45.00
60808 Elexco Wellington Ct. Work 7,760.00
60809 Fastenal Company PPE 214.63
60810 Hawkins Inc Chemicals 3,093.88
60811 Heartland Business Systems, LLC Monthly billing for December 199.56
60814 Petty Cash Postage, Supplies, Candy for office 82.63
60815 Mastercard Parts for truck #1, Aluminum fitting, AWS for GIS
server, Water Dept tools for jobs & supplies, Laptop for
Audra B., Background check -Audra B.
1,622.10
60816 WI Department of Natural Resources DNR Certification-Alex Bula 50.00
60817 WRWA WRWA Training Class - Alex Bula 625.00
60818 3K Custom Apparel Jackets embroidered 9.00
60820 Central States H & W Fund Health Insurance Premiums 29,804.17
60822 Ferguson Waterworks #1476 Meter gaskets 49.25
60824 Jerry's Small Engine Supply Co. Job tools 971.39
REPORT TO THE JANUARY 12, 2026
MEETING OF THE BOARD OF WATER AND SEWERAGE COMMISSIONERS
WATER DEPARTMENT
Page 4 of 58
60825 NAPA Paint for shop 68.42
60828 Vestis Rugs 46.82
60829 Community Foundation of Central WI Employee Contribution 10.00
60830 United Way Of Portage County United Way 145.00
60831 American Welding & Gas Inc Utility Garage Supplies 151.35
60832 AnSer After hours answering service 195.00
60833 Capital OneTrade Credit Tools & supplies 152.21
60834 City Of Stevens Point 2025 Street Improvement Project #25-102-Sept, 2025
Street Improvement Project #25-102-November, 2025
Street Improvement Project #25-101
November,Workers Comp Premiums
258,155.91
60835 Fastenal Company PPE - Gloves 154.19
60837 John Fabick Tractor Co Back hoe #8 parts 508.81
60838 Plaski Disposal Dumpster services 75.00
60842 Strand Associates Inc Professional Services Well 12 9,755.02
60843 Nicole Wottreng Refund Check 039247-000, 3933 Doolittle Dr #12 52.80
60844 Wroblewski Concrete Construction, LLC Concrete rings 1,512.00
Transfer Transfer of funds 1,463.49
Business Tax Fee Business Tax Fee 10.00
Bank Fees Bank Fees 1,308.54
WPS Utility Charges 21,283.86
Payroll Payroll 94,976.28
IRS & DOR PR Tax Payroll Taxes 42,773.50
Verizon Cell & iPad Charges Phone & iPad Charges 673.72
DOR Garnishment Garnishment 9.66
HRA Admin Fees Admin Fees 30.00
$ 533,760.81 $ 533,760.81
$ 7,800,852.01
Balance on Hand $ 7,800,852.01
Plus uncleared checks $ 304,185.66
Less checks previously written clearing this month $ 40,824.58
Ending Cash Balance matching Bank Statements 8,145,862.25$
BALANCE ON HAND DECEMBER 31, 2025
TOTAL EXPENSES LISTED
Page 5 of 58
FINANCES:
Bank Balance as of December 1, 2025 6,722,670.93$
Bank Deposits recorded in December 2025 2,840,550.17$
9,563,221.10$
CHECKS ISSUED IN DECEMBER 2025:
60745 Andritz Separation Inc. Biosolids dryer firmware update 7,016.00
60746 Baker Tilly Virchow Krause LLP Rate Study 4,590.00
60747 Central States H & W Fund Health Insurance Premiums 21,143.18
60748 Vestis Rugs & laundry services 219.13
60750 Aquachem of America Inc. Aquachem 15,180.00
60751 Aspirus Medical Group, Inc. Wellness Program 109.00
60752 Atlas Copco Compressors LLC Parts & labor 2,624.86
60753 Badger Laboratories, Inc. Nitrate testing 60.00
60754 Baker Tilly Virchow Krause LLP 2025 Audit 151.34
60756 City Of Stevens Point Retirement, insurance, phone & fuel, workers comp
premiums
10,700.02
60757 Dakota Electric Services Inc Troubleshoot Blower Motor 195.00
60758 Ben Edwards Boot & winter coat allowance-Ben Edwards 368.14
60759 Employee Resource Center Inc Monthly EAP Fees 26.91
60760 First Aid Corp Gloves 488.15
60761 H&S Protection Systems Inc Annual Alarm Monitoring-Old water garage 2,305.20
60762 Harter's Fox Valley Disposal Dumpster Services 702.63
60763 Hawkins Inc Chemicals 585.55
60764 Brad Kucharzak Jean allowance 168.75
60767 NCL of Wisconsin Inc Lab Supplies 675.26
60768 Pace Analytical Services Inc 4th Quarter Mercury Samples 434.60
60770 Security Fence & Supply Co Inc Security gates & fencing 40,769.00
60771 Spee Dee Delivery Service Inc. Shipping Charges 20.47
60773 Summit Fire Protection Annual fire extinguisher inspection 2,259.52
60777 Atlas Copco Compressors LLC New VFD for blower 34,715.95
60778 H&S Protection Systems Inc Annual Alarm Monitoring - Sewage Lab 636.96
60781 Marathon County Treasurer/Solid Waste Sludge hauling 8,960.66
60782 MC Tools and Repair LLC Supplies 1,269.72
60783 Mastercard Office supplies, winter jackets/bibs 399.97
60785 Staab Construction Corp UV Replacement 164,842.00
60786 Vestis Rugs & laundry services 219.13
60787 WDATCP Water lab license renewal 408.00
60789 Wood Street Rental LLC Material lift 84.00
60790 Airgas USA, LLC Nitrogen 2,481.12
60795 AT&T Phone charges 44.98
60796 First Aid Corp Gloves 112.00
60798 Mulcahy Shaw Water Inc Wash press gaskets 340.67
60799 RJB Property Management LLC Refund Check 020264-001, 2101 Wyatt Ave. 5.67
60800 Securian Financial MN Life Insurance Policy #002832L 70.28
60801 Spee Dee Delivery Service Inc. Shipping charges 23.00
60804 Angela Whelan Refund Check 004740-000, 2101-A Wyatt Ave. 130.53
60805 City Of Stevens Point Dec 2025 Concrete & ashphalt, Sept 2025 Concrete 8,541.00
60806 County Materials Corp Lateral replacement 2147 Strongs 844.00
60810 Hawkins Inc Chemicals 561.05
60811 Heartland Business Systems, LLC Monthly billing for December 199.56
60813 NCL of Wisconsin Inc Lab supplies 950.45
60815 Mastercard Supplies, AWS for GIS Server, pump assembly & tubing,
ladder, parts for truck #30, tools, light bulbs, heating boiler
cert, boiler registration renewal, AWS for IT Pipes, Laptop for
Audra B., PPE L. Betro
5,162.85
60816 WI Department of Natural Resources DNR Certification-Jonathan Hankins 50.00
60817 WRWA WRWA Training Class - J. Hankins 625.00
60818 3K Custom Apparel Jackets embroidered 18.00
60819 Brenntag Great Lakes LLC Chemicals 15,582.49
60820 Central States H & W Fund Health Insurance Premiums 21,143.18
60821 CT Laboratories Biosolids Analysis 209.00
60823 Hach Company Chemicals 515.96
60827 Staab Construction Corp Condenser repair 2,113.00
60828 Vestis Rugs & laundry services 219.13
REPORT TO THE JANUARY 12, 2026
MEETING OF THE BOARD OF WATER AND SEWERAGE COMMISSIONERS
SEWAGE DEPARTMENT
Page 6 of 58
60834 City Of Stevens Point 2025 Street Improvement Project #25-102 September &
November, 2025 Street Improvement Project #25-101
November, Workers Comp Premiums
292,076.27
60836 Hach Company Chemicals 223.17
60839 Rasmussen Plumbing & Heating Lateral Replacement Fund-2147 Strongs Ave 11,565.40
60840 Spee Dee Delivery Service Inc. Shipping charges 27.06
60841 Staab Construction Corp UV Final Clarifier - Payment No. 7 109,155.00
60843 Nicole Wottreng Refund Check 039247-000, 3933 Doolittle Dr #12 57.79
Transfer Transfer of funds 11,210.01
HRA HRA Admin Fee 30.00
Verizon Charges Verizon Charges 574.74
WPS Utility Charges Gas & Electric 19,165.40
Sewer Payroll Payroll 63,504.40
Payroll Taxes Payroll Taxes 4,047.12
Bank Fees Bank Fees 1,308.52
$ 895,216.90 895,216.90$
$ 8,668,004.20
Balance on Hand 8,668,004.20$
Plus uncleared checks 459,220.17$
Less checks previously written clearing this month (38,268.57)$
Ending Cash Balance matching Bank Statements 9,088,955.80$
(5,689,000.99)$
*Additional restricted cash of $250,000.00 is invested in CDs. 3,399,954.81$
** Lateral Replacement fund $126,043.06
Less Restricted Balance
BALANCE ON HAND DECEMBER 31, 2025
TOTAL OF EXPENSES LISTED
Page 7 of 58
FINANCES:
Bank balance as of December 1, 2025 288,719.13$
Bank deposits recorded in December 2025 3,339,921.50$
3,628,640.63$
CHECKS ISSUED DECEMBER 2025:
60747 Central States H & W Fund Health Insurance Premiums 11,014.65
60751 Aspirus Medical Group, Inc. Wellness Program 109.00
60754 Baker Tilly Virchow Krause LLP 2025 Audit 151.09
60756 City Of Stevens Point Retirement, insurance, phone & fuel, workers comp premiums 5,003.61
60759 Employee Resource Center Inc Monthly EAP Fees 11.96
60773 Summit Fire Protection Annual fire extinguisher inspection 677.84
60776 Zorn Compressor & Equipment Parts for truck #33 924.23
60783 Mastercard Office supplies 26.02
60799 RJB Property Management LLC Refund Check 020264-001, 2101 Wyatt Ave. 33.09
60800 Securian Financial MN Life Insurance Policy #002832L 45.50
60805 City Of Stevens Point Dec 2025 Concrete & ashphalt, Sept concrete 11,684.00
60811 Heartland Business Systems, LLC Monthly billing for December 199.56
60815 Mastercard Laptop for Audra B., AWS for GIS Server, PPE-J. Hankins 1,455.92
60816 WI Department of Natural Resources DNR Certification-Lucas Betro 50.00
60817 WRWA WRWA Training Class - Lucas Betro 625.00
60818 3K Custom Apparel Jackets embroidered 18.00
60820 Central States H & W Fund Health Insurance Premiums 11,014.65
60826 Safe-Way Bus Transit Inc. CDL Test- L. Betro 200.00
60834 City Of Stevens Point 2025 Street Improvement Project #25-102 September &
November, 2025 Street Improvement Project #25-101
November, Workers Comp Premiums
153,873.13
Bank Fees Bank Fees 1,308.52
Verizon iPad & cell phone charges 498.17
Transfer Transfer of funds 9,938.17
Payroll Payroll 16,896.51
IRS Payroll Taxes 1,778.20
WPS Monthly Utility Charges 342.27
227,879.09$ 227,879.09$
3,400,761.54$
Balance on Hand 3,400,761.54$
Plus uncleared checks 167,282.78$
Less checks previously written clearing this month (5,105.97)$
Ending Cash Balance matching Bank Statements 3,562,938.35$
REPORT TO THE JANUARY 12, 2026
MEETING OF THE BOARD OF WATER AND SEWERAGE COMMISSIONERS
STORM WATER DEPARTMENT
BALANCE ON HAND DECEMBER 31, 2025
TOTAL OF EXPENSES LISTED
Page 8 of 58
FINANCES:
Bank balance as of December 1, 2025 370,720.91$
Bank deposits recorded in December 2025 140.27$
370,861.18$
CHECKS ISSUED DECEMBER 2025:
60812 Millennium Fiber optic cable tag 480.37
480.37$ 480.37$
370,380.81$
Balance on Hand 370,380.81$
Plus checks written after the end of this month -$
Plus uncleared checks
Less checks previously written clearing this month
Ending Cash Balance matching Bank Statements 370,380.81$
REPORT TO THE JANUARY 12, 2026
MEETING OF THE BOARD OF WATER AND SEWERAGE COMMISSIONERS
FIBER (COMMUNITY AREA NETWORK)
BALANCE ON HAND DECEMBER 31, 2025
TOTAL OF EXPENSES LISTED
Page 9 of 58
City of Stevens Point
Department of
Public Utilities &
Transportation
P.O. BOX 243, 300 BLISS AVENUE, STEVENS POINT, WISCONSIN 54481-0243
PHONE 715-345-5260 * FAX 715-345-5369 * stevenspoint.com/water
Joel C Lemke
Director
Phone: 715-345-5266
jlemke@stevenspoint.com
January 8, 2026
MEMO
RE: Water Supply Service Area Plan (NR 854)
Commissioners,
Our January agenda lists a public hearing for comments on the Water Supply Service Area Plan
that we had created by Ruekert-Mielke. This plan requires that we provide an opportunity for
public comment. We have listed the plan on the website as and put a public hearing on this
agenda for those opportunities.
