Pre-bid Meeting for garage 3.17.26 — Documents
Town of Brule · Douglas County · Pre-bid Meeting for garage 3.17.26 · meeting of Mar 17, 2026 · Other
Open the original document More from Town of Brule
Text
Extracted automatically from the original. Tables and formatting may not survive; the original document is authoritative.
Materials
Graphic Symbols
Location Map
Project Team
EARTH
COMPACT FILL/SAND
POROUS FILL/GRAVEL
FACE BRICK
MORTAR/PLASTER
CMU
CONCRETE
RIGID INSULATION
BATT INSULATION
STUD WALL/METAL
PLYWOOD
GYPSUM BOARD
FINISHED WOOD
CONT. ROUGH WOOD
WOOD BLOCKING
BITUMINOUS
SPRAY FOAM INSUL. OSB SHEATHING
DETAIL NUMBER
SHEET NUMBER
AREA TO BE
DETAILED OR
ENLARGED
ACTUAL NORTH (IF
DIFFERENT)
REVISION TYPE
SHEET NUMBER
SECTION NUMBER
5
A8.1
AREA A
SHEET
NUMBER
ELEVATION
NUMBER
A7.2
12
13
14
15
NORTH ARROW / COMPASS
DETAIL REFERENCE SECTION REFERENCE
REVISION IDENTIFICATION TITLE MARKER
ROOM IDENTIFICATION
ROOM NAME
ROOM NUMBER
DOOR TAG
BREAKLINE
ELEVATION REFERENCE
WALL TAG WINDOW TAG
ELEVATION LABEL MATCHLINE IDENTIFICATION NOTE IDENTIFICATION
(LEADER
OPTIONAL)
10
A7.1
1
1
A5.1
WORK
ROOM
204
T.O. STL.
100' -0"
204
1 VIEW TITLE
VIEW SCALE
W205
1ASI
5A
SEQUENTIAL
INDICATOR
APPROXIMATE THICKNESS IN
INCHES
N
REPRESENTS NEW
DOOR
REPRESENTS
EXISTING DOOR TO
REMAIN
REPRESENTS
EXISTING DOOR TO
BE REMOVED
WALLS WITH HATCH
INDICATE NEW
CONSTRUCTION
WALLS SHADED GRAY
INDICATE EXISTING TO
REMAIN
DASHED LINES INDICATE
WALLS & ITEMS TO BE
REMOVED
PLAN NORTH
REVISION NUMBER
5A
48"
PARTIAL HT.
WALL; IN
INCHES
AREA B
Star Indicates Project Location
Refer to Civil
OWNER ARCHITECT
STRUCTURAL ENGINEER
Town of Brule
Brule, WI
MECH/ELECT. ENGINEER
CIVIL ENGINEER
Northland Consulting Engineers
102 S. 21st Avenue West Suite 1
Duluth, MN 55806
Phone: 218 -727 -5995
Contact: Jon Aamodt
Email: jon@nce -duluth.com
Windsor Egineers
4802 Oneota St, Ste 2
Duluth, MN 55807
Phone: 218 -206 -8484
Contact: Josh Netterlund
Email: jnetterlund@windsorengineers.com
ARCHITECT
Contact: John Erickson
Email: jerickson@dsgw.com
DSGW Architects
2 West First St. Suite 201
Duluth, MN 55802
Phone: 218 -727 -2626
Windsor Egineers
4802 Oneota St, Ste 2
Duluth, MN 55807
Phone: 218 -203 -8323
Contact: Jack Dougherty
Email: jdougherty@windsorengineers.com
7-Mechanical - Plumbing
M0.1 Cover Sheet -Mechanical
M0.2 Schedules -Mechanical
M2.1 Floor Plan -Mechanical
M2.2 Me -Mechanical
M5.1 Cover Sheet -Mechanical
P0.1 Cover Sheet
Schedules
Schedules
Underfloor Plan
Floor Plan
Enlarged Floor Plan
Details
P0.2
P0.3
P2.1
P2.2
P3.1
P5.1
Details P5.2
Diagrams P6.1
1-Civil
G001 Sheet Index and Notes
G002 Civil Legends and Abbreviations
G003 Topographic Survey
C050 Existing Conditions and Demolition
C100 Composite Site and Utility Plan
C110 Erosion Control and Grading
C111 Grading Enlargement
C300 Stormwater Facility
C600 Erosion Control Details
C610 Site Details
C620 Sewer Details
3-Structural
S0.1 General Notes/Sheet Index
S1.0 Typical Details -Concrete
S1.1 Typical Details -Light Gauge Steel
S2.0 Foundation Plan/Mezzanine Framing Plan
S3.0 Sections and Details
8-Electrical
E0.1 Cover Sheet - Electrical
E0.2 Schedules - Electrical
E1.0 Site Plan - Electrical
E2.1 Floor Plan - Electrical
E3.1 Lighting RCP - Electrical
E5.1 Details - Electrical
E6.1 One -Line Diagram - Electrical
Çê~ïå=ÄóW
ÅÜÉÅâÉÇ=ÄóW
éêáåíÉÇ=
å~ãÉW
êÉÖK=@W
ëáÖå=Ç~íÉW
Ç~íÉW
éêçàÉÅí=@W
ëÜÉÉí=íáíäÉW
ëÜÉÉí=
åìãÄÉêW
www.dsgw.com
John E. Erickson, NCARB, LEED AP
9676
3/10/2026 9:08:13 AM
025170.00
JMG
JMG 3/10/2026
Brule Public
Works
Garage
G0.1
24x36 Title
Sheet
Town of Brule, Wisconsin
0-General Sheets
G1.1 Life Safety Plan & Energy Code Summary
G1.2 Mounting Heights
Project Number:
Brule Public Works Garage
Town of Brule, Wisconsin
025170.00
ADA AMERICANS WITH DISABILITIES ACT
ADJ ADJUSTABLE
AFF ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
ALT ALTERNATE
ALUM ALUMINUM
APPROX APPROXIMATE
ARCH ARCHITECT
B.O. / BO BOTTOM OF
B.SPLASH BACKSPLASH
BLDG BUILDING
BLKG BLOCKING
BRG BEARING
C-TOP COUNTERTOP
CG CORNER GUARD
CJ CONTROL JOINT
CL CENTERLINE
CLG CEILING
CLR CLEAR(ANCE)
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONT CONTINOUS
CPT CARPET
CT CERAMIC / PORCELAIN TILE
D DEEP
DF DRINKING FOUNTAIN
DIA DIAMETER
DIM DIMENSION
DISP DISPENSER
DN DOWN
DS DOWNSPOUT
DW DISHWASHER
DWG DRAWING
EA EACH
EIFS EXTERIOR INSULATION & FINISH SYSTEM
EJ EXPANSION JOINT
ELEC ELECTRICAL
EPDM ETHYLENE PROPYLENE DIENE MONOMER ROOFING
EQ EQUAL (EQUALLY)
EQUIP / EQPT. EQUIPMENT
EXST / EX. / EXIST. EXISTING
EXT EXTERIOR
F.T. FIRE TREATED
F.V. FIELD VERIFY
FD FLOOR DRAIN
FDN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FFGB FIBERGLASS FACED GYPSUM BOARD
FLR FLOOR
FRP FIBERGLASS REINFORCED PANEL
FTG FOOTING
FUR FURRING
GALV GALVANIZED
GB GRAB BAR
GLAZ GLAZING
GYP. BD / G.BD / GBD GYPSUM BOARD
H HIGH
HC HANDICAPPED
HM HOLLOW METAL
HT HEIGHT
ICF INSULATED (OR INSULATING) CONCRETE FORM
INSUL INSULATION
INT INTERIOR
JST JOIST
LAM LAMINATE
LVT LUXURY VINYL TILE
1. General Notes apply to all drawing sheets.
2. Review the Construction Documents prior to start of construction. Notify Architect upon encountering any unforeseen
conditions, discrepancies, errors, or inconsistencies.
3. Work shall be done in accordance with all rules a nd regulations of all applicable safety and building codes. The General
Contractor is responsible for securing and paying for all permits required and for the scheduling of all required inspections
during the course of the project.
4. The General Contractor shall take precautions and be responsible for the safety of all building occupants from construction
procedures during construction to minimize disturbances to adjacent spaces and /or structures and their occupants, property,
public thoroughfares, etc. Maintain all required exits during construction.
5. All materials and systems shall be installed as p er manufacturer's specifications and all construction shall be of industry
standard or better.
6. Do not scale drawings. Verify all dimensions in the field for accuracy prior to construction. No extra charge or compensation
shall be allowed because of difference between actual dimensions and those indicated on the drawings, unless they contribute to
a change in the scope of work.
7. In the event of conflict between data shown on dr awings and data shown in the Specification, the Work of greater quality or
quantity shall be provided, in accordance with the Architect's interpretation, and no change in the Contract Sum will be permitted.
Detail drawings take precedent over drawings of larger scope. Notify Architect if at any time an error or discrepancy is
discovered.
8. Immediately notify Architect of any long lead ite ms that will affect the completion date
9. All wood in contact with concrete or concrete blo ck to be pressure treated - typical.
10. Provide metal backing and / or treated wood bloc king for all wall mounted equipment (grab bars, toilet room accessories, TV
mounts, headwalls, equipment rails, etc.) Verify height and length with actual equipment.
11. Patch all disturbed fireproofing as required to maintain rating. Repair and install all fireproofing as required by code. Fireproof
any new penetrations required by the work. Refer to code summary for ratings.
12. All exposed metal to receive paint unless otherw ise noted
13. All adjacent dissimilar materials to receive cau lking, including equipment mounted to walls
MANUF MANUFACTURER
MATL MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MIN MINIMUM
MISC MISCELLANEOUS
MO MASONRY OPENING
MTL METAL
NA NOT APPLICABLE
NIC NOT IN CONTRACT
NOM NOMINAL
NTS NOT TO SCALE
OC / O.C. ON CENTER
OFD OVERFLOW DRAIN
OH OVERHEAD
P.T. PRESSURE TREATED
PC PRECAST
PL PLATE
PLAM / P.LAM. PLASTIC LAMINATE
PLY / PLYWD PLYWOOD
PMB PRE-MANUFACTURED METAL BUILDING SYSTEM
PNT PAINT
PREFIN / P/F PREFINISHED
PTD PAPER TOWEL DISPENSER
QT QUARRY TILE
QTY QUANTITY
RB RESILIENT BASE
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
REF REFRIGERATOR
REINF REINFORCED
REQD REQUIRED
RF RESILIENT FLOORING
RPF STRIP REINFORCED PERIMETER FASTENING STRIP
RTU ROOF TOP UNIT (MECH.)
RWL RAIN WATER LEADER
S.SPLASH SIDESPLASH
SACT SUSPENDED ACOUSTICAL CEILING TILE
SCHED SCHEDULE
SD SOAP DISPENSER
SEAL SEALANT (SEALED)
SF SQUARE FOOT (FEET)
SIM SIMILAR
SIP STRUCTURAL INSULATED (OR INSULATING) PANEL
SND SANITARY NAPKIN DISPOSAL
SPEC SPECIFICATION
SS STAINLESS STEEL
SSM SOLID SURFACE MATERIAL
STL STEEL
STND STANDARD
STRUCT STRUCTURAL CONSULTANT
SV SHEET VINYL
T.O. TOP OF
TBB TILE BACKER BOARD
TEMP TEMPERED
TPD TOILET PAPER DISPENSER
TRTD TREATED
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
VB VINYL BASE
VCT VINYL COMPOSITION TILE
VIF VERIFY IN FIELD
VWC VINYL WALL COVERING
W WIDE
W/ WITH
W/O WITHOUT
WD WOOD
WRB WEATHER RESISTIVE BARRIER
# NUMBER (OR POUND)
& AND
@ AT
Abbreviations
Perspective View
Sheet Index Architectural General Notes
êÉîáëáçå=L=áëëìÉ åçK Ç~íÉ
4-Architectural
A2.0 Floor Plan
A2.1 Enlarged Plans & Interior Elevations
A2.2 Roof Plan / RCP Plan
A4.1 Schedules and Types
A5.1 Exterior Elevations
A5.2 Exterior Elevations 3D
A6.1 Building Sections & Wall Sections
A6.2 Wall Sections
Life Safety Analysis
13'-7"
Life Safety & Energy Code Analysis
REF.
BUILDING EXIT
ACCESSIBLE FEATURE
ROOM OCCUPANCY
EXIT SIGNAGE
EMERGENCY LIGHTING
#
1 HOUR FIRE BARRIER
(EXIT ENCLOSURE OR SHAFT)
1 HOUR FIRE BARRIER
(OTHER)
2 HOUR FIRE BARRIER
(EXIT ENCLOSURE OR SHAFT)
2 HOUR FIRE BARRIER
(OTHER)
SMOKE RESISTANT PARTITION
2 HOUR FIRE WALL
1 HOUR FIRE PARTITION
MAX EXIT ACCESS TRAVEL POINT
EXIT
COMMON EGRESS PATH
FIRE EXTINGUISHER
FIRE EXTINGUISHER WITH CABINET
R
P
14
227 EXIT CAPACITY REQUIRED
PROVIDED
E
FEX
FEC
1 HOUR SMOKE BARRIER
3 HOUR FIRE (WALL OR BARRIER)
4 HOUR FIRE (WALL OR BARRIER)
MAX EXIT ACCESS TRAVEL POINT
EXIT NODE
DISTANCE BETWEEN NODES
(XX' MAX EXIT ACCESS)
EGRESS PATH
MAX EGRESS PATH
SUMMARY:
ALLOWABLE AREA CALCULATIONS
FIXTURE TYPE
REQUIRED MINIMUM TOTAL PROVIDED
WATER CLOSET
MEN
PLUMBING SYSTEMS NOTES:
WOMEN
WATER CLOSETS:
OCCUPANT LOAD: Business, RATIO: 1 PER 25 1st 50, Then 1
per 50
LAVATORIES:
OCCUPANT LOAD: Business, RATIO: 1 PER 40 1st 80, Then 1
per 80
DRINKING FOUNTAINS:
OCCUPANT LOAD: Business, RATIO: 1 PER 100
UNISEX MEN WOMEN UNISEX
** ALL RATED WALLS SHALL BE IDENTIFIED BY STENCILING ON EACH SIDE OF THE
WALL ABOVE THE CEILING WITH 3" HIGH LETTERS IDENTIFYING THE TYPE OF WALL
RATING "SMOKE PARTITION, 1 HOUR FIRE BARRIER, OR 1 HOUR SMOKE
BARRIER". SPACING OF IDENTIFICATIONS SHALL BE 6'-0" APART HORIZONTALLY.
REFER TO LIFE SAFETY PLAN FOR RATED WALL LOCATIONS. **
LAVATORY
DRINKING FOUNTAIN
SHOWER
SERVICE SINK
URINAL
1 1 3
0 0
1 1 3
0 0 0 0
1 1
1 1
FIRE RESISTANCE RATINGS (TABLE 601)
0 HR.
0 HR.
0 HR.
0 HR.
0 HR.
0 HR.
0 HR.
WISCONSIN Applicable Building Codes:
2021 International Building Code
Wisconsin Commerical Building Code
Fire Code:
2021 International Fire Code
Mechanical Code:
2021 International Mechanical Code
Energy Code:
2021 International Energy Code
Plumbing Code:
2018 Wisconsin Uniform Plumbing Code
Electrical Code:
National Electrical Code 2020
STRUCTURAL FRAME
BEARING WALLS - EXTERIOR
BEARING WALLS - INTERIOR
NONBEARING WALLS - EXTERIOR
NONBEARING WALLS - INTERIOR
FLOOR CONSTRUCTION
ROOF CONSTRUCTION
PROJECT TYPE:
SPRINKLER SYSTEM:
FIRE ALARM SYSTEM:
NON-SEPARATED OCCUPANCY:
SEPARATED OCCUPANCY:
NEW BUILD
NO
NO
NO
NO
OCCUPANCY
TYPE
CONSTRUCTION
TYPE
SPRINKLE CLASS
(NS/S1/SM)
VEHICLE
STORAGE S-1
II-B NS
OCCUPANCY GROUP
ALLOWABLE HT. (FT)
(TABLE 504.3)
65
ACTUAL STORIES
ABOVE GRADE (S a)
ACTUAL HEIGHT (FT)
ALLOW. STORIES
ABOVE GRADE
(TABLE 504.4)
18 3 1
TABULAR SF
(A
t - TABLE 506.2)
9,500
ACTUAL SF
1,970
ALLOW. AREA
(NS - TABLE 506.2)
9,500
FRONTAGE INCREASE
SF (I
f) (SECTION 506.3)
7,125
ALLOW. AREA (A a)
16,625
FRONTAGE
INCREASE %
75%
AIR BARRIER <0.004 cfm/ft^2
ASTM E2178
<0.004 cfm/ft^2
ASTM E2178
OCCUPANT LOAD (SEC 1004)
EXIT TRAVEL DISTANCE (SEC 1017)
NUMBER OF EXITS (SEC 1006)
OCCUPANT LOAD:
OCCUPANCY:
MAX. TRAVEL DISTANCE (FT):
A
200
SEE CODE PLAN
ASSEMBLY A-3
II-B NS 65 30 2 1 17,500 4,560 17,500 13,125 30,625 75%
MEANS OF EGRESS (CH. 10)
REQUIRED:
PROVIDED:
2
2
MIXED USE AND OCCUPANCY (SEC. 508)
OCCUPANCIES EXCEPTION RATING (HR)
A S-1 2
S-1
200
CORRIDORS (SEC 1020)
FIRE RATING (HR):
MIN. WIDTH (INCHES):
MAX. DEAD END DISTANCE (FT):
N.a.
PLUMBING SYSTEMS (CH. 29)
(TABLE 2902.1)
This project is for the Town of Brule's Public Works Department and Town Administration. It will be a rigid steel
framed structure with a service garage consiting of four bays and five overhead garage doors, staff area, restroom
and miscallaneous storage for equipment and supplies. Abutting the garage will be an administration building with
one office, small kitchenette, two restrooms and a large meeting room.
Code Requirements
ENERGY CODE: MINNESOTA ENERGY CODE 2024 - Prescriptive Method
Design Criteria
7
THERMAL ENVELOPE
ZONE
ROOFS: METAL BUILDING
WALLS: METAL BUILDING
HEATED SLAB
OPAQUE DOORS: SWINGING
FENESTRATION
OPERABLE
ENTRANCE DOORS
FIXED
R-30+R-11 LS
U-0.029
R-20 for 48" below
R-5 Full Slab
U-0.37 U-0.37
U-0.36; SHGC 0.36 U-0.30 Argon
U-0.63; SHGC 0.36 U-0.29
U-0.29; SHGC 0.40 U-0.45
R-30+R-11 LS
U-0.029
R-13+R-17 C.I.
U-0.044
R-13+R-17 C.I.
U-0.044
R-20 for 48" below
R-5 Full Slab
Exit Width
Required
Provided
2"
36"
S-1 Occ
4,960 sf
A-3 Occ
1460 sf
Exit Width
Required
Provided
2"
36"
FEX
FEX
EE
E
E
Exit Width
Required
Provided
6"
36"
54
Exit Width
Required
Provided
6"
36"
8
8
20'
22'
33' 30
8'
13'
36'
12'
27
27
16
E
3-HR
FIRE BARRIER
NOTE:
PLATFORM OVER THESE ROOMS
IS DESIGNATED AS AN
EQUIPMENT PLATFROM AND
NON -OCCUPIED --
WILL BE MARKED "NO STORAGE ALLOWED"
NOTES:
903.2.9: S-1 LIMITED TO LESS THAN 5,000 SF FIRE AREA WITHOUT A SPRINKLER SYSTEM
707.3.10: FIRE AREA TO BE SEPARATED WITH FIRE BARRIER RATED 3-HOUR
FEX
Çê~ïå=ÄóW
ÅÜÉÅâÉÇ=ÄóW
éêáåíÉÇ=
å~ãÉW
êÉÖK=@W
ëáÖå=Ç~íÉW
Ç~íÉW
éêçàÉÅí=@W
ëÜÉÉí=íáíäÉW
ëÜÉÉí=
åìãÄÉêW
www.dsgw.com
John E. Erickson, NCARB, LEED AP
9676
3/10/2026 9:08:14 AM
025170.00
JMG
JMG
3/10/2026
Brule Public
Works
Garage
G1.1
Life Safety Plan
& Energy Code
Summary
Town of Brule, Wisconsin
3/32" = 1'-0" G1.1
1 Level 1 Code Plan
êÉîáëáçå=L=áëëìÉ åçK Ç~íÉ
URINAL SIDE VIEW
URINAL SHIELD URINAL SHIELD
STANDARD URINAL
FRONT VIEW
NOT ACCESSIBLE
ADA URINAL
FRONT VIEW
MIN. CLEAR FLOOR AREA
48"
17" MAX
FLOOR AREA
30" MIN. CLR.
SEE NOTE ABOVE
48" MAX.
30"
SANITARY
NAPKIN
DISPOSAL
SANITARY
NAPKIN
DISPENSER
TYPICAL FIXTURES AND ACCESSORIES MOUNTING HEIGHTS
LAVATORY SIDE VIEW
17" MIN.
34" MAX.
48" MIN. CLR. FLR AREA
LAVATORY FRONT VIEW
MIRROR
30" MIN.
24" TYP
36" TYP
34" MAX.
40" MAX. REFL'D SURFACE
KNEE
CLEARANCE
MIN.
11"
MIN.
8"
MAX.
6" MIN.
15"
COUNTER
WHERE
OCCURS
ACCESSIBLE
LAVATORY
BOWL 6 1/2"
DEEP
MIN.
9"
MIN.
27"
PIPE
SHIELD
TYP.
MIRROR
MIRROR WITH OUT LAVATORIES
OR COUNTERTOPS
40" MAX.
FULL LENGTH MIRRORS SHOULD BE 74" MIN.
HAND DRYER
SIDE VIEW
HAND DRYER
FRONT VIEW
SEE NOTE ABOVE
FOR SIDE APPROACH
50" CLR. FL. SPACE
SEE NOTE ABOVE
10"
FOR SIDE APPROACH
30" CLR. FL. SPACE
SOAP DISPENSER
FOR SIDE APPROACH
48" CLEAR FLR. SPACE
MAX. HT. @ COUNTERS
44"
SEE NOTE ABOVE
SEE NOTE ABOVE
PAPER TOWEL DISPENSERS
KNEE
CLEARANCE TOE CLEARANCE
KNEE CLEARANCE
TOE CLEARANCE
MIN
11"
25" MAX
9"
17" - 25"
6" MAX
9"
MIN
8"
27" MIN
F.E.C.
RECESSED F.E.C. MOUNT
CONTROLS @ 40" A.F.F.
FIRE EXTINGUISHER CABINET FRONT
VIEW
48" MAX. OPERABLE PARTS
OPERABLE PARTS
15" MIN.
40"
COUNTER
W/ BACK
SPLASH
SEE TABLE 603.6 DIM (B)
NOTE: TO OPERABLE PART OF PTD & HAND DRYERS
WITHOUT COUNTER OR OBSTRUCTION TYPICAL
48" MAX FORWARD APPROACH & SIDE APPROACH
(A) MAX
SEE TABLE 603.6
(B) MAX
MAX REACH
DEPTH (A)
MAX REACH
HEIGHT (B)
0.5" 48"
2" 46"
5" 42"
6" 40"
9" 36"
11" 34"
TABLE 603.6
PAPER TOWEL DISPENSER FRONT VIEW @
COUNTER OR LAVATORY IN TOILET &
BATHING ROOMS (HAND DRYER SIM.)
PROVIDE BLOCKING AS REQUIRED FOR ALL
WALL MOUNTED ITEMS
WATER CLOSET SIDE VIEW
(F LOOR MOUNT )
WATER CLOSET FRONT VIEW
(FLOOR MOUNT )
MAX.