Since we are not a community who draws water from the great lakes basin, this plan will not be
reviewed or approved by the DNR. The DNR has informed me that they will not request or
require a copy of the document. State Statutes simply require it to be created.
The document provided is in draft form. We will take public comment, if any, into consideration
and return the document with staff thoughts and corrections.
No action is needed at the January Commission meeting, just an opportunity to comment from
the public and from the Commission.
Best Regards,
Joel Lemke
Director
Page 10 of 58
2025 Copyright Ruekert & Mielke, Inc.
Draft 2025 Water Supply Service Area Plan
December 11, 2025
Draft 2025
Water Supply
Service Area
Plan
PREPARED FOR:
City of Stevens Point Water Utility
300 Bliss Avenue
Stevens Point, WI 54481
PREPARED BY:
Ruekert & Mielke, Inc.
W233 N2080 Ridgeview Parkway
Suite 300
Waukesha, WI 53188
Page 11 of 58
City of Stevens Point
2025 Water Supply Service Area Plan
TOC-1
12/11/2025
09-10118.100 > 2025 Water Supply Service Area Plan (20251211 Draft).docx
TABLE OF CONTENTS
I. INTRODUCTION ................................................................................................................................ 1
A. PLANNING PERIOD .................................................................................................................... 1
B. SCOPE ......................................................................................................................................... 1
C. STUDY LIMITATIONS AND ASSUMPTIONS ............................................................................. 1
II. EXISTING WATER SYSTEM FACILITIES ......................................................................................... 3
A. SERVICE AREA ........................................................................................................................... 3
B. WATER SYSTEM PRESSURE ZONES ...................................................................................... 3
C. WATER SUPPLY FACILITIES ..................................................................................................... 6
D. WATER QUALITY AND TREATMENT METHODS ..................................................................... 6
E. WATER STORAGE ...................................................................................................................... 9
F. BOOSTER PUMPING FACILITIES............................................................................................ 10
G. INVENTORY OF ALTERNATIVE SOURCES ............................................................................ 10
III. POPULATION AND COMMUNITY GROWTH ................................................................................. 11
A. POPULATION AND POPULATION DENSITY .......................................................................... 11
B. UTILITY SERVICE AREA .......................................................................................................... 11
C. PROJECTED GROWTH AREAS ............................................................................................... 11
D. SUMMARY ................................................................................................................................. 11
IV. WATER REQUIREMENTS ............................................................................................................... 14
A. WATER CONSUMPTION HISTORY ......................................................................................... 14
B. UNIT CONSUMPTION WATER USAGE ................................................................................... 14
C. TEN LARGEST WATER CUSTOMERS .................................................................................... 14
D. NON-REVENUE WATER AND UNACCOUNTED FOR WATER .............................................. 20
E. VARIATIONS IN CUSTOMER DEMANDS AND PUMPAGE .................................................... 21
F. HOURLY DEMAND FLUCTUATIONS ....................................................................................... 23
G. WATER CONSUMPTION AND PUMPAGE PROJECTIONS .................................................... 23
H. SUMMARY OF TOTAL DEMANDS AND PUMPAGE REQUIREMENTS ................................. 24
V. SUPPLY AND STORAGE ANALYSIS .............................................................................................. 26
A. WATER SUPPLY ANALYSIS .................................................................................................... 26
1. Existing Recommended Reliable Supply Capacity ............................................................. 27
B. WATER STORAGE ANALYSIS ................................................................................................. 28
1. Water Storage Needs .......................................................................................................... 28
2. Effective Storage Volumes .................................................................................................. 29
3. Recommended Existing Water Storage Volumes ............................................................... 29
C. SUPPLY AND STORAGE RESULTS ........................................................................................ 32
Page 12 of 58
City of Stevens Point
2025 Water Supply Service Area Plan
TOC-2
12/11/2025
09-10118.100 > 2025 Water Supply Service Area Plan (20251211 Draft).docx
D. SUMMARY ................................................................................................................................. 32
VI. CONCLUSION AND RECOMMENDATIONS................................................................................... 33
A. KEY FINDINGS AND RECOMMENDATIONS ........................................................................... 33
1. Population Projections ......................................................................................................... 33
2. Water Demands ................................................................................................................... 33
3. Supply .................................................................................................................................. 33
4. Storage ................................................................................................................................ 33
5. Other Considerations ........................................................................................................... 33
B. CONSISTENCY WITH OTHER PLANS AND AGREEMENTS ................................................. 33
C. PLAN IMPLEMENTATION ......................................................................................................... 34
D. PUBLIC PARTICIPATION .......................................................................................................... 34
E. UPDATES TO PLAN .................................................................................................................. 34
FIGURES
Figure II-1: Existing Water System ............................................................................................................... 4
Figure II-2: Existing Water System Schematic .............................................................................................. 5
Figure III-1: Proposed Developments ......................................................................................................... 13
Figure V-1: Storage Components ............................................................................................................... 28
Page 13 of 58
City of Stevens Point
2025 Water Supply Service Area Plan
TOC-3
12/11/2025
09-10118.100 > 2025 Water Supply Service Area Plan (20251211 Draft).docx
TABLES
Table II-1: Wells and Treatment Facilities ..................................................................................................... 7
Table II-2: Annual Well Pumpage Records ................................................................................................... 8
Table II-3: Raw Water Iron and Manganese Concentrations. Exceedances are shown red. ....................... 8
Table II-4: Well 12 PFAS Concentrations ..................................................................................................... 9
Table II-5: Water Street EST ....................................................................................................................... 10
Table II-6: Bliss Avenue EST ...................................................................................................................... 10
Table III-1: Population Trends & Projections .............................................................................................. 12
Table IV-1: Historical Water Pumpage and Sales ...................................................................................... 15
Table IV-2: Historical Customer Summary .................................................................................................. 16
Table IV-3: Water Consumption History ..................................................................................................... 17
Table IV-4: Water Usage per Customer per Day ........................................................................................ 18
Table IV-5: Historical Per Acre Usage ........................................................................................................ 18
Table IV-6: Historical Per Capita Usage ..................................................................................................... 19
Table IV-7: Ten Largest Water Customers ................................................................................................. 20
Table IV-8: Daily Pumpage Variations ........................................................................................................ 22
Table IV-9: Water Sales Projections to Planned Developments................................................................. 23
Table IV-10: Annual Water Sales and Pumpage Projections ..................................................................... 24
Table IV-11: Future Pumpage Projections .................................................................................................. 25
Table V-1: Existing Reliable Supply Capacity ............................................................................................. 27
Table V-2: Existing Recommended Reliable Supply Capacity ................................................................... 27
Table V-3: Effective Storage Volumes ........................................................................................................ 30
Table V-4: Existing and Projected Supply and Storage Requirements ...................................................... 31
Page 14 of 58
City of Stevens Point
2025 Water Supply Service Area Plan
1
12/11/2025
8166-10118.100 > 2025 Water Supply Service Area Plan (20251211 Draft).docx
I. INTRODUCTION
In June of 2024, Wisconsin Administrative Code (WAC) NR 854 was released, requiring many
public water utilities to create water supply service area plans. This requirement applies to public
water systems that withdraw from the waters of the state and that serve a population of 10,000 or
more. Water systems are required to have a Water Supply Service Area Plan (WSSAP) prepared
before the end of the year 2025. In addition to preparing a WSSAP, a water system is required to
obtain approval from the Wisconsin Department of Natural Resources (WDNR) if either of the
following conditions apply:
• A general or individual permit is needed
• The water system is requesting a new or increased diversion of Great Lakes water
The City of Stevens Point (City) has a population of about 26,619 and is required to prepare a
WSSAP; however, neither of the above criteria apply and therefore the Utility is not required to
obtain WDNR approval. The City of Stevens Point Water Utility (Utility) withdraws its water from the
waters of the state with its five groundwater wells; however, the Utility does not divert Great Lakes
water nor plans to do so in the future. Therefore, this WSSAP is prepared to meet the requirements
of NR 854.
A. Planning Period
This WSSAP uses a 20-year planning period and expires in the year 2045. This plan is
required to be reviewed at least every 5 years and updated as necessary (NR 854.05). Current
and future water needs were evaluated over a 20-year planning period with consideration given
to projected future water needs extending to the year 2045.
B. Scope
This plan uses a systematic approach to introduce and expand basic planning concepts. A
review of existing water system facilities is summarized in Chapter II. Population, community
growth, and water consumption projections serve as the foundation for evaluating and
identifying recommended improvements to the system and are introduced in Chapter III. The
assumptions and conclusions presented in Chapter III were used to develop projections of
water requirements that are presented in Chapter IV. The developed water requirements are
used in Chapter V to summarize the evaluation of the water system supply and storage needs.
Because needs change with time, comprehensive planning is a continuous function; therefore,
the longer-term projections and improvements discussed in this report should be periodically
reviewed, reevaluated, and modified, as necessary, to ensure the adequacy of future planning
efforts. Proper future planning will help ensure that system expansion is coordinated and
constructed in the most effective manner.
C. Study Limitations and Assumptions
The following limitations and assumptions underlie the work elements of this plan:
1. The primary purpose of this WSSAP is to develop a system plan to guide the extension of
adequate water supply services by the Utility to existing and probable future development
within the planned service area. This WSSAP includes an analysis of supply facilities such
as wells and well pumps, but it does not include an analysis of distribution facilities, such
as water mains and booster pumping.
Page 15 of 58
City of Stevens Point
2025 Water Supply Service Area Plan
2
12/11/2025
8166-10118.100 > 2025 Water Supply Service Area Plan (20251211 Draft).docx
2. Recommendations resulting from the planning efforts are to be consistent with current
federal, state and local regulations regarding facility design.
3. The investigation is limited to a review of existing available water quality data and does not
include any sampling, laboratory work, or pilot testing.
Page 16 of 58
City of Stevens Point
2025 Water Supply Service Area Plan
3
12/11/2025
8166-10118.100 > 2025 Water Supply Service Area Plan (20251211 Draft).docx
II. EXISTING WATER SYSTEM FACILITIES
This chapter presents a summary of the existing water system components of the Utility water
system. The various facilities operated and maintained by the Utility include:
• Seven groundwater wells, one of which is temporarily offline and one of which is not yet
operational
• Two elevated water storage tanks
• A network of transmission and distribution water mains
The general location and layout of the water system facilities are illustrated in Figure II-1 and a
schematic is shown in Figure II-2.
A. Service Area
The service area of the Utility includes the entire municipal boundary of the City. There are
plans expand the water service area beyond the current boundaries of the City, as described in
the “East Park Commerce Center Water System Study” that was done by Ruekert & Mielke,
Inc. in July 2025 (the EPCC Study). The existing and planned service areas are shown in
Figure II-1. The existing and planned service areas are completely within the Mississippi River
Basin.
B. Water System Pressure Zones
The Utility’s water distribution system currently consists of one pressure zone, but a new
pressure zone is planned to be developed in the future, as illustrated in Figure II-1, as
described in the EPCC Study. Because the City boundaries encompass an area of varied
elevations, the future boosted pressure zone will be necessary to provide adequate distribution
system pressures as the water system expands to the east and to the north.
The main pressure zone is currently the only pressure zone, but a new pressure zone is
planned to be developed, as described in the EPCC Study. The ground elevations currently
served by the main pressure zone range from approximately 1,068 ft to 1,147 ft. The future
pressure zone, shown in Figure II-1, is planned to develop starting at the East Park Commerce
Center and will serve areas of higher elevation east of the main pressure zone. The elevations
that are planned to be served by the future pressure zone range from about 1,099 ft to 1,189 ft.
This boosted pressure zone is planned to include an elevated storage tank (EST) and will be
supplied by several booster stations.
Page 17 of 58
Page 18 of 58
Well 7
2,100 GPM
0.75 MG0.75 MG
Existing Water System Schematic
City of Stevens Point
Portage County, WI
December 2025
Main Pressure Zone
LEGEND
ELEVATED TANK
VOLUME (MG) AND OVERFLOW
ELEVATION (FEET)
WELL AND PUMP
RATED CAPACITY (GPM)
900 GPM
Water Street
Elevated Tank
Well 11
5,100 GPM
Bliss Avenue
Elevated Tank
EL. 1,252 FT USGS
EL. 1,252 FT USGS
1.0 MG
0.75 MG0.75 MG
Proposed
Well 12
±1,014 GPM
8166-10018 > 101 Water Supply Service Area Plan > Figure II-2_Water System Schematic.vsd
Well 10
1,500 GPM
Well 9
1,500 GPM
Well 6
2,100 GPM
Well 8
1,691 GPM
Well 8
1,691 GPM
Well Field
Treatment Station
Well 11
Treatment
Station
Well 12
Treatment
Station1
Notes:
1. Well 12 will replace Well 4 which has been abandoned. The building that was
used for Well 4 treatment will be reused for Well 12.
Page 19 of 58
City of Stevens Point
2025 Water Supply Service Area Plan
6
12/11/2025
8166-10118.100 > 2025 Water Supply Service Area Plan (20251211 Draft).docx
C. Water Supply Facilities
The City of Stevens Point Water Utility has seven groundwater wells, as shown in Table II-1,
five of which are currently operational. The wells that are currently in operation (Wells 7-11)
have a total supply capacity of 13.7 million gallons per day (MGD). The annual well pumpage is
shown in Table II-2. Pumpage from each well is measured using flow meters at each well
discharge.
Wells 6 through 10 comprise of a well field that pumps to a common treatment station. Well 6
has temporarily been taken offline until filtration equipment for manganese removal is provided.
Wells 10 and 11 are radial collector wells that each have multiple pumps.
Well 12 was constructed in 2024 and is not yet in full operation. Well 12 was constructed to
replace Well 4 which was deactivated in 2019 and abandoned. The Well Site Investigation
Report (WSIR) for Well 12 was approved by the WDNR in 2020. The well construction was
approved in 2022 and completed in 2024. The Utility has plans to construct new iron and
manganese removal facilities by the end of 2026 within the building that was previously used
for Well 4.
D. Water Quality and Treatment Methods
Treatment methods used at each well are also summarized in Table II-1. Wells 6 through 11
include polyphosphate injection for corrosion control, disinfection with gas chlorine, and fluoride
injection. Well 11 is also treated to remove organics, iron, and manganese. The organics
removal process includes coagulation, flocculation, and sedimentation. The iron and
manganese removal process includes greensand filtration. Iron and manganese sample results
from Wells 6 through 12 are shown Table II-3.
Well 6, which is currently offline, is planned to be equipped with filters for iron and manganese
removal. Well 12, which is planned to be put into operation by the end of 2026, will also be
equipped with filters to remove iron and manganese. The treatment facilities will be housed
within the building that was previously used for Well 4, which was abandoned in 2019.
Water samples from Wells 11 and 12 have low levels of perfluoro- and polyfluoroalkyl
substances (PFAS). The PFAS concentrations found in sampling are lower than any existing or
proposed health advisory levels and maximum contaminant levels (MCL), as shown in Table
II-4. The Utility should continue to monitor PFAS levels to ensure that they are stable. Unless
PFAS concentrations increase in future sampling, treatment to remove PFAS will likely not be
needed.
Page 20 of 58
City of Stevens Point
2025 Water Supply Service Area Plan
7
12/11/2025
8166-10118.100 > 2025 Water Supply Service Area Plan (20251211 Draft).docx
Table II-1: Wells and Treatment Facilities
Well Characteristic
Well Field
Well 11 Well 12
(Planned) Well 6
(Offline)1 Well 7 Well 8 Well 9 Well 10
WI Well ID BG711 BG712 BG713 BG714 LG796 WQ159 ACA566
Year Constructed 1967 1967 1967 1968 1994 2010 2024
Depth 90 ft 80 ft 85 ft 80 ft 87 ft 106 ft 83 ft
Diameter 30 in 30 in 30 in 30 in 15 in 236 in 36 in
Static Water Level 19.3 ft 19.1 ft 21.9 ft 20.2 ft 25.6 ft 26.5 ft 33.0 ft
Pump Level 26.3 ft 23.9 ft 30.6 ft 30.7 ft 30.7 ft 39.1 ft 49.0 ft
Pump Type Vertical
Turbine
Vertical
Turbine
Vertical
Turbine
Vertical
Turbine
Vertical
Turbine
Vertical
Turbine -
Capacity 2,100 gpm 2,100 gpm 1,691 gpm 1,500 gpm 4,200 gpm 5,100 gpm 1,014
gpm
Motor Size 200 hp 200 hp 200 hp 200 hp 150/1502 75/75/1502 -
Treatment Methods Well 6
(Offline)1 Well 7 Well 8 Well 9 Well 10 Well 11 Well 12
(Planned)
Polyphosphate Injection (Corrosion
Control) X X X X X X X3
Gas Chlorination (Disinfection) X X X X X X X3
Fluoridation X X X X X X X3
Ultraviolet Radiation Disinfection X
Coagulation/Flocculation/
Sedimentation (Organics Removal) X
Greensand Filtration
(Iron/Manganese Removal) X X3
Notes:
1. Well 6 is temporarily offline and will be on standby until filtration equipment can be provided for manganese removal.
2. Well 10 has two well pumps each with 150 hp motors. Well 11 has 3 well pumps, two with 75 hp motors and one with 150 hp.
3. Treatment method is planned to be provided at Well 12.
Page 21 of 58
City of Stevens Point
2025 Water Supply Service Area Plan
8
12/11/2025
8166-10118.100 > 2025 Water Supply Service Area Plan (20251211 Draft).docx
Table II-2: Annual Well Pumpage Records
Year
Annual Withdrawal (MGY)
Well 4
(Abandoned)
Well 6
(Offline) Well 7 Well 8 Well 9 Well 10 Well 11 Total
2017 77.0 2.6 83.9 317.4 340.7 19.9 987.4 1,828.9
2018 179.3 1.3 90.4 218.2 457.9 19.3 1,030.7 1,997.2
2019 0.5 13.0 93.6 254.9 509.0 1.9 1,040.9 1,913.8
2020 0.4 0.4 41.2 428.3 436.7 2.2 1,043.8 1,953.1
2021 - 0.0 52.4 410.3 607.4 3.9 1,044.4 2,118.5
2022 - 0.0 163.6 540.0 759.5 2.0 1,052.2 2,517.4
2023 - 0.7 254.0 445.6 631.0 41.5 981.1 2,353.9
2024 - 0.1 233.4 464.1 694.4 0.4 1,050.2 2,442.7
Table II-3: Raw Water Iron and Manganese Concentrations. Exceedances are shown red.
Well Sample
Date
Iron
(mg/L)1
Manganese
(mg/L)1
Well 6 3/17/1999 0 0.394
Well 7 3/17/1999 0 0.465
Well 8 3/17/1999 0.018 0.005
Well 9 3/17/1999 0 0
Well 10 3/14/2017 0 0.032
Well 11 12/11/2025 0.06 0.085
Well 12 12/3/2024 0.77 0.31
Notes:
1. Secondary Maximum Contaminant Levels for Iron and Manganese
are 0.3 mg/L and 0.05 mg/L, respectively.
Page 22 of 58
City of Stevens Point
2025 Water Supply Service Area Plan
9
12/11/2025
8166-10118.100 > 2025 Water Supply Service Area Plan (20251211 Draft).docx
Table II-4: Well 12 PFAS Concentrations
PFAS Chemical Name
MCL, ppt Well 11
(3/10/2023)
Well 12
(11/22/2024) Current Future2
PFOA - 4 1.2 2.0
PFOS - 4 1.3 2.4
PFHxs - 10 0.7 2.3
HFPO-DA (GenX) - 10 0.0 0.0
PFNA - 10 0.0 0.0
PFBS - - 1.5 1.5
Combined PFOA & PFOS 70 - 2.5 4.4
Mixture of two or more: PFHxS,
PFNA, HFPO-DA and PFBS1 - 1.0 0.1 0.2
Note:
ppt = Parts per trillion or ng/L
1. Hazard index is calculated per EPA requirements, as follows:
2. More stringent MCLs for PFAS are proposed by the EPA to be effective by Fall
2026. Water systems that exceed any of the MCLs need to provide treatment
solutions by 2029.
E. Water Storage
The Utility operates two ESTs which are located throughout the water distribution system. The
combined storage capacity of all the facilities is 1,750,000 gallons. One EST is a double
ellipsoid tank and the other is a composite tank. Both tanks have an overflow elevation of 1,252
ft. The elevated facilities are identified as follows:
Water Street (Tank #1, Double Ellipsoid) (Table II-5)
Bliss Avenue (Tank #2, Composite) (Table II-6)
There is also a third EST that is planned to be constructed in the future pressure zone, as
described in the EPCC Study. This EST is planned to be a 1-MG composite storage tank with
an overflow elevation of 1,285 ft.
Page 23 of 58
City of Stevens Point
2025 Water Supply Service Area Plan
10
12/11/2025
8166-10118.100 > 2025 Water Supply Service Area Plan (20251211 Draft).docx
Table II-5: Water Street EST
Capacity 1,000,000 gallons
Year constructed 1956
Type Ellipsoid
Construction material Steel
Overflow elevation 1,252 ft
Diameter 75 ft
Head range 35 ft
Height to overflow 168 ft
Table II-6: Bliss Avenue EST
Capacity 750,000 gallons
Year constructed 2004
Type Composite
Construction material Steel & Concrete
Overflow elevation 1,252 ft
Diameter Varies
Head range 40 ft
Height to overflow 172 ft
F. Booster Pumping Facilities
The Utility currently does not have any booster pumping facilities; however, there are plans to
construct three booster stations with the development of the future pressure zone. Preliminary
locations and sizing for these booster stations are discussed in the EPCC Study.
G. Inventory of Alternative Sources
The Utility currently has seven groundwater wells. There are currently no plans to abandon any
of the wells or seek an alternative supply. However, if the need for an alternative supply arises
due to well contamination or failure, the most feasible option to provide an alternative water
supply would be to drill one or more new wells.
Another option that was considered for alternative water supply is establishing a wholesale
connection with a neighboring water system; however, the City of Stevens Point is the largest
municipality in the area and other nearby water systems would likely not have the capacity to
provide large amounts of drinking water to the Utility. While a wholesale connection would be
unlikely to have the capacity to be a primary source of drinking water for the City , it could be a
potential option to serve as an emergency or supplemental source if the need arises. However,
the City has sufficient redundancy in its water supply with seven wells and will likely not serve
to benefit from an emergency connection.
Page 24 of 58
City of Stevens Point
2025 Water Supply Service Area Plan
11
12/11/2025
8166-10118.100 > 2025 Water Supply Service Area Plan (20251211 Draft).docx
III. POPULATION AND COMMUNITY GROWTH
This chapter summarizes the planning assumptions made regarding the City. The population and
community growth discussed here will be used as the basis for the service area water requirement
projections presented in Chapter IV.
A. Population and Population Density
There is generally a close relationship between a community’s population and total water
consumption volumes. As a community’s population may fluctuate up or down, it is anticipated
that the water sales will also fluctuate. Therefore, future water sales can be expected to
generally reflect future changes in service area population. Similarly, commercial and public
water consumption will also tend to vary proportionately with the growth of the community.
Table III-1 summarizes historical population data and estimates of future population for the
City. According to the Wisconsin Department of Administration (DOA), the 2024 population of
the City was approximately 26,619. Comparatively, the 2020 census population was 25,666.
The population has, therefore, grown in recent years having seen an estimated increase of
approximately 3.7% since the 2020 census. Per the United States Census Bureau QuickFacts,
the average household size is 2.06.
Table III-1 includes population projections from both the DOA and the from the City Planning
Department. According to DOA projections, the population of the City is projected to decrease
from 26,619 in 2024 to 22,454 in 2045. However, the population projections provided by the
City Planning Department predict that the population will increase to 27,619 by 2045. The
population projections provided by the City Planning Department, rather than the DOA, are
used in projecting future water demands.