12"
MIN.
42"
39" - 41"
MIN. CLR. FLOOR AREA
48"
33" - 36"
39" - 41" 18" MIN.
33" - 36"
MIN. CLEAR FLOOR AREA
42" 16" - 18"
36" MIN.
OR 48" FROM WATER CLOSET
78" MIN.
58" STANDARD TYP. 12"
6"
60" MIN.
6"
6" x 9" MIN. TOE
SPACE TYP.
(12" HIGH FOR
CHILDREN)
PARTITION WHERE OCCURS
1 1/4" -2" DIA. GRAB BAR WITH 1
1/2" GAP FROM WALL TYP. FOR ALL
GRAB BARS. PROVIDE BLOCKING
TYP.
PROTRUDING DISPENSER IN AREA
1 1/2" BELOW GRAB BAR ONLY
AMBULATORY STALL SIDE
VIEW TYP. BOTH SIDES
MAX.
12"
MIN.
42"
39" - 41"
33" - 36"
39" - 41" 18" MIN.
60" MIN.
VERIFY SIZE W/MANUFACTURER
58" TYP. 12"
6"
GRAB BARS TYP.
24" MIN.
MIN.
18"
AMBULATORY STALL
FRONT VIEW
36"
6"
PARTITION
17" - 19"
33" - 36"
39" - 41" 18" MIN.
54" MIN. 54" MIN.
24" MIN. 12" MIN.
42" MAX.
39" - 41" 18" MIN.
9"
12"
9"
12"
NOTE: FLUSH
CONTROLS SHALL BE
LOCATED ON THE
OPEN SIDE OF THE
WATER CLOSET
NOTE: AMBULATORY
STALL FLUSH
CONTROLS SHALL BE
PERMITTED ON EITHER
SIDE OF THE WATER
CLOSET
17" - 19"
17" - 19"
17" - 19"
1 1/2" MIN
MIN.
18" 1 1/2" MIN 24" MIN
42" MAX
17" - 19"
17" MAX
24"
13 1/2" MIN
OH BRACE
FLOOR MOUNT
8"
36" MAX
48" MAX
PROTRUDING DISPENSER IN AREA
1 1/2" BELOW GRAB BAR ONLY
36" MAX
48" MAX
RECESSED DISPENSER
MAY ALSO BE
INSTALLED WITHIN
SHADED AREA
RECESSED DISPENSER
MAY ALSO BE
INSTALLED WITHIN
SHADED AREA
Çê~ïå=ÄóW
ÅÜÉÅâÉÇ=ÄóW
éêáåíÉÇ=
å~ãÉW
êÉÖK=@W
ëáÖå=Ç~íÉW
Ç~íÉW
éêçàÉÅí=@W
ëÜÉÉí=íáíäÉW
ëÜÉÉí=
åìãÄÉêW
www.dsgw.com
John E. Erickson, NCARB, LEED AP
9676
3/10/2026 9:08:15 AM
025170.00
Template
xx
3/10/2026
Brule Public
Works
Garage
G1.2
Mounting
Heights
Town of Brule, Wisconsin
êÉîáëáçå=L=áëëìÉ åçK Ç~íÉ
PROJECT NOTESTHE PROPOSED PROJECT CONSISTS OF THE CONSTRUCTION OF A NEW PUBLIC WORKSGARAGE BUILDING APPROXIMATELY 132 FEET BY 53 FEET IN SIZE, INCLUDING ASSOCIATEDSITE IMPROVEMENTS SUCH AS A GRAVEL DRIVE AISLE AND PARKING AREA, SIDEWALKINSTALLATION, SANITARY SEWER SERVICE, WATER WELL INSTALLATION, AND A STORMWATERMANAGEMENT FACILITY. THE PROJECT SITE ENCOMPASSES APPROXIMATELY 6.00 ACRES ANDIS LOCATED WITHIN THE TOWN OF BRULE NEAR THE INTERSECTION OF OLD HIGHWAY 2 ANDDUMP ROAD. THE PROPOSED DEVELOPMENT WILL RESULT IN APPROXIMATELY 2.08 ACRES OFLAND DISTURBANCE.PARCEL NO.(S):BR-006-00179-00SITE ADDRESS:0 DUMP ROADBRULE, WI. 54820LEGAL DESCRIPTION:E-1/2 NW-1/4, LYG N & W OF TOWN RD 13-47-10, DESC 413 RP 930, EX R/WCOUNTY:DOUGLAS COUNTY, WISCONSINCONTACT INFORMATIONAPPLICANT / PROPERTY OWNERTOWN OF BRULE, WISCONSIN5231 S COUNTY LINE ROADBRULE, WI 54820CONTACT: TOWN OF BRULEPHONE: (218) 591-0693EMAIL: CLERK@BRULEWI.GOVREPRESENTATIVE / CONTACTWINDSOR ENGINEERS, LLC4802 ONEOTA STREET, SUITE 2DULUTH, MN 55807CONTACT: JACK DOUGHERTYPHONE: (218) 203-8323EMAIL: JDOUGHERTY@WINDSORENGINEERS.COMARCHITECTDSGW ARCHITECTURE2 W 1ST ST SUITE 201DULUTH, MN 55802CONTACT: NICK HULSTROMPHONE: (218) 727-2626EMAIL: NHULSTROM@DSGW.COMGEOTECHNICAL ENGINEERTWIN PORTS TESTING1301 N 3RD ST.SUPERIOR, WI 54880CONTACT: BRETT CARLSONPHONE: 715-392-7114EMAIL: BCARLSON@TWINPORTSTESTING.COM
GENERAL PLAN NOTES1. CONTRACTOR TO VERIFY ALL UTILITY LOCATIONS AND DEPTHS PRIOR TO CONSTRUCTION. A MINIMUM OFTWO FULL BUSINESS DAYS PRIOR TO BEGINNING CONSTRUCTION, THE CONTRACTOR SHALL CALL 811 (UTILITYNOTIFICATION CENTER) FOR LOCATION MARK-UP OF EXISTING UTILITIES3. IN CASE OF A CONFLICT BETWEEN THE REGULATORY STANDARDS OR SPECIFICATIONS, THE MORESTRINGENT REQUIREMENT WILL PREVAIL.4. ANY CHANGES TO THE DESIGN AND/OR CONSTRUCTION SHALL BE APPROVED BY THE OWNER OR ENGINEER.5. APPROVAL OF THESE PLANS DOES NOT CONSTITUTE AN APPROVAL OF ANY OTHER CONSTRUCTION NOTSPECIFICALLY SHOWN ON THE PLANS. PLANS FOR STRUCTURES SUCH AS BRIDGES, BUILDINGS, TANKS,VAULTS, ROCKERIES, AND RETAINING WALLS MAY REQUIRE A SEPARATE REVIEW AND APPROVAL BY THEBUILDING DEPARTMENT PRIOR TO CONSTRUCTION.6. A COPY OF THESE APPROVED PLANS SHALL BE ON THE JOB SITE WHENEVER CONSTRUCTION IS INPROGRESS.7. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO OBTAIN ALL CONSTRUCTION EASEMENTS ANDPERMITS NECESSARY TO PERFORM THE WORK.8. THE CONTRACTOR IS RESPONSIBLE FOR ALL CONSTRUCTION STAKING.9. PUBLIC AND PRIVATE DRAINAGE WAYS SHALL BE PROTECTED FROM POLLUTION. NO MATERIAL IS TO BEDISCHARGED TO OR DEPOSITED IN STORMWATER SYSTEMS THAT MAY RESULT IN VIOLATION OF STATE ORFEDERAL WATER QUALITY STANDARDS.10. ALL CONSTRUCTION WITHIN THE PUBLIC RIGHT-OF-WAY SHALL HAVE AN APPROVED PUBLIC RIGHT-OF-WAYWORK PERMIT PRIOR TO ANY CONSTRUCTION ACTIVITY WITHIN THE RIGHT-OF- WAY.11. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ADEQUATE SAFEGUARDS, SAFETY DEVICES,PROTECTIVE EQUIPMENT, FLAGGERS, AND ANY OTHER NEEDED ACTIONS TO PROTECT THE LIFE, HEALTH, ANDSAFETY OF THE PUBLIC, COMPLY WITH OSHA REGULATIONS, AND TO PROTECT PROPERTY IN CONNECTIONWITH THE PERFORMANCE OF WORK COVERED BY THE CONTRACTOR. ALL TRAFFIC CONTROL DEVICES SHALLCONFORM TO THE LATEST ADOPTED EDITION OF THE "MANUAL ON UNIFORM TRAFFIC CONTROL DEVICES"(MUTCD) PUBLISHED BY THE U.S. DEPARTMENT OF TRANSPORTATION. TWO-WAY TRAFFIC MUST BEMAINTAINED AT ALL TIMES ON THE ADJACENT PUBLIC STREETS.12. ANY PUBLIC OR PRIVATE CURB, GUTTER, SIDEWALK, OR ASPHALT DAMAGED DURING CONSTRUCTIONSHALL BE REPAIRED TO DOUGLAS COUNTY STANDARDS AND PRACTICES.13. THE CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING THE INTEGRITY OF ADJACENT UTILITIESWHICH MAY INCLUDE, BUT ARE NOT LIMITED TO, WATER, SANITARY SEWER, STORMWATER, POWER,TELEPHONE, CABLE TV, GAS, IRRIGATION, AND STREET LIGHTING. THE CONTRACTOR SHALL NOTIFYRESIDENTS AND BUSINESSES 48 HOURS IN ADVANCE OF ANY WORK AFFECTING ACCESS OR SERVICE ANDSHALL MINIMIZE INTERRUPTIONS TO DRIVEWAYS FOR RESIDENTS AND BUSINESSES ADJACENT TO THEPROJECT.14. ALL LAWN AND VEGETATED AREAS DISTURBED WILL BE RESTORED TO ORIGINAL CONDITION. ANYDISTURBANCE OR DAMAGE TO OTHER PROPERTY ON ADJACENT PARCELS OR IN THE PUBLIC RIGHT OF WAYSHALL ALSO BE REPAIRED OR RESTORED TO ORIGINAL CONDITION.15. ALL MATERIALS AND METHODS OF CONSTRUCTION AND INSTALLATION FOR WATER, SANITARY SEWER, ANDSTORM FACILITIES SHALL CONFORM TO THE AHJ AND LGU. CONSTRUCTION SHALL BE AS PER THE MOSTCURRENT STANDARD DETAIL CONTAINED THEREIN.16. THE TYPES, LOCATIONS, SIZES AND/OR DEPTHS OF EXISTING UNDERGROUND UTILITIES AND STRUCTURESAS SHOWN ON THE DRAWINGS ARE APPROXIMATE AND WERE OBTAINED FROM SOURCES OF VARYINGRELIABILITY. THE CONTRACTOR IS CAUTIONED THAT ONLY ACTUAL EXCAVATION WILL REVEAL THE TYPES,EXTENT, SIZES, LOCATIONS, AND DEPTHS OF UTILITIES. A REASONABLE EFFORT HAS BEEN MADE TO LOCATEAND DELINEATE ALL KNOWN UNDERGROUND UTILITIES. THE CONTRACTOR SHALL VERIFY THE LOCATION OFAND PROVIDE PROTECTION FOR ALL UTILITIES AND STRUCTURES. OVERHEAD UTILITIES ARE NOT SHOWN.17. EXISTING UTILITIES DAMAGED BY THE CONTRACTOR SHALL BE REPAIRED BY THE CONTRACTOR OR BY THEUTILITY.18. WHERE THE CONTRACTOR MUST RELOCATE WATER AND GAS UTILITIES, SHUTDOWN SHALL ONLY BEACCOMPLISHED BY THE CITY OR UTILITY PURVEYOR.19. ALL OPEN TRENCHES THAT IMPACT PUBLIC ACCESS OR OTHER PROJECT WORK ACCESS OUTSIDE OF THISPROJECTS SITE, MUST BE STEEL PLATED OR BACKFILLED AND PAVED WITH AT LEAST 2" OF COLD MIX TOADJACENT EXISTING GRADE AT THE END OF EACH WORKDAY.20. NOTIFY ADJACENT RESIDENCES AT LEAST ONE DAY PRIOR TO COMMENCING WORK ADJACENT TO THEIRRESIDENCES.21. SAWCUT ALL PAVEMENT JOIN LINES. WHERE THERE IS A PREVIOUS PAVING EDGE OR CRACK WITHIN 5' OFTHE SAWCUT EDGE, REMOVE THE PAVEMENT TO THE PREVIOUS PAVING EDGE.22. THE CONTRACTOR SHALL COMPLY WITH WISCONSIN REQUIREMENTS FOR TRENCH SAFETY.23. THE CONTRACTOR SHALL REPLACE ALL SURVEY MONUMENTS THAT ARE DESTROYED BY THECONSTRUCTION.24. ALL WATER SERVICE PIPING SHALL BE CONSTRUCTED WITH 7' MINIMUM COVER, ALL WATER MAIN PIPINGSHALL BE CONSTRUCTED WITH 7.5' MINIMUM COVER, 1' VERTICAL SEPARATION BETWEEN UTILITIES, AND AMINIMUM OF 10' HORIZONTAL SEPARATION AND 18" ABOVE SEWER LINES, UNLESS OTHERWISE NOTED.25. THE CONTRACTOR SHALL RESTORE PAVEMENT AND LANDSCAPING DISTURBED BY THE CONSTRUCTION TOTHE PREVIOUSLY UNDISTURBED CONDITION.26. CONTRACTOR TO DISPOSE OF TREES, SHRUBS, SOD AND OTHER DEBRIS IN A PROPER MANNER OF THECONTRACTOR'S CHOOSING.27. CONTRACTOR IS RESPONSIBLE FOR KEEPING ALL ROADS, SIDEWALK, AND TRAILS CLEAN AND CLEAR FROMCONSTRUCTION MATERIAL AND DEBRIS.28. IN ADDITION TO IN-PLACE DENSITY TESTING, THE SUBGRADE AND BASE ROCK SHALL BE PROOF-ROLLEDWITH A LOADED 10-YD DUMP TRUCK PROVIDED BY THE CONTRACTOR. BASE ROCK PROOF-ROLL SHALL TAKEPLACE IMMEDIATELY PRIOR TO (WITHIN 24 HOURS OF) PAVING, AND SHALL BE WITNESSED BY THE OWNERSREPRESENTATIVE. LOCATION AND PATTERN OF PROOF-ROLL TO BE AS DIRECTED BY OWNERSREPRESENTATIVE OR APPROVING AGENCY.
GENERAL CIVIL NOTESSURVEYBOUNDARY SURVEY: PINE RIDGE LAND SURVEYING, LLC.TOPOGRAPHIC: LIDAR INFORMATION FROM WISDOTHORIZONTAL DATUM: DOUGLAS COUNTYVERTICAL DATUM: NAVD88COORDINATE SYSTEM: DOUGLAS COUNTY TRANSVERSE MERCATOR 96STORM DRAINAGE:ON-SITE STORM SEWER IMPROVEMENTS SHALL CONFORM TO THE LATEST VERSION OF THE TOWN OFBRULE OR DOUGLAS COUNTY STANDARD SPECIFICATIONS. IN INSTANCES WHERE TOWN OF BRULE ORDOUGLAS COUNTY STANDARD SPECIFICATIONS DO NOT APPLY, WISDOT SPECIFICATIONS SHOULD BEFOLLOWED.THE CONTRACTOR SHALL MAINTAIN 6" MINIMUM VERTICAL AND 3' MINIMUM HORIZONTAL CLEARANCE(OUTSIDE SURFACES) BETWEEN STORM DRAIN PIPES AND OTHER UTILITY PIPES AND CONDUITS. FORCROSSINGS OF SANITARY SEWER LINES, THE WISCONSIN DEPARTMENT OF NATURAL RESOURCES ANDNATURAL RESOURCE CODE APPLY.STORM DRAIN PIPE, BENDS, AND FITTINGS SHALL BE PVC, ASTM D 3034, SDR 35, OR SMOOTH INTERIOR,HIGH DENSITY POLYETHYLENE CORRUGATED PIPE AASHTO M252 OR M294, TYPE S AS PRODUCED ANDSPECIFIED BY ADS, PRODUCT NAME N12, OR APPROVED EQUAL. ALL STORM SEWER FITTINGS ANDPIPE JOINTS SHALL BE GASKETED.ALL ON-SITE STORMWATER FACILITIES SHALL BE PRIVATELY MAINTAINED BY THE CURRENT ORFUTURE PROPERTY OWNER(S).ALL VAULT, UTILITY BOX, INLET, MANHOLE AND CLEANOUT RIMS SHALL BE ADJUSTED TO FINISH GRADEUNLESS OTHERWISE NOTED.IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO PROTECT AND MAINTAIN ANY STORM SYSTEMPIPING TO EXISTING DRAINAGE APPURTENANCES TO REMAIN.CONTRACTOR IS RESPONSIBLE FOR ALL PERMITS AND INSPECTIONS.ARCHAEOLOGYIF ANY CULTURAL RESOURCES AND/OR HUMAN REMAINS ARE DISCOVERED IN THE COURSE OFUNDERTAKING THE DEVELOPMENT ACTIVITY, THE DEPARTMENT OF ARCHAEOLOGY AND HISTORICPRESERVATION SHALL BE NOTIFIED. FAILURE TO COMPLY WITH THESE STATE REQUIREMENTS MAYCONSTITUTE A CLASS C FELONY, SUBJECT TO IMPRISONMENT AND/OR FINES.GRADING & EROSION CONTROL NOTESFINISH GRADE CONTOURS ARE TO TOP OF FINISHED SURFACE IN IMPERVIOUS AREAS AND TOP OFREPLACED STRIPPINGS IN PERVIOUS AREAS.CUT AND FILL QUANTITIES HAVE NOT BEEN DETERMINED. CONTRACTOR TO PERFORM QUANTITYTAKEOFF FOR ESTIMATING PURPOSES. CONTRACTOR SHALL BE RESPONSIBLE FOR HAUL-OFF EXCESSMATERIAL.GRADING AND FILL TO BE PERFORMED IN ACCORDANCE WITH GEOTECHNICAL RECOMMENDATIONSAS LAID OUT IN THE GEOTECHNICAL REPORT PREPARED BY TWIN PORTS TESTING.
GENERAL FIRE NOTES1.GENERAL FIRE SAFETY PRECAUTIONS SHALL BE MAINTAINED, IN ACCORDANCE WITH CHAPTER33 OF THE INTERNATIONAL FIRE CODE; FIRE SAFETY DURING CONSTRUCTION2.ALL WORK SUBJECT TO FIELD INSPECTION AND CORRECTION(S) AS IDENTIFIED AT THE TIME OFTHE ON-SITE INSPECTION; ALL WORK SHALL BE COMPLIANT WITH THE APPLICABLE STANDARDSAND CODES; TO INCLUDE THE ADOPTED EDITION OF THE INTERNATIONAL FIRE CODE AND THECOUNTY'S MUNICIPAL CODE.3.IFC APPENDIX D FIRE APPARATUS ACCESS ROADS. WHERE HYDRANTS ARE ON A FIREAPPARATUS ACCESS ROAD, THE MINIMUM WITH OF THE ROAD SHALL BE 26 FEET FOR ADISTANCE OF 20 FEET; 10 FEET IN EITHER DIRECTION.4.IFC 503.3 MARKING WHERE REQUIRED BY THE FIRE CODE OFFICIAL, APPROVED SIGNS OROTHER APPROVED NOTICES OR MARKINGS THAT INCLUDE THE WORDS NO PARKING FIRE LANESHALL BE PROVIDED FOR FIRE APPARATUS ACCESS ROADS TO IDENTIFY SUCH ROADS ORPROHIBIT THE OBSTRUCTION THEREOF. THE MEANS BY WHICH FIRE LANES ARE DESIGNATEDSHALL BE MAINTAINED IN A CLEAN AND LEGIBLE CONDITION AT ALL TIMES AND BE REPLACEDOR REPAIRED WHEN NECESSARY TO PROVIDE ADEQUATE VISIBILITY.5.IFC D103.6 FIRE APPARATUS ACCESS PARKING RESTRICTIONS--SIGNS: REQUIRED ROADWAYSMUST HAVE SIGNAGE FOR PARKING RESTRICTIONS AS FOLLOWS: SIGNS FOR NO-PARKING--FIRELANE SHALL COMPLY WITH A MINIMUM DIMENSION OF 12 INCHES WIDE BY 18 INCHES HIGH ANDHAVE RED LETTERS ON A WHITE REFLECTIVE BACKGROUND. SIGN'S SHALL BE PROVIDED ONBOTH SIDES OF ALL STREETS THAT ARE LESS THAN 26 IN WIDTH IN ACCORDANCE WITH LOCALSTANDARDS FOR ACCESS AND FUTURE ENFORCEMENT; SIGNS FOR NO-PARKING MUST BEPROVIDED ON ONE SIDE OF ALL STREETS THAT ARE BETWEEN 26 AND 32 IN WIDTHACCORDANCE WITH LOCAL STANDARDS FOR ACCESS AND FUTURE ENFORCEMENT.6.IFC 506 WHERE REQUIRED ACCESS IS RESTRICTED WITH A GATE, AN APPROVED PADLOCK ORKEY SWITCH (FOR ELECTRONIC/AUTOMATED GATES) SHALL BE PROVIDED TO ALLOW FIREDEPARTMENT ACCESS.7.IFC 503.1.1 / D102 / D103 ROADWAYS TO ACCESS STRUCTURES: THE PERIMETER OF ALLSTRUCTURES MUST BE WITHIN 150 FEET OF AN APPROVED ACCESS ROAD WITH A MINIMUMCLEAR WIDTH OF 20 FEET (26 FEET WHERE A HYDRANT IS LOCATED). BUILDING SHALL BEINSTALLED WITH AUTOMATIC FIRE SPRINKLERS AS AN ALTERNATIVE TO DISTANCE FROM A FIREACCESS ROAD.8.IFC 507.5.4 FIRE PROTECTION WATER SUPPLY: UNOBSTRUCTED ACCESS TO FIRE HYDRANTSSHALL BE MAINTAINED AT ALL TIMES. THE FIRE DEPARTMENT SHALL NOT BE DETERRED ORHINDERED FROM GAINING IMMEDIATE ACCESS TO FIRE PROTECTION EQUIPMENT OR FIREHYDRANTS REQUIRED ACCESS ROADWAYS AND HYDRANTS SHALL BE SERVICEABLE ANDUNOBSTRUCTED PRIOR TO COMBUSTIBLE CONSTRUCTION.