B. Utility Service Area
The service area of the water system encompasses the municipal boundaries of the City and
are shown in Figure II-1. There are about 32 water customers outside of the City’s municipal
boundary: eight in the Village of Whiting and 24 in the Town of Hull. With the planned
development of a new pressure zone, the Utility plans to expand water service beyond its
current service area to encompass future developments to the east and northeast.
C. Projected Growth Areas
Planned growth areas are shown in Figure III-1. The majority of proposed developments are
planned in the future pressure zone and are described in the EPCC Study. The developments
described in the EPCC Study include single- and multi-family residential, commercial, public
authority, and industrial developments. There is another residential development planned near
North Brilowski Road.
For water demand projections, sales of water to the existing service area are assumed to be
correlated with population change. Estimated future water demands to the projected growth
areas are taken from the EPCC Study and are assumed to be additive to projected sales to the
existing service area
D. Summary
This chapter summarizes the primary assumptions regarding future growth within the Utility
service area. The needs and characteristics of the service area will have a direct impact on the
need for the expansion of water system facilities. Therefore, the conclusions discussed in this
Page 25 of 58
City of Stevens Point
2025 Water Supply Service Area Plan
12
12/11/2025
8166-10118.100 > 2025 Water Supply Service Area Plan (20251211 Draft).docx
chapter are used as a primary basis for projecting future water needs, evaluating the adequacy
of existing water system facilities, and determining what water system improvements are
needed to maintain an adequate level of service as population increases.
Table III-1: Population Trends & Projections
Year
Historical Population
Population Change
1970 23,479 ---
1980 22,970 -2.2%
1990 23,002 0.1%
2000 24,551 6.7%
2010 26,717 8.8%
2020 25,666 -3.9%
2024 26,619 3.7%
Year
Projected Population
DOA
Projections1 Change City
Projections2 Change
2030 24,861 -6.6% 26,869 0.9%
2035 24,124 -3.0% 27,119 -3.0%
2040 23,387 -3.1% 27,369 -3.1%
2045 22,454 -4.0% 27,619 -4.0%
Notes:
1. Projections from the DOA.
2. Preliminary population projections provided by the City Planning Department.
0
5,000
10,000
15,000
20,000
25,000
30,000
1970 1980 1990 2000 2010 2020 2030 2040
Population
Year
Population Trends & Projections
Historical Population
DOA Projections
City Projections
Page 26 of 58
Page 27 of 58
City of Stevens Point
2025 Water Supply Service Area Plan
14
12/11/2025
8166-10118.100 > 2025 Water Supply Service Area Plan (20251211 Draft).docx
IV. WATER REQUIREMENTS
Projections of customer demands serve as the basis for capital improvements planning. Several
standard methods were used in this study to project water supply and storage needs based on
estimates of population and community growth. This chapter summarizes the methods used and
the results of those projections.
A. Water Consumption History
Water consumption history reported annually to the Wisconsin Public Service Commission
(PSC) from 2014 to 2024 was reviewed. A summary of historical water sales and pumpage is
provided in Table IV-1. Over the 11-year period, annual water pumpage has fluctuated from a
low of 1.8 billion gallons in 2016 to a high of 2.5 billion gallons in 2023. Although water usage
has fluctuated both up and down, the overall trend over the past 11 years has generally
increased.
A summary of the number of customers in each customer class that is served by the Utility is
provided in Table IV-2. Water sales to individual customer classes are summarized in Table
IV-3. As shown in the tables, the number of residential and multi-family customers, as well as
water sales to these customers, have increased over the past 11 years. The number of
commercial customers and sales to commercial customers have remained relatively stable.
The number of industrial customers has not changed significantly but sales to industrial
customers have increased. Also, the number of public customers remained constant, but sales
to public customers have decreased.
As illustrated in Table IV-2 and Table IV-3, residential customers presently account for 84% of
the Utility’s customers but only approximately 18% of the total sales in 2024. Industrial
customers only make up 0.3% of the total number of customers served by the Utility; however,
about 60% of all sales were to industrial customers in 2024. This is largely due to the Ahlstrom
Paper Mill (formerly the Pixelle Specialty Solutions Paper Mill) which is by far the largest water
customer. The paper mill alone accounts for between 40% and 50% of all water sales .
B. Unit Consumption Water Usage
Tables IV-4 through IV-6 show water usage per customer, per acre, and per capita,
respectively. The water sales per customer show that industrial customers by far use the
highest amount of water, largely due to the paper mill. The water sales per acre are based on
existing land use data from the 2005 City of Stevens Point Comprehensive Plan. The water
sales per capita are based on annual population for each given year.
C. Ten Largest Water Customers
The ten largest individual water users served by the Utility are shown in Table IV-7. According
to billing data, the largest water users served by the Utility include several industrial customers,
two commercial customers, and one multi-family customer.
By a significant margin, the largest water customer is the Ahlstrom Paper Mill (formerly the
Pixelle Specialty Solutions Paper Mill). With all its meters combined, the paper mill used a total
of 1,139 MGY in 2024, resulting in an average daily flow of 3.1 MGD. The paper mill accounts
for more than 95% of all industrial water usage and between 40% and 50% of all water usage
in the Utility. In the past 5 years, the paper mill’s annual water usage has varied from 874 MGY
in 2020 to 1,358 MGY in 2022.
Page 28 of 58
City of Stevens Point
2025 Water Supply Service Area Plan
15
12/11/2025
8166-10118.100 > 2025 Water Supply Service Area Plan (20251211 Draft).docx
Table IV-1: Historical Water Pumpage and Sales
Year Estimated
Population
Total
Pumpage
(MG)
Total
Sales
(MG)
Pumpage
Sold
Non-
Revenue
Water
Water
Losses
Average Day Maximum Day Ratio of
Maximum to
Average Day
Pumpage MGD GPCD MGD Date
2014 27,040 1,896 1,753 92% 8% 6% 5.194 192.1 8.980 July 25 1.73
2015 27,037 1,884 1,734 92% 8% 5% 5.161 190.9 8.417 July 31 1.63
2016 26,895 1,801 1,588 88% 12% 7% 4.933 183.4 8.551 June 22 1.73
2017 26,757 1,826 1,797 98% 2% 6% 5.003 187.0 8.083 July 26 1.62
2018 26,749 1,990 1,944 98% 2% 7% 5.451 203.8 9.586 Aug 17 1.76
2019 26,490 1,909 1,732 91% 9% 10% 5.231 197.5 7.771 Aug 23 1.49
2020 25,666 1,947 1,746 90% 10% 1% 5.333 207.8 9.440 Aug 21 1.77
2021 25,580 2,113 1,697 80% 20% 1% 5.790 226.4 9.550 June 15 1.65
2022 25,954 2,512 2,195 87% 13% 6% 6.883 265.2 10.200 Aug 02 1.48
2023 26,332 2,532 2,271 90% 10% 7% 6.937 263.4 10.940 Jul 07 1.58
2024 26,619 2,439 1,947 80% 20% 17% 6.681 251.0 9.367 Aug 26 1.40
0
500
1,000
1,500
2,000
2,500
3,000
2014 2015 2016 2017 2018 2019 2020 2021 2022 2023 2024
Sales & Pumpage (MGY)
Year
Annual Water Sales and Pumpage
Total Pumpage Total Sales Non-Revenue
Page 29 of 58
City of Stevens Point
2025 Water Supply Service Area Plan
16
12/11/2025
8166-10118.100 > 2025 Water Supply Service Area Plan (20251211 Draft).docx
Table IV-2: Historical Customer Summary
Year
Number of Customers
Residential Commercial Industrial Public
Multi-
Family Total
2014 7,614 1,124 31 177 112 9,058
2015 7,647 1,089 30 176 159 9,101
2016 7,741 1,101 30 179 160 9,211
2017 7,701 1,102 25 139 160 9,127
2018 7,739 1,131 34 176 162 9,242
2019 7,959 1,225 34 194 175 9,587
2020 7,972 1,282 25 167 176 9,622
2021 7,808 1,094 26 167 159 9,254
2022 7,834 1,075 26 165 158 9,258
2023 7,880 1,120 31 166 165 9,362
2024 7,896 1,116 29 167 165 9,373
Residential
84%
Commercial
12%
Industrial
0.3%
Public
2%
Multifamily
2%
2024 Customer Summary
Residential Commercial Industrial Public Multifamily
Page 30 of 58
City of Stevens Point
2025 Water Supply Service Area Plan
17
12/11/2025
8166-10118.100 > 2025 Water Supply Service Area Plan (20251211 Draft).docx
Table IV-3: Water Consumption History
Year
Annual Water Sales (MGY) Total Sales
(MGY)
Total
Pumpage
(MGY)
% of
Pumpage
Sold Residential Commercial Industrial Public Multi-
Family
2014 378.85 318.55 901.53 122.68 31.81 1,753.41 1,895.86 92%
2015 378.21 311.52 874.56 110.59 58.70 1,733.59 1,883.79 92%
2016 368.86 284.83 766.06 111.92 55.92 1,587.59 1,800.53 88%
2017 359.20 283.62 993.26 102.96 57.94 1,796.98 1,826.18 98%
2018 419.39 310.54 1,022.18 123.17 68.40 1,943.67 1,989.74 98%
2019 342.01 271.58 953.32 95.90 68.91 1,731.72 1,909.40 91%
2020 388.14 288.38 930.83 88.94 49.87 1,746.17 1,946.58 90%
2021 382.52 293.78 879.96 86.04 54.68 1,696.98 2,113.40 80%
2022 362.10 294.27 1,399.90 89.62 49.33 2,195.22 2,512.31 87%
2023 432.58 381.18 1,297.38 105.94 53.61 2,270.69 2,531.91 90%
2024 344.66 292.43 1,173.47 85.12 51.58 1,947.26 2,438.59 80%
0
200
400
600
800
1,000
1,200
1,400
1,600
2014 2015 2016 2017 2018 2019 2020 2021 2022 2023 2024
Sales (MGY)
Year
Water Sales by Customer
Residential Commercial Industrial Public Multi-Family
Page 31 of 58
City of Stevens Point
2025 Water Supply Service Area Plan
18
12/11/2025
8166-10118.100 > 2025 Water Supply Service Area Plan (20251211 Draft).docx
Table IV-4: Water Usage per Customer per Day
Year
Gallons per Customer per Day
Residential Commercial Industrial Public Multi-Family
2014 136 776 79,676 1,899 778
2015 136 784 79,869 1,722 1,011
2016 131 709 69,960 1,713 958
2017 128 705 108,851 2,029 992
2018 148 752 82,367 1,917 1,157
2019 118 607 76,819 1,354 1,079
2020 133 616 102,009 1,459 776
2021 134 736 92,724 1,412 942
2022 127 750 147,513 1,488 855
2023 150 932 114,660 1,748 890
2024 120 718 110,862 1,396 856
Average 133 735 96,846 1,649 936
Table IV-5: Historical Per Acre Usage
Customer Class Residential Commercial Industrial Public Multi-Family
Existing Acres1: 1,774 620 768 2,249 370
Year Gallons per Acre per Day
2014 585.1 1,407.6 3,216.1 149.4 235.5
2015 584.1 1,376.6 3,119.9 134.7 434.7
2016 569.7 1,258.6 2,732.8 136.3 414.1
2017 554.7 1,253.3 3,543.3 125.4 429.0
2018 647.7 1,372.2 3,646.5 150.0 506.5
2019 528.2 1,200.1 3,400.8 116.8 510.3
2020 599.4 1,274.3 3,320.6 108.3 369.3
2021 590.8 1,298.2 3,139.1 104.8 404.9
2022 559.2 1,300.4 4,993.9 109.2 365.3
2023 668.1 1,684.4 4,628.2 129.1 397.0
2024 532.3 1,292.2 4,186.2 103.7 381.9
Average 583.6 1,338.0 3,629.8 124.4 404.4
Notes:
1. Based on land use areas from the 2005 City of Stevens Point Comprehensive Plan.
Page 32 of 58
City of Stevens Point
2025 Water Supply Service Area Plan
19
12/11/2025
8166-10118.100 > 2025 Water Supply Service Area Plan (20251211 Draft).docx
Table IV-6: Historical Per Capita Usage
Year Service
Population
Gallons per Capita per Day
Residential Commercial Industrial Public Multi-
Family
Total
Retail
Sales
2014 27,040 38.4 32.3 91.3 12.4 3.2 177.7
2015 27,037 38.3 31.6 88.6 11.2 5.9 175.7
2016 26,895 37.6 29.0 78.0 11.4 5.7 161.7
2017 26,757 36.8 29.0 101.7 10.5 5.9 184.0
2018 26,749 43.0 31.8 104.7 12.6 7.0 199.1
2019 26,490 35.4 28.1 98.6 9.9 7.1 179.1
2020 25,666 41.4 30.8 99.4 9.5 5.3 186.4
2021 25,580 41.0 31.5 94.2 9.2 5.9 181.8
2022 25,954 38.2 31.1 147.8 9.5 5.2 231.7
2023 26,332 45.0 39.7 135.0 11.0 5.6 236.3
2024 26,619 35.5 30.1 120.8 8.8 5.3 200.4
Average: 39.5 31.5 103.9 10.7 5.7 191.3
0
20
40
60
80
100
120
140
160
2014 2015 2016 2017 2018 2019 2020 2021 2022 2023 2024
Per Capita Consumption (gpcd) Year
Water Sales per Capita
Residential Commercial Industrial Public Multi-Family
Page 33 of 58
City of Stevens Point
2025 Water Supply Service Area Plan
20
12/11/2025
8166-10118.100 > 2025 Water Supply Service Area Plan (20251211 Draft).docx
Table IV-7: Ten Largest Water Customers
Rank Customer Name Customer Class Annual Water
Usage (MGY)1
Average Daily
Water Use (GPD)1
1 Ahlstrom Stevens Point Mill2 Industrial 950.7 2,604,624
2 Ahlstrom Stevens Point Mill2 Industrial 91.9 251,735
3 Ahlstrom Stevens Point Mill2 Industrial 55.2 151,131
4 Ahlstrom Stevens Point Mill2 Industrial 39.9 109,215
5 Sentry Insurance Commercial 18.7 51,146
6 Lineage Logistics, LLC Industrial 17.1 46,954
7 Sentry Insurance Commercial 12.1 33,181
8 Eagle Housing, LLC Multi-Family 11.5 31,523
9 Donaldson Industrial 11.4 31,192
10 Stevens Point Brewery Industrial 8.4 23,016
Notes:
1. Based upon billing records from January to December 2024.
2. The paper mill has several meter locations.
D. Non-revenue Water and Unaccounted for Water
The difference between total water pumped and total water sold is called non-revenue water.
Non-revenue water is typically the result of one or more of the following:
1. Unmetered water usage for firefighting.
2. Inaccuracies in water metering devices.
3. Unmetered public water usage.
4. Leakage within the distribution system.
5. Unmetered water usage for treatment processes and maintenance purposes, such as filter
cleaning, hydrant flushing and water main repairs.
Non-revenue water is usually expressed as a percentage. That portion of non-revenue water
attributed to leakage, meter inaccuracies, and other unknown losses is often terme d water
losses and can be an indicator of the condition of the water system. When a distribution system
is very old or poorly maintained, the amount of unaccounted for water often increases
dramatically.
Over the last 11 years, the percentage of the total non-revenue water has been reported to be
as high as 20% in 2024 and as low as 2% in 2018. A summary of historical non-revenue water
and water loss volumes is provided in Table IV-1. The degree of fluctuation experienced in
metered pumpage is common for public water utilities and can be influenced by the factors
summarized above. For example, the percentage of non-revenue water would be expected to
increase in years when unusual problems with leakage or meter stoppage occurred, or when
unusually high water demands for fire protection occurred. As a general rule, the percentage of
non-revenue water should ideally be less than 15%. For water pumpage projections, this study
assumes that the percentage of non-revenue water in future years will be maintained at 10%.
Historically, the water losses for the Utility have varied. Reported non-revenue water has
typically varied between 2% and 20%.
Page 34 of 58
City of Stevens Point
2025 Water Supply Service Area Plan
21
12/11/2025
8166-10118.100 > 2025 Water Supply Service Area Plan (20251211 Draft).docx
It is important to note that quantifying non-revenue water simply as a percent of pumped water
to billed water, while widely used and accepted, is limited in its ability to accurately indicate an
appropriate or acceptable level of water loss. For example, if water conservation measures are
implemented causing total consumption to decrease, and yet leakage and other unaccounted -
for water uses remain the same (as volume), then the percent of water losses actually
increases as a percent. This would mistakenly indicate that the level of water loss has gotten
worse, while in actuality, the total quantity has remained the same.
E. Variations in Customer Demands and Pumpage
Maximum daily water demands usually occur during the summer months on hot days when
additional water is used for watering lawns, gardening, washing, and industrial cooling.
Understanding and quantifying the maximum day pumpage is of particular importance to water
system planning because water supply facilities must be sized to meet this demand. The
maximum day demand is defined as the amount of water pumped during a single day of the
year with the highest water usage. Maximum day demand is often expressed as a ratio (or
factor) of the annual average day pumpage.
Table IV-8 presents the average and maximum day pumpage for each year from 201 4 to 2024.
With the exception of maximum day pumpage resulting from artificial demands caused by
water main breaks, tank overflows, or hydrant flushing, the maximum day pumpage typically
occurs during the summer months of July to September.
Over the last 11 years, the maximum day pumpage ratio (ratio of maximum day to average day
pumpage) has varied from a low of approximately 1.40 in 2024 to a high of 1.77 in 2020. The
values shown in Table IV-8 are typical for similar sized communities.
To gain a better understanding of expected fluctuations in customer demands for the Utility, a
statistical analysis was performed of historical maximum day to average day pumpage ratios.
The results of this analysis are also summarized in Table IV-8.
The average maximum to average ratio for the past 11 years was 1.62; however, it is good
practice to use a larger ratio to project future pumpage. For this reason, Table IV-8 also
includes a statistical analysis of maximum day pumpage ratios for various confidence levels.
For example, using a 95% confidence level, the corresponding maximum to average ratio is
1.76. Therefore, to evaluate future water supply and storage needs, a maximum day pumpage
ratio of 1.76 is used for this study.
Page 35 of 58
City of Stevens Point
2025 Water Supply Service Area Plan
22
12/11/2025
8166-10118.100 > 2025 Water Supply Service Area Plan (20251211 Draft).docx
Table IV-8: Daily Pumpage Variations
Year Avg. Day
Pumpage (MGD)
Max. Day
Pumpage (MGD)
Date of Maximum
Day
Ratio of Max. to
Avg. Day
2014 5.19 8.980 July 25 1.73
2015 5.16 8.417 July 31 1.63
2016 4.93 8.551 June 22 1.73
2017 5.00 8.083 July 26 1.62
2018 5.45 9.586 Aug 17 1.76
2019 5.23 7.771 Aug 23 1.49
2020 5.33 9.440 Aug 21 1.77
2021 5.79 9.550 June 15 1.65
2022 6.88 10.20 Aug 02 1.48
2023 6.94 10.94 Jul 07 1.58
2024 6.68 9.367 Aug 26 1.40
Statistical Analysis Result
Number of years of Data 11
Maximum Ratio - Max. to Avg. Day Pumpage 1.77
Minimum Ratio - Max. to Avg. Day Pumpage 1.40
Average Ratio Max. to Avg. Day Pumpage 1.62
Confidence Level (%) Ratio of Max. to Avg. Day
80% 1.73
85% 1.75
90% 1.76
95% 1.76
98% 1.77
100% 1.77
0.0
0.5
1.0
1.5
2.0
2.5
2014 2016 2018 2020 2022 2024
Historical Maximum Day Ratios
Ratio of Max. to Avg. Day 95% Confidence Level
95% Confidence Level: 1.76
Page 36 of 58
City of Stevens Point
2025 Water Supply Service Area Plan
23
12/11/2025
8166-10118.100 > 2025 Water Supply Service Area Plan (20251211 Draft).docx
F. Hourly Demand Fluctuations
The hourly variation of water demands is an essential parameter in evaluating water supply
and storage requirements. Peak hour demand is important because storage facilities are
usually designed to equalize demands when they exceed the maximum day demand. Peak
hour demand represents the hour of maximum demand. Peak hour demand is typically
expressed as a ratio to the maximum day demand.
According to AWWA Manual M32, typical ranges for peak hour factors in distribution systems
of various sizes are 1.3 to 2.0 for peak hour to maximum day and 0.2 to 0.6 for minimum hour
to maximum day. In the EPCC Study, the Utility’s SCADA data was analyzed to determine the
typical peak hour factor which was found to be about to be about 1.5. In this study, a peak hour
demand factor of 1.5 times the maximum day demand is used, which is typical for
municipalities the size of the City of Stevens Point.
G. Water Consumption and Pumpage Projections
Except for industrial water sales, projected water sales to the existing service area are
assumed to correlate with population change summarized in Table III-1. As discussed in
Chapter III, the population is projected to increase from 26,619 in 2024 to 27,619 in 2045
according to the projections provided by the City Planning Department. Industrial water sales
within the existing service area are projected to remain stable, independent of population
change, at 1,200 MGY.
Projected water sales to planned developments in the proposed pressure zone are taken from
the EPCC Study. The total demands from the proposed developments described in the EPCC
Study are about 2.95 MGD or 1,075.8 MGY. To project sales to the proposed 40-acre
development near North Brilowski Road as described in Chapter III, a water use of 600 gallons
per acre per day (GPAD) is applied. As shown in Table IV-5, 600 GPAD is the approximate
water usage for residential areas. Using this approximate water usage per acre, the total
annual water usage from the North Brilowski Road development is approximately 8.8 MGY.
Water sales projections to these planned developments are shown in Table IV-9.
Table IV-9: Water Sales Projections to Planned Developments
Development Type Acres Projected Water Sales
GPAD2 MGD MGY
North Brilowski Road Development (Residential): 40 600 0.02 8.8
Developments in Proposed New Pressure Zone1 - - 2.95 1,075.8
Total Demands from Proposed Developments: 2.97 1,085
Notes:
1. Projected sales are taken from Table 4-7 from the EPCC Study.
Water sales projections for the 20-year planning period of this WSSAP are shown in Table
IV-10. Water sales to the existing service area and sales to new developments are added
together to estimate the total projected sales. To ensure that the supply capacity of the Utility’s
wells is sufficient for all proposed developments, the water demand projections assume that
the proposed pressure zone will reach full buildout by 2045. The actual rate of development will
likely be slower, however, by assuming a rapid rate of development, this will ensure that the
supply capacity is sufficient for all proposed developments. The projected total pumpage
assumes that the non-revenue water is 10% of the total pumpage.
Page 37 of 58
City of Stevens Point
2025 Water Supply Service Area Plan
24
12/11/2025
8166-10118.100 > 2025 Water Supply Service Area Plan (20251211 Draft).docx
Table IV-10: Annual Water Sales and Pumpage Projections
Customer Classification Actual
2024
Projected
2030 2035 2040 2045
Water Sales
Per Capita Sales (gpcd)
Residential Sales 35 45 45 45 45
Commercial Sales 30 40 40 40 40
Industrial Sales 121 - - - -
Public Sales 9 13 13 13 13
Multi-Family 5 8 8 8 8
Population Projections: 26,619 26,869 27,119 27,369 27,619
Annual Sales to Service Area (MGY)1
Residential Sales 345 441 445 450 454
Commercial Sales 292 392 396 400 403
Industrial Sales2 1,173 1,200 1,200 1,200 1,200
Public Sales 85 127 129 130 131
Multi-Family 52 78 79 80 81
Sales to New Developments3
Proposed New Pressure Zone4 0 269.0 537.9 806.9 1,075.8
N Brilowski Development 0 8.8 8.8 8.8 8.8
Total Sales (MGY) 1,947 2,517 2,796 3,075 3,353
Non-revenue Water (MGY)5 491 280 311 342 373
Total Pumpage (MGY) 2,439 2,797 3,107 3,416 3,726
Notes
1. Residential, commercial, public and multi-family water usage is assumed to correlate with
population change.
2. Industrial sales are assumed to remain constant independent of population change.
3. Sales to new developments are assumed to be in addition to the sales to existing
customers which correlates with population change.
4. Taken from the EPCC Study. Projected demands are assumed to reach full buildout by
2045.