STANDARD NOTES FOR EROSION CONTROL PLAN1. APPROVAL OF THIS EROSION/SEDIMENTATION CONTROL (ESC) PLAN DOES NOT CONSTITUTE ANAPPROVAL OF PERMANENT ROAD OR DRAINAGE DESIGN (E.G. SIZE AND LOCATION OF ROADS,PIPES, RESTRICTIONS, CHANNELS, RETENTION FACILITIES, UTILITIES, ETC.)2. THE IMPLEMENTATIONS OF THESE ESC PLANS AND THE CONSTRUCTIONS, MAINTENANCE,REPLACEMENT, AND UPGRADING OF THESE ESC FACILITIES IS THE RESPONSIBILITY OF THEAPPLICANT/CONTRACTOR, UNTIL ALL CONSTRUCTION IS COMPLETED AND APPROVED ANDVEGETATION/LANDSCAPING IS ESTABLISHED.3. THE BOUNDARIES OF THE CLEARING LIMITS SHOWN ON THIS PLAN SHALL BE CLEARLY FLAGGEDIN THE FIELD PRIOR TO CONSTRUCTION. DURING THE CONSTRUCTION PERIOD, NO DISTURBANCEBEYOND THE FLAGGED CLEARING LIMITS SHALL BE PERMITTED. THE FLAGGING SHALL BEMAINTAINED BY THE APPLICANT/CONTRACTOR FOR THE DURATION OF CONSTRUCTION.4. THE ESC FACILITIES SHOWN ON THIS PLAN MUST BE CONSTRUCTED IN CONJUNCTION WITH ALLCLEARING AND GRADING ACTIVITIES, AND IN SUCH A MANNER AS TO INSURE THAT SEDIMENT ANDSEDIMENT LADEN WATER DO NOT ENTER THE DRAINAGE SYSTEMS, ROADWAYS, OR VIOLATEAPPLICABLE WATER STANDARDS.5. THE ESC FACILITIES SHOWN ON THIS PLAN ARE THE MINIMUM REQUIREMENTS FORANTICIPATED SITE CONDITIONS, DURING THE CONSTRUCTION PERIOD, THESE ESC FACILITIESSHALL BE UPGRADED AS NEEDED FOR UNEXPECTED STORM EVENTS AND TO ENSURE THATSEDIMENT AND SEDIMENT LADEN WATER DO NOT LEAVE THE SITE.6. THE ESC FACILITIES SHALL BE INSPECTED DAILY BY THE APPLICANT/CONTRACTOR ANDMAINTAINED AS NECESSARY TO ENSURE THEIR CONTINUED FUNCTIONING.7. THE ESC FACILITIES ON INACTIVE SITES SHALL BE INSPECTED AND MAINTAINED A MINIMUM OFONCE A MONTH OR WITHIN THE 48 HOURS FOLLOWING A STORM EVENT.8. AT NO TIME SHALL MORE THAN ONE FOOT OF SEDIMENT BE ALLOWED TO ACCUMULATE WITHINA TRAPPED CATCH BASIN. ALL CATCH BASINS AND CONVEYANCE LINES SHALL BE CLEANED PRIORTO PAVING. THE CLEANING OPERATIONS SHALL NOT FLUSH SEDIMENT LADEN WATER INTO THEDOWNSTREAM SYSTEM.9. STABILIZED CONSTRUCTION ENTRANCES SHALL BE INSTALLED AT THE BEGINNING OFCONSTRUCTION AND MAINTAINED FOR THE DURATION OF THE PROJECT. ADDITIONAL MEASURESMAY BE REQUIRED TO ENSURE ALL PAVED AREAS ARE KEPT CLEAN FOR THE DURATION OF THEPROJECT.10. THE PROPOSED STORMWATER FACILITY MUST REMAIN OFFLINE UNTIL THE PROJECT ISCOMPLETE AND VEGETATION THROUGHOUT THE SITE HAS BEEN ESTABLISHED. IF AT ANY TIMETHE FACILITY BECOMES INUNDATED WITH SEDIMENT FILLED RUNOFF, THE TOP 2" OF MATERIALMUST BE REMOVED AND REPLACED PRIOR TO PROJECT COMPLETION.RECOMMENDED CONSTRUCTION SEQUENCE FOR EROSIONCONTROL1. PRE-CONSTRUCTION MEETING.2. FLAG OR FENCE CLEARING LIMITS3. POST NOTICE OF CONSTRUCTION ACTIVITY SIGN WITH THE NAME AND PHONE NUMBER OFEROSION SEDIMENT CONTROL SUPERVISOR.4. INSTALL CATCH BASIN PROTECTION, IF REQUIRED.5. INSTALL PERIMETER PROTECTION (SILT FENCE, BRUSH BARRIER, ETC.).6. INSTALL TREE PROTECTION FENCING.7. GRADE AND INSTALL CONSTRUCTION ENTRANCE(S).8. CONSTRUCT SEDIMENT POND(S) AND TRAP(S).9. GRADE AND STABILIZE CONSTRUCTION ROADS.10. CONSTRUCT SURFACE WATER CONTROLS (INTERCEPT DIKES, PIPE SLOPE DRAINS, ETC)SIMULTANEOUSLY WITH CLEARING AND GRADING FOR PROJECT DEVELOPMENT.11. MAINTAIN EROSION CONTROL MEASURES IN ACCORDANCE WITH STORMWATER MANAGEMENTMANUAL FOR WESTERN MINNESOTA AND MANUFACTURER'S RECOMMENDATIONS12. RELOCATE SURFACE WATER CONTROLS AND EROSION CONTROL MEASURE OR INSTALL NEWMEASURES SO THAT AS SITE CONDITIONS CHANGE THE EROSION AND SEDIMENT CONTROL ISALWAYS IN ACCORDANCE WITH THE CLARK COUNTY EROSION AND SEDIMENT CONTROLSTANDARDS.13. COVER ALL AREAS THAT WILL BE UNWORKED FOR MORE THAN SEVEN DAYS DURING THE DRYSEASON OR TWO DAYS DURING THE WET SEASON WITH STRAW, WOOD FIBER MULCH, COMPOST,PLASTIC SHEETING OR EQUIVALENT.14. STABILIZE ALL AREAS THAT REACH FINAL GRADE WITHIN SEVEN DAYS.15. SEED OR SOD ANY AREAS TO REMAIN UNWORKED FOR MORE THAN 30 DAYS.16. UPON COMPLETION OF THE PROJECT, ALL DISTURBED AREAS MUST BE STABILIZED AND BESTMANAGEMENT PRACTICES REMOVED IF APPROPRIATE.
AMERICANS WITH DISABILITIES ACT (ADA) NOTES1. CONTRACTORS SHALL EXERCISE APPROPRIATE CARE AND PRECISION IN CONSTRUCTION OF ADAACCESSIBLE COMPONENTS ON THE PROJECT, THE ADA COMPONENTS MUST COMPLY WITH ALL LOCAL,STATE, AND FEDERAL ACCESSIBILITY RULES, CODES, AND REGULATIONS.2. FINISHED SURFACES ALONG THE ACCESSIBLE PATH OF TRAVEL FROM PARKING STALLS, PUBLICTRANSPORTATION, AND PEDESTRIAN ACCESS WAYS TO THE POINT(S) OF ACCESSIBLE BUILDINGINGRESS AND EGRESS SHALL COMPLY WITH ADA CODE REQUIREMENTS.3. PARKING SPACE AND AISLE SLOPE SHALL NOT EXCEED 1:48 (1/4" PER FOOT OR NOMINALLY 2.0%) INANY DIRECTION.4. CURB RAMP SLOPE SHALL NOT EXCEED 1:12 (8.3%) AND RAMP LENGTH IS LIMITED TO 15 FEET.5. LANDINGS SHALL BE PROVIDED AT EACH END OF RAMPS, SHALL HAVE POSITIVE DRAINAGE, ANDSHALL NOT EXCEED 1:48 (1/4"PER FOOT OR NOMINALLY 2.0%) IN ANY DIRECTION.6. PATH OF TRAVEL ALONG ACCESSIBLE ROUTE SHALL PROVIDE A MINIMUM OF 36 INCH UNOBSTRUCTEDWIDTH OF TRAVEL. SLOPE SHALL BE NO GREATER THAN 1:20 (5.0% OR 5/8" PER FOOT) IN THE DIRECTIONOF TRAVEL, AND SHALL NOT EXCEED 1:48 (1/4" PER FOOT OR NOMINALLY 2.0%) IN CROSS SLOPE. WHEREPATH OF TRAVEL BE GREATER THAN 1:20 (5.0%), AN ACCESSIBLE RAMP WITH A MAXIMUM SLOPE OF 1:12(8.3%) FOR A MAXIMUM DISTANCE OF 30 FEET SHALL BE PROVIDED INCLUDING HANDRAILS. THE RAMPSHALL HAVE ACCESSIBLE HAND RAILS AND LANDINGS ON EACH END WITH A SLOPE IN ANY DIRECTIONNOT EXCEEDING 1:48 (1/4" PER FOOT OR NOMINALLY 2.0%).7. DOORWAYS SHALL HAVE A LANDING AREA ON THE EXTERIOR SIDE OF THE DOOR THAT IS SLOPED NOMORE THAN 1:48 (1/4" PER FOOT OR NOMINALLY 2.0%) FOR POSITIVE DRAINAGE. THIS LANDING AREASHALL BE NO LESS THAN 60 INCHES (5 FEET) LONG, EXCEPT HERE OTHERWSE PERMITTED BYACCESSIBILITY STANDARDS FOR ALTERNATIVE DOORWAY OPENING CONDITIONS AND APPROVED BYTHE OWNER'S REPRESENTATIVE.8. WHERE PEDESTRIAN ACCESS ROUTES ARE CONTAINED WITHIN A STREET OR HIGHWAYRIGHT-OF-WAY, THE GRADE OF THE PEDESTRIAN ACCESS ROUTE IS PERMITTED TO EQUAL THEGENERAL GRADE ESTABLISHED FOR THE ADJACENT STREET OR HIGHWAY, EXCEPT THAT WHEREPEDESTRIAN ACCESS ROUTES ARE CONTAINED WITHIN PEDESTRIAN STREET CROSSINGS A MAXIMUMGRADE OF 5 PERCENT IS REQUIRED. (EXCERPT FROM PROWAG)
drawn by:checkedby:printedname:reg. #:signdate:
date:project #:
signature:
2532303/10/2026JJBJFD
3/10/2026
Brule PublicWorksGarage
sheet title:sheetnumber:
revision / issueno.date
www.dsgw.com
G001SHEET INDEX ANDNOTESCIVIL SHEET INDEXG001SHEET INDEX AND NOTESG002CIVIL LEGENDS AND ABBREVIATIONSG003TOPOGRAPHIC SURVEYC050EXISTING CONDITIONS AND DEMOLITIONC100COMPOSITE SITE AND UTILITY PLANC110EROSION CONTROL AND GRADINGC111GRADING ENLARGMENTC300STORMWATER FACILITYC600EROSION CONTROL DETAILSC610SITE DETAILSC620SEWER DETAILS
FSFSWW
CULVERT - DRIVEWAYSTORM DETENTION (CAVFS)BERM
R/WESMTtuPROPOSED RIGHT OF WAYPROPOSED EASEMENTPROPOSED CURB AND GUTTERPHASE LINEPROPOSED PROPERTY LINECONSTRUCTION LIMITSPROPOSED CONTOUR- MINORPROPOSED CONTOUR- MAJOREXISTING BOUNDARY LINEEXISTING CONTOUR- MINOREXISTING CONTOUR- MAJORSITE PLAN
INLET / BEEHIVE CB
423420
FLARED END SECTION (FES)FLARED END SECTION WITH RIPRAPPROPOSED BUILDINGPROPOSED DRIVE LANE CENTERLINE
LANDSCAPE ISLANDLANDSCAPE STRIPTREE - DECIDUOUSSD >>>SD >>>DRAINTILE AND BUILDING DOWNSPOUT
STORM WATERPROPOSED CENTERLINE OF DITCH
WATERMAIN
STM >>>SD >>>
FM
PROPOSED STORM WATER
SANITARY SEWER FORCEMAIN
PROPOSED STORM SUBDRAIN
FIRE HYDRANT
*POWER AND GAS BY PUBLIC UTILITY PROVIDERSTREET LIGHTING
FIRE SERVICE WITH FDC
XXPROPOSED PROJECT BOUNDARYPROPOSED ROAD CENTERLINEPROPOSED FENCE
tuCONSTRUCTION LIMITS
THRUST BLOCK
WHITE BROKEN / SOLID
EXISTING PAVEMENT TO REMAINPROPOSED BITUMINOUS PAVEMENTCONCRETE PAVEMENTADA PARKING WITH CURB STOPADA CURB RAMPPARKING STALLS
TIME OF CONCENTRATION (LENGTH)CATCHMENT BOUNDARYCATCHMENT AREA LEGEND
PROPOSED SILT FENCEEROSION CONTROLSF
PROPOSED WATER MAIN - TRENCH
> SAN >PROPOSED SANITARY SEWERPROPOSED SANITARY SEWER SERVICEWITH CLEAN OUT> >CO
PROPOSED SERVICE WITH METERWATER METERBLOW OFF VALVE ASSEMBLY
|
W
SANITARY SEWER LIFT STATIONLSCO
W
UTILITY LEGENDWATER DEVICESSANITARY SEWER STRUCTURESWWPROPOSED WATER MAIN> SAN >PROPOSED SANITARY SEWERSTM >>>SD >>>PROPOSED STORM WATERPROPOSED STORM SUBDRAINSTORM WATER STRUCTURESLSCOW
423420
SANITARY SEWER CLEAN OUTSANITARY SEWER MANHOLE
STORM WATER CATCH BASINSTORM WATER CATCH BASIN MANHOLESTORM WATER MANHOLEINLET / BEEHIVE CBSTORM FACILITY
SANITARY SEWER
DRY UTILITIES
TREE - CONIFEROUS
COCLEAN OUT
METER PIT / VAULT
MJ CAPMJ WITH GATE VALVEMJ WITH REDUCERMJ WITH ADAPTERMJ WITH SLEEVE / COUPLINGMJ WITH CAPMJ WITH CAP AND BLOCKING
PLUGBLIND FLANGE
MJ WITH VERTICAL CROSS
RJ CAPRJ WITH GATE VALVERJ WITH REDUCERRJ WITH ADAPTERRJ WITH SLEEVE / COUPLINGRJ WITH CAPRJ WITH CAP AND BLOCKINGRJ WITH VERTICAL CROSSMJ x FL - GATE VALVEMJ X FL - REDUCERFL - VERTICAL CROSSFL - REDUCERFL - GATE VALVE
BLOW-OFF ASSEMBLY
TEE - MJTEE - MJ x FLTEE - FL x MJTEE - FLTEE - FL x RJTEE - RJ x FLTEE - RJTEE - MJ CUT INTEE - FL CUT INTEE - RJ CUT INCROSS - MJCROSS - MJ x FLCROSS - FL x MJCROSS - FLCROSS - FL x RJCROSS - RJ x FLCROSS - RJCROSS - MJ CUT INCROSS - FL CUT INCROSS - RJ CUT IN
TEES
CROSS
FL
MJRJ
HYDRANT WITH GATE VALVE AND TEE11.25 DEGREE BEND22.5 DEGREE BEND90 DEGREE BENDAIR RELEASE ASSEMBLY
MJ CHECK VALVE
WATERMAIN SYMBOLS
OEUEOTUTFOCATVGASGASOVERHEAD ELECTRICUNDERGROUND ELECTRICOVERHEAD TELEPHONEUNDERGROUND TELEPHONEFIBER OPTICCABLETELEVISIONGAS
GENERAL ABBREVIATIONSCCONCRETECBCATCH BASINCLCENTERLINECNSCOMPACTED NATIVE SOILCOCLEAN OUTCRCURB RETURNDDIRT / DRAINAGEEXSTEXISTINGFGFINISHED GRADEFHFIRE HYDRANTFLFLOW LINEFMFORCE MAINGNATURAL GAS (LOW PRESSURE)GBGRADE BREAKHPHIGH POINTLFLINEAR FOOTLPLOW POINTMGNATURAL GAS (MEDIUM PRESSURE)MGMATCH EXISTING GRADEMHMANHOLENSNATIVE SOILNTSNOT TO SCALEPCPOINT OF CURVATUREPOCPOINT OF CONNECTIONPOSPOINT OF SERVICEPPPOWER POLEPTPOINT OF TANGENCYPVPAVEMENTRRADIUSROWRIGHT OF WAYSSLOPE / SANITARYSANSEWER SEWERSDCO STORM DRAIN CLEANOUTSSMHSANITARY MANHOLESTASTATIONSTMSTORM DRAINSTMHSTORM MANHOLETBDTO BE DETERMINEDTBLTO BE RELOCATED BY RESPECTIVE UTILITYTBRTO BE REMOVED BY CONTRACTORTCTOP OF CURBTOETOE OF BANKTOPTOP OF BANKTPTELEPHONE POLEUUNDERGROUNDVIPVERIFY IN FIELD PRIOR TO CONSTRUCTIONWWATER MAIN
SITE - ABBREVIATIONSFFE - FIRST FLOOR FINISH ELEVATIONLLE - LOWER LEVEL FINISH ELEVATIONWO - WALKOUTLO - LOOKOUTGRADING LEGEND / ABBREVIATIONS TC: 391.49 FL: 390.99 TW: 391.49 BW: 380.99GB: GRADE BREAKLP: LOW POINTHP: HIGH POINTFC: FLUSH CURBMG: MATCH GRADEFL: FLOWLINESW: SIDEWALKPV: PAVEMENTTC: TOP OF CURBFG: FINISH GRADE (DEFAULT- IF NOT LABELED)
ACCESSIBLE ROUTE
TRASH ENCLOSUREGRDDRR
SIGN
STREET LIGHT
XXXXXXXXX GATEETELECTRICAL BOX / TRANSFORMER
XXXX
ETELECTRICAL TRANSFORMER
RIGHT / LEFT - TURN ARROW
DIRECTIONAL - TURN ARROWSTOP BARYELLOW DOUBLE SOLIDCROSS WALK
SHRUBSTREESTREE - CONIFEROUSTREE - CONIFEROUSTREE - CONIFEROUSTREE - CONIFEROUSTREE DECIDUOUSTREE DECIDUOUSTREE DECIDUOUSTREE DECIDUOUSTREE DECIDUOUSTREE DECIDUOUSTREE - GROUPSEED - SODSEED MIX - 1SEED MIX - 2SEED MIX - 3SOD
LANDSCAPE SYMBOLS
TREE DECIDUOUS
DEMOLITION
//////////////////////////////////////////////////////////////CURB & GUTTER REMOVALCONCRETE REMOVALUTILITY REMOVALBITUMINOUS REMOVALTREE - CONIFEROUS REMOVALTREE - DECIDUOUS REMOVALPIPECENTERLINECALCULATIONPIPECENTERLINECALCULATIONPIPECENTERLINECALCULATION
RIM ELEVATION
STRUCTURE REFERENCE LEGEND
CURB INLETYARD INLETMANHOLE
WATER LEVEL
GPECT
OOTREE PROTECTION FENCE
INLET PROTECTIONROCK CONSTRUCTION ENTRANCECONCRETE WASH OUT STATIONBMP C240OVERFLOW SEDIMENT TRAP (TYP). SEEECOLOGY STD DETAILS FIGURE II-4.2.16AND FIGURE II-4.2.17, SHEET ED1SEDIMENT BASIN (BMP)EROSION BLANKETSBSOIL BORINGtuCONSTRUCTION LIMITSPROPOSED SILT FENCE (HEAVY DUTY)SSFBIO ROLLFLOW ARROW
THRUST BLOCK
STM >>>
SAWCUTBUILDING REMOVAL
HYDRANT COVERAGE
DOUBLE CHECK VALVE ASSEMBLY
BARRICADE
EXISTING WATER MAIN - ABANDONEDPROPOSED WATER MAIN - HDDPROPOSED WATER MAIN - BURSTINGWWW - AB
drawn by:checkedby:printedname:reg. #:signdate:
date:project #:
signature:
2532303/10/2026JJBJFD
3/10/2026
Brule PublicWorksGarage
sheet title:sheetnumber:
revision / issueno.date
www.dsgw.com
G002CIVIL LEGENDS ANDABBREVIATIONS
drawn by:checkedby:printedname:reg. #:signdate:
date:project #:
signature:
2532303/10/2026JJBJFD
3/10/2026
Brule PublicWorksGarage
sheet title:sheetnumber:
revision / issueno.date
www.dsgw.com
G003TOPOGRAPHICSURVEY
1061106210631064106510661067106810691070
1071
107210731074107510761077
1078107910801081108210831084108510861087108810891090109110921093
1067106810691070
107110711071
10721073107410751076107710781079
T
T
COMMCOMM
COMM
COMM
COMM
COMMCOMM
COMMUGEUGEUGEUGE
UGEUGEUGEUGE
S
S
SANSANSAN
SANSAN.MHRIM ELEV. = 1,077.96APPROX IE = 1,064.96(TO BE FIELD VERIFIED)
SAN.MHRIM ELEV. = 1,069.35APPROX. IE = 1058.35(TO BE FIELD VERIFIED)
drawn by:checkedby:printedname:reg. #:signdate:
date:project #:
signature:
2532303/10/2026JJBJFD
3/10/2026
Brule PublicWorksGarage
sheet title:sheetnumber:
revision / issueno.date
www.dsgw.com
CONTRACTOR NOTE:ALL EXISTING UTILITIES SHOWN ON PLANS ARE TO BE VERIFIED HORIZONTALLY ANDVERTICALLY PRIOR TO ANY CONSTRUCTION. ALL EXISTING FEATURES INCLUDINGBURIED UTILITIES ARE SHOWN AS INDICATED ON RECORD MAPS AND SURVEYSFURNISHED BY OTHERS. WINDSOR ASSUMES NO LIABILITY FOR THE ACCURACY OFTHOSE RECORDS AND SURVEYS. CONTACT THE UTILITY OWNER/AGENCY FOR THEFINAL LOCATION OF EXISTING UTILITIES IN AREAS CRITICAL TO CONSTRUCTION.