5. Estimated to be 10% of total pumpage for future projections.
H. Summary of Total Demands and Pumpage Requirements
The total annual sales and pumpage projections previously summarized in Table IV-10 were
based on a summation of water sales projections for each major customer classification. An
allowance was also made for unmetered miscellaneous water usage and losses (non -revenue
water) to arrive at total pumpage projections.
Table IV-11 summarizes projections of future water needs for average day, maximum day, and
peak hour demands. Total annual pumpage is projected to increase from approximately
2,439 MGY (6.68 MGD) to approximately 3,504 MGY (9.60 MGD) by the year 2045. Table
IV-11 also illustrates the projected water sales and pumpage through the planning period.
Page 38 of 58
City of Stevens Point
2025 Water Supply Service Area Plan
25
12/11/2025
8166-10118.100 > 2025 Water Supply Service Area Plan (20251211 Draft).docx
Table IV-11: Future Pumpage Projections
Estimate Actual
2024
Projected
2030 2035 2040 2045
Total Annual Sales (MGY) 1,947 2,517 2,796 3,075 3,353
Total Annual Pumpage (MGY) 2,439 2,797 3,107 3,416 3,726
Average Day Pumpage (MGD) 6.68 7.66 8.51 9.36 10.21
Design Maximum Day Pumpage (MGD)2 9.37 13.49 14.98 16.47 17.97
Design Peak Hour Demand (gpm)3 9,800 14,100 15,700 17,200 18,800
Notes:
1. Non-Revenue water is assumed to be 10% of total pumpage for future projections.
2. Projected maximum day pumpage projections were estimated using a ratio of maximum to
average day pumpage of 1.76.
3. Design peak hour demand projections were estimated using a ratio of peak hour demand to
maximum day pumpage of 1.50.
Page 39 of 58
City of Stevens Point
2025 Water Supply Service Area Plan
26
12/11/2025
8166-10118.100 > 2025 Water Supply Service Area Plan (20251211 Draft).docx
V. SUPPLY AND STORAGE ANALYSIS
A critical step in the water system evaluation for the Utility is an assessment of water supply and
storage requirements. Water supply and storage needs are closely related. The primary criteria
used in determining required supply rates and storage volumes include maximum day and peak
hour demands, operational characteristics, and fire protection needs.
A. Water Supply Analysis
As it is frequently necessary to take a well and/or booster pump out of service for periods of
days to even weeks for maintenance or repair, it is necessary to properly plan to ensure that
demand requirements can be met even when a pumping unit may be out of service. It is then
necessary to determine a reliable capacity that accounts for the uncertainty that all pumping
units will be available. By excluding one pumping unit (for planning purposes, the largest
capacity unit is typically used) the reliable capacity is then determined. Therefore, reliable
capacity is defined as the total available delivery rate with the largest pumping unit out of
service.
For evaluating a municipal water system, the reliable supply capacity should at least equal
maximum day pumpage requirements, assuming adequate storage is available. If this criterion
is met, supply facilities will have adequate capacity to replenish storage during off -peak hours,
while depletion of available storage occurs during peak demand hours.
Reliable water supply capacity is the capacity of the existing supply sources (well facilities and
service pumps) to reliably supply maximum day demands from the aquifer to the water system.
Table V-1 summarizes the well and well pump capacities used for the reliable water supply
capacity evaluation. The reliable supply capacity is calculated assuming that the largest supply
unit, Well 11, is out of service. The following sections discuss reliable water supply and system
capacity in further detail for the existing water system.
Page 40 of 58
City of Stevens Point
2025 Water Supply Service Area Plan
27
12/11/2025
8166-10118.100 > 2025 Water Supply Service Area Plan (20251211 Draft).docx
Table V-1: Existing Reliable Supply Capacity
Supply Source Supply Capacity Water to Distribution
Capacity
Wells (gpm) (MGD) (gpm) (MGD)
Well 6 (Temporarily Offline)1 2,100 3.02 2,100 3.02
Well 7 2,100 3.02 2,100 3.02
Well 8 1,691 2.44 1,691 2.44
Well 9 1,500 2.16 1,500 2.16
Well 10 4,200 6.05 4,200 6.05
Well 112 9,050 13.03 5,100 7.34
Well 12 (Planned)3 1,014 1.46 1,014 1.46
Total Pumping Supply Capacity 21,655 31.18 17,705 25.50
Less: Largest Supply Units 9,050 13.03 5,100 7.34
Existing Reliable Supply4 9,491 13.67 9,491 13.67
Future Reliable Supply5 12,605 18.15 12,605 18.15
Notes:
1. Planned to be brought back into service in 2026.
2. Well 11 is rated for a total of 9,050 gpm. However, when all well pumps are operated
simultaneously, the maximum pumping capacity based on water modeling is
approximately 5,100 gpm.
3. Well 12 is not yet in operation and is planned to be put into service in 2026.
4. Capacity from Wells 6 and 12 is not included in the existing reliable supply.
5. Capacity from Wells 6 and 12 is included in the future reliable supply.
1. Existing Recommended Reliable Supply Capacity
As shown in Table V-2, the existing reliable supply capacity exceeds the current maximum
day demand. Therefore, the City’s wells are sufficient to meet current demands.
Table V-2: Existing Recommended Reliable Supply Capacity
Supply Requirements Water System
2024
gpm MGD
Design Average Day Demand 4,639 6.68
Design Maximum Day Demand1 6,505 9.37
Present Reliable Supply Capacity 9,491 13.67
Reliable Supply Capacity Excess or (Deficiency) (gpm) 2,986 4.30
Notes:
1. See Table IV-1
Page 41 of 58
City of Stevens Point
2025 Water Supply Service Area Plan
28
12/11/2025
8166-10118.100 > 2025 Water Supply Service Area Plan (20251211 Draft).docx
B. Water Storage Analysis
1. Water Storage Needs
In addition to providing water for fire protection, system storage is used as a “cushion” to
equalize fluctuations in customer demands, establish and maintain water system
pressures, provide operational flexibility for water supply facilities, and improve water
supply reliability. The primary criteria used in this study for evaluating storage volume
needs include average and peak hour demands, water supply capacities, and fire
protection needs.
In general, storage facilities should be adequately sized to provide sufficient quantities of
water for fire protection on days of maximum customer demands. Although storage
requirements for fire protection are not anticipated to change over the planning period of
this study, peak hour demands and reliable supply capacities will change as the community
grows and improvements are implemented.
Figure V-1 illustrates general components of system storage. As customer demands
exceed supply capacities during peak hour conditions, the excess demand must be met by
depleting available storage. The amount of storage depleted is referred to as equalizing
storage for peak hour requirements.
Figure V-1: Storage Components
Page 42 of 58
City of Stevens Point
2025 Water Supply Service Area Plan
29
12/11/2025
8166-10118.100 > 2025 Water Supply Service Area Plan (20251211 Draft).docx
Storage should also be available for fire protection purposes. To ensure a reliable supply
for fire protection, this portion of storage should be reserved for emergency use only and
should not be used to meet peak hour or operational requirements. It is assumed that the
maximum fire flow requirement for the Utility is 3,500 gpm for a duration of 3 hours, or the
equivalent of 630,000 gallons in each pressure zone.
It is also good practice to provide additional storage for the purposes of operational needs.
Operational storage allows for the control of pumps prior to the depletion of needed peak
hour equalizing storage. Operational storage may be needed as a safety f actor in
emergencies or where customer demands are unpredictable and fluctuate widely.
Operational storage may also be desired to take advantage of off-peak electrical rates for
pumping. Operational storage is assumed to be 15% of the total storage volume.
2. Effective Storage Volumes
The effective storage volume of a water storage facility is the amount of available water
that can be utilized while meeting regulatory requirements for system pressure. The WDNR
requires that water system pressures under normal operating conditions remain above
35 psi and under emergency conditions, such as during a fire, system pressures must be
maintained at a minimum pressure of 20 psi. To meet these requirements, the water
surface in the storage facility must be approximately 81 feet above the highest elevation
area in the service area to maintain 35 psi and at least 46 feet to maintain 20 psi. These
water column heights are based upon static conditions (assuming no head losses due to
friction) so actual water column heights would be higher as friction losses are included.
Based upon this evaluation, the effective volume of each existing and proposed storage
facility is summarized in Table V-3. Using gauging tables for the Utility’s existing and
proposed ESTs, it was determined that the total storage volume effective for peak hour
equalization is 1,049,000 gallons and that all the storage volume is effective for fire
protection.
3. Recommended Existing Water Storage Volumes
The following relationships between supply capacities and storage volumes are the primary
criteria used to determine optimum storage volumes:
1. Reliable supply capacity should at least equal projected maximum day supply
requirements.
2. Total available storage should be capable of meeting demands in excess of the
maximum day demand as well as fire protection needs, assuming reliable supply
capacity is adequate to meet maximum day requirements.
The existing optimum water storage requirement for the Utility is about 1.58 MG, as shown
in Table V-4. The existing storage facilities provide 1.75 MG of available storage. However,
due to excess pumping capacity, the recommended storage volume can be reduced
because the excess pumping capacity can be used to reduce the equalizing storage
needed. When this is done, the recommended total storage capacity can be reduced by
0.70 MG to 0.88 MG. The Utility’s combined storage capacity of 1.75 MG in elevated
storage is sufficient for existing demands.
Page 43 of 58
City of Stevens Point
2025 Water Supply Service Area Plan
30
12/11/2025
8166-10118.100 > 2025 Water Supply Service Area Plan (20251211 Draft).docx
Table V-3: Effective Storage Volumes
Storage Criteria Water Street
Tank
Bliss Avenue
Tank
Proposed
Tank #3
Pressure Zone Main Main Zone 2
Design Volume (gallons) 1,000,000 750,000 1,000,000
Diameter (feet) Varies Varies Varies
Head Range (feet) 35.0 40.0 40.0
Storage Volume per foot (gallons) Varies Varies Varies
Overflow elevation (feet USGS)1 1,252.0 1,252.0 1,285.0
Approximate Highest Elevation Served in Pressure
Zone (feet USGS) 1,148 1,148 1,189
Approximate Hydraulic Grade Elevation needed to
provide minimum 35 psi to all areas 1,229 1,229 1,270
Maximum Effective Peak Hour Storage Volume
(gallons)2 374,000 245,000 430,000
Approximate Hydraulic Grade Elevation needed to
provide minimum 20 psi to all areas 1,194 1,194 1,235
Additional Effective Fire Protection and Emergency
Storage Volume (gallons)3 626,000 505,000 570,000
Total Effective Storage Volume (gallons) 1,000,000 750,000 1,000,000
Notes:
1. Not including the proposed boosted pressure zone.
2. Effective peak hour storage is considered the volume available which will continue to maintain
adequate pressures in the distribution system at a minimum of 35 psi (under static conditions).
Volumes derived from storage tank gauging tables.
3. Effective fire protection and emergency storage is considered the volume available which will
continue to maintain pressures in the distribution system at a minimum of 20 psi (under static
conditions). Volumes derived from storage tank gauging tables.