040'80' C050EXISTINGCONDITIONS ANDDEMOLITION
SITE PLAN LEGENDCLEARING & GRUBBING (AREA ESTIMATEDAND MAY DIFFER THAN AREAPREVIOUSLY CLEARED)UTILITY TRENCHING
EXISTING CONDITIONS AND DEMOLITION PLANSCALE: 1:40
DUMP ROAD
OLD HIGHWAY 2
HILL ROAD
3C620
EXISTING UNDERGROUNDUTILITIES TO REMAINCOMMUNICATIONUTILITIES TO REMAIN
EXISTING TELECOMMUNICATIONEQUIPMENT TO REMAIN
SAWCUT FULLDEPTH OF ASPHALT5.0'17.5'
> >> >> >> >> >> >> >> >> >> >> >> >> >
||||
COCO
SD >>>
UEUEUEUEUEGASGASGASGASGASGASGASGASGASGASGAS
TCOMMCOMM
COMM
COMM
COMM
COMMUGEUGEUGE
UGE
UGE
UGE
S
S
SANSANSAN
SAN
SAN.MHRIM ELEV. = 1,077.96APPROX IE = 1,064.96(TO BE FIELD VERIFIED)
SAN.MHRIM ELEV. = 1,069.35APPROX. IE = 1058.35(TO BE FIELD VERIFIED)
72.6'
50.0'32.0'
127.8'
182.1'
PROPOSED UNDERGROUND ELECTRIC SEEELECTRICAL PLANS FOR DETAILS
PROPOSED GAS CONNECTION SEE PLUMBINGPLANS FOR DETAILSAPPROXIMATE GAS TIE IN LOCATION.CONTRACTOR TO FIELD VERIFY EXACT GASLOCATION
106.1'21.1'R20.0'R20.0'R10.0'R30.0'R30.0'R10.0'35.0'
drawn by:checkedby:printedname:reg. #:signdate:
date:project #:
signature:
2532303/10/2026JJBJFD
3/10/2026
Brule PublicWorksGarage
sheet title:sheetnumber:
revision / issueno.date
www.dsgw.com
030'60'
CONTRACTOR NOTE:ALL EXISTING UTILITIES SHOWN ON PLANS ARE TO BE VERIFIEDHORIZONTALLY AND VERTICALLY PRIOR TO ANY CONSTRUCTION. ALLEXISTING FEATURES INCLUDING BURIED UTILITIES ARE SHOWN ASINDICATED ON RECORD MAPS AND SURVEYS FURNISHED BY OTHERS.WINDSOR ASSUMES NO LIABILITY FOR THE ACCURACY OF THOSE RECORDSAND SURVEYS. CONTACT THE UTILITY OWNER/AGENCY FOR THE FINALLOCATION OF EXISTING UTILITIES IN AREAS CRITICAL TO CONSTRUCTION.SITE PLAN LEGENDGRAVEL SECTION - DRIVEWAY ANDPARKING LOTCONCRETE SIDEWALKCONCRETE - HEAVY DUTYSTORM FACILITYASPHALT PAVEMENTHYDROSEED REPAIR
C100SITE ANDCOMPOSITEUTILITY PLANSITE AND COMPOSITE UTILITY PLANSCALE: 1:30
100 SITE PLAN100WHEEL STOP101ACCESSIBLE PARKING STALL102LIGHT RIP-RAP103MEDIUM RIP-RAP
400 SANITARY SEWER400PROPOSED 6" HDPE SANITARY SERVICE LINE(MINIMUM SLOPE OF 1/8" PER FOOT)401PROPOSED 6" SANITARY CLEANOUT402TIE INTO EXISTING SEWER MAINAPPROX. INVERT ELEV: 1060.65CONTRACTOR TO FIELD VERIFY MAIN DEPTH AND NOTIFY ENGINEERIMMEDIATELY IF INVERT DIFFERS403SEWER SERVICE CONNECTION TO BUILDINGINVERT ELEV: 1,067.00500 WATER5002" PVC WATER LINE SERVICE501PROPOSED WELL502CONNECT WATER SERVICE LINE TO BUILDINGINVERT ELEV: 1,067.00
501500400 502403402 401
300
3019.0'
1C610
PRPOSEDBLDGSEE ARCHPLANS
100
304
DUMP ROAD
OLD HIGHWAY 2
HILL ROAD101
300 STORM300PROPOSED STORMWATER INFILTRATION FACILITY 1003 PER WISCONSIN DNRTECHINCAL STDS301PROPOSED STORMWATER VEGETATED SWALEMINIMUM SLOPE OF 0.5%302NOT USED303OVERFLOW WEIR WITH 2' WIDE CREST AND 4:1 SIDE SLOPESSEE SHEET C3003042.5' TALL 2' WIDE BERM305NOT USED306BUILDING FOUNDATION DRAIN TO DAYLIGHT TO STORMWATER FACILITY
3C610
1C620
1C300
6C610
4C610
102102
103
301
301
2C300
2C620
303
15.5'20.0'
20.0'
65.0'80.0'
3C3004C300
401
1C6105C610
1C300
7C610
5.0'5.0'5.0'
4C600
306
TCOMMCOMM
COMM
COMM
COMMUGEUGEUGE
UGE
UGE
> >> >> >> >> >> >> >> >> >> >
|||||||
COCO
SD >>>
UEUEUEUEUEUEUEUEGASGASGASGASGASGASGASGASGASGAS
1070
1071
1072
10731074
1075107610771078
1071
1072
1073
1074
10751076107710781074
GRADE BREAK
1.51%1.74%
1.51%
1.00%1.50%
5.58%
3.87%
4.59%
1.92%
1.99%
2.52%
1.99%
8.95%2.59%2.28%
SFSFSFSFSFSFSFSFSFSFSFSFSFSFSFSFSFSFSFSFSFSFSFSFSFSFSFSFSFSFSFSFSFSFSFSFSFSFSFSFSFSFSFSFSFSFSFSFSFSFSF
4:14:15:1 6:1
3:1
4:1
5.17%
6.99%
10:16:1
3.21%8.83%2.44%4:1
106910691070
10701071107110711072107210721073 107110721073
10691070107010711071
107010711071
10701070107110711071
107110711072107310741075107510761076
1070107010711071107110711072 10731073 1073
10701070107110711072 1072107210731073
1073107410751076107710781078
0.07%
1071.421071.521071.621071.71
1071.101073.281073.501073.501073.281073.20
1073.021073.411073.501073.501073.411073.421073.42
1073.411072.991072.05
1072.22
1076.87
1074.93
1073.14
1071.88
1073.39
1070.551070.43 1071.49
1070.001069.871069.82
1069.20
1069.47
1072.561072.44
1071.79
1071.26
1069.231069.601069.731069.871069.921070.08
1071.42
1072.86
11.06%1069.201071.201071.321071.47
1071.562.98%
1071.59
1072.111072.44
1071.35
4:14:1
4:1
4:1
9.06%5:1
3:14:1 1.49%
1070.05
6:1
3.93%
3.73%
1071.52
19.29%17.1'24.1' 30.0'11.0'17.0'11.0'
0.00%
2.68%
2.45%
GRADE BREAK
25.51%
PROPOSED WELL
1069.101069.05
7.39%3.58%
GRADE BREAK
1073.60
1071.771073.33RIDGE LINE
1071.461072.011071.80
1060
1070
1080
1090
1060
1070
1080
1090
0+251071.31070.460+501071.41072.73
3:1 MAX3:1 MAX
1060
1070
1080
1090
1060
1070
1080
1090
0+251075.41077.620+501074.61071.11
VARIABLE SLOPE3:1 MAX3:1 MAX
drawn by:checkedby:printedname:reg. #:signdate:
date:project #:
signature:
2532303/10/2026JJBJFD
3/10/2026
Brule PublicWorksGarage
sheet title:sheetnumber:
revision / issueno.date
www.dsgw.comEROSION CONTROL LEGENDPROPOSED SILT FENCECONCRETE WASHOUTROCK CONSTRUCTION ENTRANCESF
CONTRACTOR NOTE:ALL EXISTING UTILITIES SHOWN ON PLANS ARE TO BE VERIFIED HORIZONTALLY ANDVERTICALLY PRIOR TO ANY CONSTRUCTION. ALL EXISTING FEATURES INCLUDINGBURIED UTILITIES ARE SHOWN AS INDICATED ON RECORD MAPS AND SURVEYSFURNISHED BY OTHERS. WINDSOR ASSUMES NO LIABILITY FOR THE ACCURACY OFTHOSE RECORDS AND SURVEYS. CONTACT THE UTILITY OWNER/AGENCY FOR THEFINAL LOCATION OF EXISTING UTILITIES IN AREAS CRITICAL TO CONSTRUCTION.
C110EROSIONCONTROL ANDGRADING020'40'EROSION CONTROL AND GRADING PLANSCALE: 1:20
CONCRETE TRUCK WASHOUT
CONSTRUCTION ENTRANCEBOTTOM OFSWALE DITCH
DUMP ROAD
OLD HIGHWAY 2
1C600
PROPOSED BLDGFFE: 1073.50
1C110
SILT FENCE (TYP)
TOP OF PROPOSED BERM
SWALE DITCH
BOTTOM OF SWALE2C110
2.5' PROPOSED BERM
PROPOSED SWALEW/ 2' BOTTOM WIDTHEXISTING GRADEPROPOSED GRADE
PROPOSED SWALEW/ 2' BOTTOM WIDTHEXISTING GRADEPROPOSED GRADESTART OF BUILDINGFFE = 1073.50TOP OF SWALE
35.0'50.0'
1C111
2C6003C600
SILT FENCE (TYP)
ESTIMATED CUT / FILL SUMMARYCUTFILLNET1,048 CY4,454 CY3,410 CY1. ACCOUNTS FOR 15% FILL COMPACTION2. DOES NOT ESTIMATE STRUCTURAL FILL REQUIRED FOR BUILDING3. DOES NOT ESTIMATE THE AGGREGATE AND PAVING REQUIRED FOR PARKING AREA4. INCLUDES 12" OF STRIPPING OVER THE ENTIRE SITE
1NORTH CROSS SECTIONHORIZONTAL SCALE: 1:10 VERTICAL SCALE 1:5
2WEST CROSS SECTIONHORIZONTAL SCALE: 1:10 VERTICAL SCALE 1:5
BOTTOM OF PONDEL = 1068.40
20.0'9.0'5.0'
1073.201073.12
1073.121073.42
1073.16
1073.16
1073.431073.16
1073.421.33%1.33%
1.33%
1.33%
0.00%
drawn by:checkedby:printedname:reg. #:signdate:
date:project #:
signature:
2532303/10/2026JJBJFD
3/10/2026
Brule PublicWorksGarage
sheet title:sheetnumber:
revision / issueno.date
www.dsgw.com
CONTRACTOR NOTE:ALL EXISTING UTILITIES SHOWN ON PLANS ARE TO BE VERIFIED HORIZONTALLY ANDVERTICALLY PRIOR TO ANY CONSTRUCTION. ALL EXISTING FEATURES INCLUDINGBURIED UTILITIES ARE SHOWN AS INDICATED ON RECORD MAPS AND SURVEYSFURNISHED BY OTHERS. WINDSOR ASSUMES NO LIABILITY FOR THE ACCURACY OFTHOSE RECORDS AND SURVEYS. CONTACT THE UTILITY OWNER/AGENCY FOR THEFINAL LOCATION OF EXISTING UTILITIES IN AREAS CRITICAL TO CONSTRUCTION.
C111GRADINGENLARGMENT
04'8'ADA ENLARGEMENT PLAN - 1SCALE: 1:4
TCOMMCOMMUGEUGE
> >> >> >> >> >> >> >> >> >> >> >> >
||||||
COCO
SD >>>
UEUEUEUEUEUEUEUEGASGASGASGASGASGASGASGASGASGASGAS 1071
1072
10701070
1070
10701070
10701071
10711071
1071
107110711071
1072
1072
1072
1073 1073
65.0'80.0'6:1
4:1
4:14:1
1071
1072
1066
106710681069
1070
1071
10661067106810691070
1071
1072
1069
106910701070
10701071
10711071
1072
106910701071107124.1'17.1'
drawn by:checkedby:printedname:reg. #:signdate:
date:project #:
signature:
2532303/10/2026JJBJFD
3/10/2026
Brule PublicWorksGarage
sheet title:sheetnumber:
revision / issueno.date
www.dsgw.comCONTRACTOR NOTE:ALL EXISTING UTILITIES SHOWN ON PLANS ARE TO BE VERIFIED HORIZONTALLY ANDVERTICALLY PRIOR TO ANY CONSTRUCTION. ALL EXISTING FEATURES INCLUDINGBURIED UTILITIES ARE SHOWN AS INDICATED ON RECORD MAPS AND SURVEYSFURNISHED BY OTHERS. WINDSOR ASSUMES NO LIABILITY FOR THE ACCURACY OFTHOSE RECORDS AND SURVEYS. CONTACT THE UTILITY OWNER/AGENCY FOR THEFINAL LOCATION OF EXISTING UTILITIES IN AREAS CRITICAL TO CONSTRUCTION.
C300STORMWATERFACILITY
020'40'
OLD HIGHWAY 2
NOTES:1.SIZE OF MATERIAL TO BE RIP-RAP PER WISCONSIN DOT STANDARDSPECIFICATIONS - SECTION 606.2.THE CONTRACTOR MAY PLACE HEAVY RIPRAP BY MECHANICAL MEANS.LIMIT HANDWORK TO THE QUANTITY NECESSARY TO FILL LARGE VOIDSOR TO CORRECT SEGREGATED AREAS. IF PLACING RIPRAP OVERGEOTEXTILE, USE TYPE HR AND CONFORM TO 645.3.1.7.3.UNLESS SPECIFIED OTHERWISE MAKE HEAVY RIPRAP AT LEAST 24INCHES THICK.
MEDIUMRIP-RAPSEE PLAN
SEE PLAN
PROPOSED OVERFLOW WEIRSEE DETAIL 22OVERFLOW WEIRSCALE: NTS
1STORMWATER FACILITYSCALE: 1"-20' 3MEDIUM RIP-RAPSCALE: NTS
2.0'3:13:1100-YEAR WSEELEV: 1070.19TOP OF OVERFLOW WEIRELEV: 1071.15BOTTOM OF OVERFLOW WEIRELEV: 1069.30
SEE PLAN
PROPOSED MEDIUM RIP-RAPFOR EROSION CONTROL
11.0'30.0'17.0'11.0'
NOTES:1.SIZE OF MATERIAL TO BE RIP-RAP PER WISCONSIN DOT STANDARDSPECIFICATIONS - SECTION 606.2.IF LAYING STONE ABOVE THE WATERLINE, PLACE IT BY HAND. LAY ITWITH CLOSE, BROKEN JOINTS AND FIRMLY BED IT IN THE SLOPE ANDAGAINST THE ADJOINING STONES. LAY THE STONES PERPENDICULAR TOTHE SLOPE WITH ENDS IN CONTACT. COMPACT THE RIPRAPTHOROUGHLY AS CONSTRUCTION PROGRESSES. MAKE THE FINISHEDSURFACE EVEN AND TIGHT. PLACE LARGER STONE IN LOWER COURSES.CHINK SPACES BETWEEN STONES BY FIRMLY RAMMING SPALLS INTOPLACE. IF PLACING RIPRAP OVER GEOTEXTILE, USE TYPE R ANDCONFORM TO 645.3.1.6.3.UNLESS SPECIFIED OTHERWISE, MAKE RIPRAP AT LEAST 12 INCHESTHICK, MEASURED PERPENDICULAR TO THE SLOPE.4.DO NOT PLACE RIPRAP AGAINST, OR IN CONTACT WITH, CONCRETESURFACE BEFORE THE END OF THE CONCRETE’S CURING ANDPROTECTION PERIOD.