Page 44 of 58
City of Stevens Point
2025 Water Supply Service Area Plan
31
12/11/2025
8166-10118.100 > 2025 Water Supply Service Area Plan (20251211 Draft).docx
Table V-4: Existing and Projected Supply and Storage Requirements
Supply Recommendations Existing
2024 Projected 2030 Projected 2035 Projected 2040 Projected 2045
gpm MGD gpm MGD gpm MGD gpm MGD gpm MGD
Design Average Day Demand 4,639 6.7 5,321 7.7 5,910 8.5 6,499 9.4 7,088 10.2
Design Maximum Day Demand 6,505 9.4 9,365 13.5 10,402 15.0 11,438 16.5 12,475 18.0
Design Peak Hour Demand 9,800 14.1 14,100 20.3 15,700 22.6 17,200 24.8 18,800 27.1
Design Reliable Supply Capacity1 9,491 13.7 12,605 18.2 12,605 18.2 12,605 18.2 12,605 18.2
Reliable Supply Capacity Excess or (Deficiency)
(gpm) 2,986 3,240 2,203 1,167 130
Storage Recommendations Existing
2024 Projected 2030 Projected 2035 Projected 2040 Projected 2045
Peak Hour Equalizing Need (gallons)2 714,000 1,028,000 1,142,000 1,256,000 1,370,000
Optimum Fire Protection Needs (gallons)3 630,000 1,260,000 1,260,000 1,260,000 1,260,000
Operating Storage (gallons; 15% of Total)4 238,000 404,000 424,000 444,000 465,000
Total Optimum Recommended Storage (gallons) 1,582,000 2,692,000 2,826,000 2,960,000 3,095,000
Available Effective Storage Capacity (gallons):
Water Street Tank (374,000 gallons peak hour;
626,000 gallons fire flow) 1,000,000 1,000,000 1,000,000 1,000,000 1,000,000
Bliss Avenue Tank (245,000 gallons peak hour;
505,000 gallons fire flow) 750,000 750,000 750,000 750,000 750,000
Proposed Tank #3 (430,000 gallons peak hour;
570,000 gallons fire flow) - 1,000,000 1,000,000 1,000,000 1,000,000
Total Effective Storage Capacity (gallons)5 1,750,000 2,750,000 2,750,000 2,750,000 2,750,000
Subtotal Additional Capacity Recommended
(gallons) None None 76,000 210,000 345,000
Less: Excess Available Reliable System Supply
Capacity for Peak Hour (gallons)6 706,000 903,000 723,000 419,000 55,000
Less: Excess Supply Capacity Available for Fire
Protection (gallons)7 None None None None None
Total Storage Capacity Excess or (Deficiency)
(gallons)8 874,000 961,000 647,000 209,000 (290,000)
Notes:
1. Reliable Supply Capacity is with largest source out of service.
2. Peak hour storage is storage utilized to meet demands which exceed the maximum day demand rate assuming the reliable supply capacity is
equal to the maximum day demand rate.
3. Optimum fire protection based on 3,500 gpm for 180 minutes in each pressure zone. A second pressure zone is proposed and is included in
future years
4. Operating storage is storage utilized to provide a start/stop range for pump operation and an emergency reserve storage supply.
5. Total Effective Storage Capacity is limited to a total of the Optimum Fire Protection Needs plus peak hour available storage to maintain
regulatory system pressures.
6. Supply Capacity Credit cannot exceed Peak Hour Equalization and is calculated utilizing the time of day demand curve and current supply
capacity.
7. Supply Capacity Credit cannot exceed Fire Protection Need and is calculated as the reliable supply capacity in excess of Peak Hour Demand x
180 min.
8. Individual pressure zones are not analyzed in this study. A separate analysis would be needed to estimate supply and storage needs in individual
pressure zones.
Page 45 of 58
City of Stevens Point
2025 Water Supply Service Area Plan
32
12/11/2025
8166-10118.100 > 2025 Water Supply Service Area Plan (20251211 Draft).docx
C. Supply and Storage Results
The results from the supply and storage analysis are included in Table V-4. The existing
reliable supply capacity does not include Wells 6 and 12, which are both planned to be put into
operation in the year 2026; the reliable supply capacity for future years includes Wells 6 and
12, as shown in Table V-1. Additionally, the storage capacity for projected years includes a
1.00 MG EST that is proposed in the new pressure zone.
The results of the analysis show that the Utility has sufficient supply for all the water demands
that were projected in Chapter IV. The projected 2045 maximum day demand is 18.0 MGD and
the reliable supply, including Wells 6 and 12, is 18.2 MGD. However, even with the proposed
1.00 MG EST, there is projected to be a 0.29 MG deficiency in storage. The EPCC Study notes
that in addition to the recommended 1.00 MG EST, an additional 0.25 MG of storage may be
needed in the new pressure zone before full buildout. It is important to note that the supply and
storage analysis in this WSSAP does not analyze the storage capacity in individual pressure
zones. As water demands increase over time, the storage capacity should be revisited to
determine how much additional storage is needed in each pressure zone. Given that a rapid
rate of development is assumed in this WSSAP, these findings should be reevaluated as
development progresses.
D. Summary
This section summarizes the findings from the supply and storage evaluation of the City of
Stevens Point Water Utility. Major findings from this evaluation include the following:
1. The reliable supply capacity, once Wells 6 and 12 are in operation, is adequate to meet
current and projected water demands until the end of the planning period of 2045.
2. The Utility is projected to need additional storage towards the end of the planning period.
However, given that a rapid rate of development is assumed in this WSSAP, this should
be confirmed later as development progresses.
Page 46 of 58
City of Stevens Point
2025 Water Supply Service Area Plan
33
12/11/2025
8166-10118.100 > 2025 Water Supply Service Area Plan (20251211 Draft).docx
VI. CONCLUSION AND RECOMMENDATIONS
A. Key Findings and Recommendations
1. Population Projections
The City Planning Department’s preliminary population projections predict an increase from
24,619 in 2024 to 27,619 by 2045 which is the end of the planning period of this study. The
proposed developments throughout the City include residential, commercial, industrial, and
multi-family.
2. Water Demands
The existing average day and maximum day water demands from 2024 pumpage are 6.68
MGD and 9.34 MGD, respectively. The total average and maximum day water demands
are projected to increase to 10.21 MGD and 17.97 MGD by 2045, respectively.
3. Supply
The Utility has seven groundwater wells with a total reliable supply capacity of 12,605 gpm
or 18.15 MGD. This is sufficient to meet the projected 2045 maximum day demand of
12,475 gpm or 18.0 MGD.
4. Storage
The Utility currently has 1.75 MG of elevated water storage with another 1.00 MG EST
proposed in the new pressure zone. The total elevated storage capacity is projected to be
slightly deficient by the end of the planning period. However, given that this WSSAP
assumes a rapid rate of development, this should be revisited in the future as demands
increase.
5. Other Considerations
The largest water customer, Ahlstrom Paper Mill, accounts for nearly half of all water
usage within the City. If the paper mill were to increase or reduce water usage, or shut
down, this would significantly impact water distribution and the findings in this report would
need to be revisited and revised. If water usage is reduced at any point, this would result in
overall lower water usage and excess supply capacity. Conversely, if the water usage at
the paper mill increases, this would reduce the Utility’s ability to serve future developments.
B. Consistency With Other Plans and Agreements
Previous studies and plans were reviewed to ensure consistency with this WSSAP. This
WSSAP uses full buildout water demand projections from the EPCC Study that was done by
Ruekert & Mielke, Inc. in 2025. Additionally, the 2024 Portage County Comprehensive Plan
and the 2025 North Central Wisconsin Regional Planning Commission (NCWRCP)
Comprehensive Plan were reviewed. It was found that the findings of this WSSAP are
consistent with these two comprehensive plans.
The latest comprehensive plan done by the City in 2005 is currently being updated by the City.
Once the updated comprehensive plan is finalized, it should be reviewed for consistency with
the findings in this WSSAP. If the findings are not consistent with the comprehensive plan,
modifications should be made to update the WSSAP and bring it to compliance with the
comprehensive plan.
Page 47 of 58
City of Stevens Point
2025 Water Supply Service Area Plan
34
12/11/2025
8166-10118.100 > 2025 Water Supply Service Area Plan (20251211 Draft).docx
C. Plan Implementation
There are no immediate steps required to implement this WSSAP.
D. Public Participation
A draft copy of this Plan will be made available on the City’s website. The public will be notified
and encouraged to provide comments and questions.
E. Updates to Plan
This Plan is required to be reviewed every five years and updated as necessary. A new
WSSAP will need to be created by 2045 before the end of the planning period.
Page 48 of 58
STEVENS POINT, WISCONSIN
WATERWORKS REPORT
FOR DECEMBER 2025
CURRENT YEAR VS. PREVIOUS YEAR
2024 2025 INCREASE DECREASE
RECORD
HIGH/LOW DATE
Total pumpage, gallons 172,688,000 166,903,000 5,785,000 201,625,000 12/1/2003
Daily pumping average, in gallons 5,570,000 5,383,970 186,030
Peak pumpage, gallons, (date) 6,660,000 8,205,000 1,545,000 8,837,000 12/2/2001
(3RD) (11TH)
Low pumpage, gallons, (date) 3,861,000 3,706,000 155,000 1,270,000 12/25/1970
(4TH) (10TH)
2,265,000 12/25/2012 ◄Record low since 1995 when
the utility started providing water
Power bill $21,119.30 $20,283.35 $835.95 $21,119.30 Dec-24 to Stora Enso.
K.W.H's used 231,414 226,679 4,735
Gallons pumped per K.W.H. 854 736 118
F:\123R3\WATERWORK REPTS\WATERWRK-Dec 25.xlsx
Page 49 of 58
MONTH 2025 2024 2023 2022 2021 2020 2019 2018 2017 2016
JANUARY 191,525 190,129 178,957 188,381 138,644 150,622 142,263 147,206 140,438 131,056
FEBRUARY 174,855 200,341 173,997 173,503 135,391 131,127 135,573 132,869 123,311 124,330
MARCH 182,380 197,093 169,879 195,466 150,690 138,327 154,358 148,770 139,881 131,189
APRIL 176,085 194,614 167,050 171,871 146,563 127,470 135,713 133,238 142,367 135,484
MAY 215,675 207,278 208,084 211,721 174,529 149,292 154,346 168,410 141,687 175,174
JUNE 229,512 228,814 284,930 238,070 225,268 181,763 181,220 187,095 175,722 187,693
JULY 237,122 232,529 280,293 261,545 214,800 199,876 199,645 240,487 202,817 185,672
AUGUST 226,475 241,404 275,018 251,597 206,429 231,447 210,777 225,280 179,208 167,623
SEPTEMBER 220,162 219,734 239,167 227,586 181,626 174,925 169,779 181,556 157,626 151,238
OCTOBER 186,924 189,354 177,717 206,986 188,859 170,759 143,805 148,186 151,878 143,498
NOVEMBER 165,376 166,568 194,002 191,454 169,636 151,193 135,482 133,317 137,452 126,023
DECEMBER 166,903 172,688 182,805 194,570 186,582 139,795 146,329 143,324 133,796 141,554
Grand Total/Yr 2,372,994 2,440,546 2,531,899 2,512,750 2,119,017 1,946,596 1,909,290 1,989,738 1,826,183 1,800,534
STEVENS POINT WATER DEPARTMENT
CONSUMPTION HISTORY
(Pumpage x 1,000)
F:\123R3\PUMPAGE 2016- 2025.xlsx
Page 50 of 58
MONTH 2025 2024 2023 2022 2021 2020 2019 2018 2017
JANUARY 89,445 89,029 88,937 88,942 83,106 82,287 82,112 88,989 89,079
FEBRUARY 79,592 83,297 79,725 80,355 80,293 83,129 80,253 80,441 80,474
MARCH 88,798 82,726 81,120 88,834 88,768 88,771 88,609 76,469 88,652
APRIL 85,446 86,122 84,933 84,742 86,110 86,022 84,640 86,223 76,187
MAY 89,075 88,543 88,563 88,861 88,978 88,891 88,880 88,968 66,836
JUNE 85,529 90,926 93,567 85,473 86,219 86,029 85,990 86,098 74,224
JULY 93,325 98,263 98,201 89,341 89,195 86,944 88,225 88,869 88,996
AUGUST 88,295 98,269 98,201 89,417 88,490 88,902 88,811 88,978 88,973
SEPTEMBER 86,386 78,157 88,166 86,525 86,109 86,044 85,974 86,010 86,157
OCTOBER 87,789 85,933 88,652 89,828 86,373 88,916 88,841 87,366 89,120
NOVEMBER 86,345 76,273 86,218 86,211 86,217 82,881 85,244 85,751 86,441
DECEMBER 88,891 89,129 88,973 89,035 89,444 88,909 88,890 87,468 72,909
Grand Total/Yr 1,048,916 1,046,667 1,065,256 1,047,564 1,039,302 1,037,725 1,036,469 1,031,630 988,048
STEVENS POINT WATER DEPARTMENT
WELL 11 PUMPAGE HISTORY
(Pumpage x 1,000)
F:\Commission Meetings\Well 11 Pumpage.xlsx
Page 51 of 58
Final Effluent Discharge Data
December 2025
Sewage Flow BOD S.S. Phosphorus Fecal Effluent
Raw Final Raw Final Raw Final Raw Final Raw Final Coliform Ammonia
Precip CBOD % Pounds Pounds Raw Final % Pounds Pounds Raw Final Pounds Pounds Final
Date INCHES MGD MGD MG/L MG/L Reduct. BOD/Day CBOD/Day (ppm) (ppm) Reduct. SS/Day SS/Day (ppm) (ppm) P/Day P/Day #/100 ml mg/L
12/01/2025 0.00 2.113 2.148 345 7.76 98 6,080 139 376 5.74 98 6,626.03 103
12/02/2025 0.04 2.192 2.264 277 8.29 97 5,064 157 240 6.99 97 4,387.51 132 23
12/03/2025 0.02 2.266 2.519 393 8.23 98 7,427 173 228 6.86 97 4,308.84 144 6.700 0.230 127 5 29
12/04/2025 0.00 2.218 2.533 195 8.37 96 3,607 177 216 5.94 97 3,995.59 125 43
12/05/2025 0.00 2.176 2.526 281 4.53 98 5,100 95 344 7.06 98 6,242.86 149 6.160 0.240 112 5 52
12/06/2025 0.05 2.040 2.390 263 4.43 98 4,475 88 300 5.94 98 5,104.08 118 5.690 0.220 97 4 58
12/07/2025 0.05 2.082 2.408 266 3.79 99 4,619 76 304 5.99 98 5,278.62 120
12/08/2025 0.00 2.224 2.562 353 4.72 99 6,548 101 288 6.43 98 5,341.87 137
12/09/2025 0.06 2.219 2.589 358 4.38 99 6,625 95 292 5.79 98 5,403.89 125 45
12/10/2025 0.55 2.170 2.545 374 3.98 99 6,769 84 288 5.59 98 5,212.17 119 35
12/11/2025 0.00 2.218 2.600 332 3.93 99 6,141 85 352 6.60 98 6,511.34 143 6.990 0.680 129 15 40
12/12/2025 0.00 2.156 2.399 296 4.45 98 5,322 89 236 5.40 98 4,243.53 108 6.230 0.560 112 11 31
12/13/2025 0.01 1.990 2.032 257 3.67 99 4,265 62 220 4.60 98 3,651.25 78
12/14/2025 0.00 2.007 2.044 236 3.25 99 3,950 55 204 5.00 98 3,414.63 85 5.650 0.490 95 8 8
12/15/2025 0.00 2.203 2.247 323 4.44 99 5,934 83 248 4.80 98 4,556.51 90
12/16/2025 0.00 2.230 2.305 339 4.21 99 6,305 81 256 5.00 98 4,761.14 96 8
12/17/2025 0.00 2.211 2.281 274 3.47 99 5,052 66 240 4.60 98 4,425.54 88 6.410 0.182 118 3 6
12/18/2025 0.00 2.180 2.246 486 3.93 99 8,836 74 240 3.73 98 4,363.49 70 6
12/19/2025 0.11 2.072 2.113 359 3.99 99 6,204 70 296 4.60 98 5,115.02 81 6.160 0.182 106 3 8
12/20/2025 0.00 1.929 1.978 150 3.65 98 2,413 60 80 4.20 95 1,287.03 69 3.330 0.182 54 3 6
12/21/2025 0.00 1.915 1.946 434 3.86 99 6,931 63 232 4.91 98 3,705.30 80
12/22/2025 0.11 2.017 2.080 405 4.38 99 6,813 76 276 3.31 99 4,642.81 57 4
12/23/2025 0.00 2.051 2.120 413 5.74 99 7,065 101 244 5.01 98 4,173.70 89 6.480 0.230 111 4 9
12/24/2025 0.00 1.866 1.920 299 5.81 98 4,653 93 220 4.73 98 3,423.74 76 5.470 0.230 85 4 8
12/25/2025 0.00 1.632 1.661 242 3.38 99 3,294 47 184 4.12 98 2,504.40 57 3.830 0.210 52 3 4
12/26/2025 0.04 1.850 1.906 334 4.37 99 5,153 69 240 3.53 99 3,702.96 56 4
12/27/2025 0.00 1.853 1.901 281 5.13 98 4,343 81 252 3.85 98 3,894.41 61
12/28/2025 0.02 1.906 1.979 255 4.71 98 4,053 78 188 5.15 97 2,988.46 85
12/29/2025 0.57 2.029 2.087 277 4.74 98 4,687 83 288 4.51 98 4,873.50 78
12/30/2025 0.00 1.942 1.982 329 11.70 96 5,329 193 252 5.94 98 4,081.46 98
12/31/2025 0.05 1.970 2.026 332 12.84 96 5,455 217 224 5.40 98 3,680.28 91
Total 1.68 63.927 68.337 9,758 164 3,045 168,512 3,013 7,848 161.32 3,033 135,901.93 3,010 69.100 3.636 1,197.431 68.906 425.490
Average 0.05 2.062 2.204 315 5 98 5,436 97 253 5.20 98 4,383.93 97 5.758 0.303 99.833 5.667 21.350
Maximum 0.57 2.27 2.60 486.00 12.84 99.19 8,836.06 216.96 376.00 7.06 98.80 6,626.03 148.73 6.99 0.68 129.30 14.75 57.90
Minimum 0.00 1.63 1.66 150.00 3.25 95.71 2,413.18 46.82 80.00 3.31 94.75 1,287.03 56.11 3.33 0.18 52.13 2.91 3.58
Page 52 of 58
BOD Raw 2 Year History
BOD Raw Actual Monthly Average
(Mo Avg)
BOD Raw Design Monthly Average
(Mo Avg)
LBS
Date ( 01/01/2024 to 12/31/2025 )
0
800
1600
2400
3200
4000
4800
5600
6400
7200
8000
8800
9600
10400
11200
12000
Jan '24 Mar '24 May '24 Jul '24 Sep '24 Nov '24 Jan '25 Mar '25 May '25 Jul '25 Sep '25 Nov '25 Jan '26
WIMS (OPSSP_WWTP)
BOD Raw 2 Year History
Page 53 of 58
SS Raw 2 Year History
SS Raw Actual Monthly Average (Mo
Avg)
SS Raw Design Monthly Average
(Mo Avg)
LBS
Date ( 01/01/2024 to 12/31/2025 )
0
800
1600
2400
3200
4000
4800
5600
6400
7200
8000
8800
9600
10400
11200
12000
Jan '24 Mar '24 May '24 Jul '24 Sep '24 Nov '24 Jan '25 Mar '25 May '25 Jul '25 Sep '25 Nov '25 Jan '26
WIMS (OPSSP_WWTP)
SS Raw 2 Year History
Page 54 of 58
Phosphorus mg/l 2 Year History
Effluent Phosphorous Total (Mo Avg) Phosphorus Final Limit (Mo Avg)
MG/L
Date ( 01/01/2024 to 12/31/2025 )
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.9
1.0
1.1
1.2
1.3
1.4
1.5
1.6
Jan '24 Mar '24 May '24 Jul '24 Sep '24 Nov '24 Jan '25 Mar '25 May '25 Jul '25 Sep '25 Nov '25 Jan '26
WIMS (OPSSP_WWTP)
Phosphorus 2 Year History
Page 55 of 58
Effluent Ammonia mg/l 2 Year History
Effluent Ammonia (Mo Avg) Effluent Ammonia Limit (Mo Avg)
MG/L
Date ( 01/01/2024 to 12/31/2025 )
0
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
46
48
50
Jan '24 Mar '24 May '24 Jul '24 Sep '24 Nov '24 Jan '25 Mar '25 May '25 Jul '25 Sep '25 Nov '25 Jan '26
WIMS (OPSSP_WWTP)
Effluent Ammonia 2 Year History
Page 56 of 58
Sewage Plant Monthly Average
Temperature Precip. Sewage Flow Phosphorus BOD Suspended Solids Per Day Gas
Max Min Influent Effluent Raw Influent Final Effluent Raw Influent Final CBOD Eff. Reduction Raw Influent Final Effluent Reduction Power LBS BOD Production
Month ° F ° F INCHES MGD MGD MG/L LBS MG/L LBS MG/L LBS MG/L LBS % MG/L LBS MG/L LBS % kW Removed Per Day CUFT
Jan 2025 23 11 0.25 2.123 2.395 5.427 94 0.318 6 291 5,157 5.52 110.25 98 247 4,378 4.81 96.00 98 6,587 5,046
Feb 2025 26 7 0.85 2.073 2.314 6.416 111 0.452 9 332 5,748 7.23 139.59 98 290 5,011 10.05 193.90 96 6,914 5,609
Mar 2025 46 24 4.88 2.255 2.563 5.675 101 0.225 5 291 5,477 5.62 120.11 98 255 4,805 5.05 107.86 98 6,703 5,356
Apr 2025 54 33 4.26 2.782 3.173 4.022 90 0.310 8 257 5,958 6.21 164.34 98 232 5,390 7.44 196.96 97 6,433 5,794
May 2025 67 44 2.15 2.553 2.925 4.437 93 0.317 8 266 5,655 2.83 69.04 99 276 5,868 4.03 98.37 98 7,548 5,586
Jun 2025 76 58 5.45 2.335 2.682 5.498 106 0.125 3 286 5,565 3.50 78.29 99 282 5,494 2.64 59.12 99 7,320 5,487
Jul 2025 83 62 4.07 2.349 2.556 5.056 100 0.124 3 283 5,536 3.40 72.50 99 296 5,806 3.61 76.88 99 6,277 5,464
Aug 2025 77 58 3.29 2.310 2.499 4.765 92 0.388 8 289 5,571 3.62 75.47 99 281 5,422 5.07 105.62 98 6,135 5,495
Sep 2025 74 52 1.93 2.318 2.591 5.830 113 0.310 7 314 6,073 5.31 114.66 98 297 5,736 5.76 124.51 98 6,853 5,958
Oct 2025 64 42 1.32 2.199 2.477 6.218 112 0.314 6 313 5,741 4.84 99.95 98 325 5,959 5.53 114.27 98 6,123 5,641
Nov 2025 44 25 0.86 2.086 2.271 5.288 92 0.187 3 281 4,897 3.92 74.23 99 243 4,233 4.57 86.59 98 5,200 4,822
Dec 2025 26 9 1.68 2.062 2.204 5.758 100 0.303 6 315 5,414 5.29 97.34 98 253 4,354 5.20 95.67 98 6,355 5,316
Minimum 23 7 0.25 2.062 2.204 4.022 90 0.124 3 257 4,897 2.83 69.04 98 232 4,233 2.64 59.12 96 5,200 4,822
Maximum 83 62 5.45 2.782 3.173 6.416 113 0.452 9 332 6,073 7.23 164.34 99 325 5,959 10.05 196.96 99 7,548 5,958
Total 660 425 30.99 27.446 30.650 64.389 1,204 3.373 72 3,518 66,791 57.29 1,215.76 1,180 3,278 62,457 63.76 1,355.74 1,175 78,450 65,576
Average 55 35 2.58 2.287 2.554 5.366 100 0.281 6 293 5,566 4.77 101.31 98 273 5,205 5.31 112.98 98 6,537 5,465
Page 57 of 58
January 2026 Meeting
December Utility Construction and Maintenance Report
1. Contracted Road/Utility Construction Progress:
• Village of Park Ridge water main/road project, complete, punch list items remain
• Washington Ave. (Project 25-101) complete, punch list items remain
• Madison St./Monroe St. (Project 25-102) complete, punch list items remain
• Public Works re-paving Country Club Dr. complete, punch list items remain
• Fiber ring from UWSP to P.D. to Transit in progress, directional boring complete,
fiber splicing/patching projected for January
• 2026 Public Works re-paving Green Ave. (Utility structure adjustments only)
• 2026 Public Works repaving Northpoint Dr. from Stanley St. to Wilshire Dr. (utility
structure adjustments only, potential water and sewer extension)
• 2026 Michigan St. underpass reconstruct from Dixon St. to Patch St.
• 2026 Division St reconstruct from Northpoint Dr. to Briggs St.
• 2026 Church St. reconstruct from Heffron St. going south to City limits
2. Utility Maintenance Activities:
• Televising, cut, jet, flush as normal (pending weather)
• Winter Operations
• Snow Removal Duties
• Fire Hydrant Checks
• Inventory Counts
• Equipment Maintenance
• Building PM’s
3. Future Construction and Maintenance Projects:
• Swale Heffron St. - 2026
• Swale Woodland St. - 2027
4. Emergencies/Pager Calls:
• (4) After hours pager calls in December
5. Training:
• February will have multiple safety sessions given by CVMIC
• (3) Employees scheduled for DNR water certification classes & exams in March
Page 58 of 58