LIGHT RIP-RAPSIZE AND SLOPE(SEE PLAN)SEE PLANS
SEE PLANSOVERFLOW WEIR
4LIGHT RIP-RAPSCALE: NTS
VEGETATED SWALE
POND BOTTOMELEV: 1068.40TOP OF PONDELEV: 1071.15
1C300 1STORMWATER FACILITY CROSS SECTIONSCALE: NTS
STORMWATER FACILITY VEGATATION NOTES:NATIVE VEGETATION SHALL BE ESTABLISHED IN CONFORMANCE WITH RECOMMENDATIONSFROM A QUALIFIED NATIVE NURSERY IN THE AREA. IF TREES ARE TO BE USED, SPECIESSHALL BE SELECTED THAT WILL NOT INTERFERE WITH THE FUNCTION OF THE BASIN, ORCAUSE MAINTENANCE PROBLEMS.THE FOLLOWING SOURCES CAN BE USED FOR NATIVE SEED MIXTURES OR APPROVED EQUAL:·METROPOLITAN COUNCIL, 2003. URBAN SMALL SITES BEST MANAGEMENT PRACTICEMANUAL, CHAPTER 3, VEGETATIVE METHODS 3-85 – 3-91. MINNEAPOLIS.·UNITED STATES DEPARTMENT OF AGRICULTURE – NATURAL RESOURCESCONSERVATION SERVICE. ENGINEERING FIELD HANDBOOK, CHAPTERS 16 AND 18.·UWEX PUBLICATION A3434 LAWN AND ESTABLISHMENT & RENOVATION.·WISDOT, 2003. STATE OF WISCONSIN STANDARD SPECIFICATIONS FOR HIGHWAY ANDSTRUCTURE CONSTRUCTION. SECTION 630, SEEDING
BTM POND EL = 1068.40
SWALE OUTFLOWTO PONDEL = 1069.20
SWALE OUTFLOWTO PONDEL = 1069.20
PROPOSED GRADEEX GRADETOP OF FACILITYEL = 1071.20MIN. 1' 70% SAND / 30% COMPOST LAYER. SANDTO MEET USDA COARSE, ASTM C33, ORAPPROVED EQUAL. COMPOST TO MEET WI DNRSPEC S100. SAND AND COMPOST TO BE WILLMIXED PRIOR TO PLACEMENT.
AVOID COMPACTION OF NATIVE SOIL BY LIMITINGCONSTRUCTION ACTIVITIES IN INFILTRATIONFACILITY. TRACKED EQUIPMENT TO BE USED WHENNECESSARY. TOP 3" OF NATIVE SOIL TO BESCARIFIED BEFORE PLACING SAND/COMPOSTLAYER.SEED BOTTOM OF FACILITY ANDINTERNAL/EXTERNAL SIDE SLOPES WITHNATIVE GRASSES IN FALL AS DORMANTSEEDS OR SPRING (MAY 1 TO JUNE 20). IFOUTSIDE THOSE WINDOWS, PLUGS SHALL BEUSED.FILL AS NEEDED TOACHIEVE FINAL GRADE (TYP)MEDIUM RIP-RIPPER DETAILOVERFLOW WEIREL = 1069.30
1C300
drawn by:checkedby:printedname:reg. #:signdate:
date:project #:
signature:
2532303/10/2026JJBJFD
3/10/2026
Brule PublicWorksGarage
sheet title:sheetnumber:
revision / issueno.date
www.dsgw.com
EROSIONCONTROLDETAILS
C600
1TRACKING PAD DETAILSCALE: NO SCALE
QUARY SPALLS, 1.0' D
COMPACTED BACKFILL CONSISTING OFBANK RUN GRAVEL FOR TRENCH BACKFILLCOMPACTED TO 95% MODIFIED PROCTOR
4'-0" MIN SEE PLANS
6" DEPTH STRIPPINGS FROM ON-SITEHYDROSEED "GROUND COVER" PER SPECIFICATIONS12" 12"
2SILT FENCESCALE: NTS
3CONCRETE WASHOUT DETAILSCALE: NTS4HYDROSEED REPAIR DETAILSCALE: NTS
drawn by:checkedby:printedname:reg. #:signdate:
date:project #:
signature:
2532303/10/2026JJBJFD
3/10/2026
Brule PublicWorksGarage
sheet title:sheetnumber:
revision / issueno.date
www.dsgw.com
C610SITE DETAILS
6" GRAVEL FINISH12" GRADED BASE COURSE3/4" DENSE GRADED BASE PER WISDOT SPECSECTION 305COMPACTED SUB-GRADE APPROVED BYGEOTECHNOTES:1. PRIOR TO PLACING ANY ADDITIONAL FILL FOR PAVEMENT SECTION CONSTRUCTION,THE UPPER 12 INCHES OF NATIVE SUBGRADE SHOULD BE THOROUGHLY WATERCONDITIONED TO WITHIN 2% OF THE OPTIMUM WATER CONTENT AND RECOMPACTEDTO A MINIMUM 95% OF THE MAXIMUM D698 DRY DENSITY.2. GRAVEL DRIVE AREAS MAY REQUIRE ADDITIONAL AGGREGATE BASE TO BE PLACEDAND ROUTINE MAINTENANCE3. CONTRACTOR TO PROOF ROLL OR PROVIDE OTHER ACCEPTED MEANS BYGEOTECH TO DEMONSTRATE THAT COMPACTIONS ARE ACHIEVED.
12" COMPACTED SUB-BASE
2' - 0"
9' - 0" MIN.9' - 0" MIN.5' - 0" MIN.2' - 0"20' - 0"2' - 0"45^ONE ACCESSIBLE STALL90° PARKING STALL ARRANGEMENTPLAN
R7-801
R7-801R7-801A
NOTES:1. AN ACCESS PARKING SPACE SYMBOL IS REQUIRED FOR EACH ACCESSIBLE PARKING STALL. A BLUEBACKGROUND AND WHITE BORDER ARE REQUIRED WHEN THE SYMBOL IS INSTALLED ON A CEMENTCON-CRETE SURFACE.2. ALL ACCESSIBLE STALLS SHALL HAVE WHEEL STOPS. PLACE WHEEL STOPS IN OTHER STALLS WHENSPECI-FIED IN THE CONTRACT. WHEEL STOPS SHALL BE APPROXIMATELY 6" HIGH AND A MINIMUM OF 6'LONG.LEGEND:RESERVED PARKING SIGN AND POSTWITH PLAQUE, IF INDICATED(SEE SIGN FABRICATION MANUAL)ACCESS PARKING SPACE SYMBOLMANUFACTURED WHEEL STOP
4" WIDE, WHITEPAINT LINE (TYP)4" WIDE, YELLOWPAINT LINES
TRANSITIONBETWEEN WALK ANDAISLE PER PLANCEMENT CONCRETESIDEWALK PER PLAN
5.0
2.00.5
2"x2" PERFORATEDSIGN POSTCONCRETE BASESLOPE TO DRAINCHAMFER EDGESPAVEMENTSECTIONSIDEWALKSECTION1.5
RESERVED PARKINGWISDOT R7-8AVAN ACCESSIBLEWISDOT R7-8V
1PARKING LOT SECTION VIEWSSCALE: NO SCALE2ADA PARKING STALL DETAILSCALE: NO SCALE3ADA PARKING STALL SIGN DETAILSCALE: NO SCALE
GRAVEL SECTION - DRIVEWAY AND PARKING LOT
7" CONCRETE6" GRADED BASE COURSE3/4" DENSE GRADED BASE PER WISDOT SPECSECTION 305COMPACTED SUB-GRADEAPPROVED BY GEOTECH12" COMPACTED SUB-BASECONCRETE SECTION - HEAVY DUTY
28" MIN /41" MAX24" MIN /36" MAXADA PARKING MARKING
WHITE PAINT
NOTES:1.SEE THE MILLENNIUM EDITION OFMUTCD FIGURE 3B-18 FORADDITIONAL PARKING INFORMATION.℄1313
1.5' (MIN)EXISTINGGROUNDFILL AREA (PERPLANS)
COMPACTED SUBGRADE , 95% AASHTOT-99 PROCTOR DENSITYNOTES1.ALL MEASUREMENTS SHOWN ARE COMPACTED DEPTHS UNLESS OTHERWISE NOTED.MINIMUM DEPTH1.50'2'
NOTES:1.CONCRETE SHALL BE 3000 PSI MIN. (CL 3000), 3 1/2" SUMP (MAX.).2.COMPACT SUBGRADE AND CRUSH SURFACING TOP COURSE TO 95% OF MAXIMUM DRYDENSITY (3" MIN. DEPTH).3.FINISH SHALL BE MEDIUM BROOM PERPENDICULAR TO PEDESTRIAN TRAFFIC UNLESSOTHERWISE DIRECTED.4.2" SMOOTH FINISH BORDER AROUND EACH SIDEWALK PANEL OR MATCH EXISTING BORDER.5.ALL EXISTING EDGES SHALL BE SAWCUT.6.CROSS SLOPE OF PLANTER STRIP SHALL BE 2% (TYP.) AND 4:1 (MAX.).7.ALL SIDEWALK REMOVAL AND REPLACEMENT SHALL BE JOINT TO JOINT.8.SIDEWALK REPLACEMENT AREAS SHALL BE ROCKED LEVEL AND COMPACTED UNTILCONCRETE IS PLACED.9.FIRE HYDRANT OR WATER METER BOX SHALL NOT BE WITHIN THE SIDEWALK.
NOMINAL JOINT SPACING:SURFACE JOINT AT 5'.CONTRACTION JOINT AT 15'.EXPANSION JOINT ATSTRUCTURES, OBSTRUCTION, ORAS DIRECTED BY THE INSPECTOR.EXPANSION JOINTW1/2" DEEP SURFACECONTRACTION JOINTW5'-0'' MIN.WWWCONTRACTION JOINTEXPANSION JOINT4" (TYP.)SURFACE JOINT (TYP.)4" CL3000 CONCRETE3" MIN. SURFACINGTOP COURSE
8" MIN,10" MAX2 12" 4"3:1 SAND AND CEMENTGROUT 1" DEPTHNON-SHRINK GROUT24" MIN
9" 6'-0"1/2" DIA. HOLES
(2) #3 BARS(2) #4 BARS
6"2" CLR (TYP)
ATTACHMENTDETAILEND VIEW
PLAN VIEWSIDE VIEW1.REFER TO PLAN FOR LOCATION OF WHEEL STOPS.2.OFFSET REQUIRED BETWEEN CURB AND WHEEL STOP IS 1'-10".3.WHEEL STOPS SHALL BE FLOW THROUGH TYPE.NOTES
4VEGETATED SWALE DETAILSCALE: NTS
5SIDEWALK SECTIONSCALE: NTS6WHEEL STOP DETAILSCALE: NTS2" DEPTH CSTC4" DEPTH CSBCCOMPACTED BACKFILL CONSISTINGOF BANK RUN GRAVEL FORTRENCH BACKFILL COMPACTED TO95% MODIFIED PROCTOR
HMA REPAIR LIMITWATER: 6' MAXSEWER: 8' MAX
3" COMPACTED THICKNESS,HMA CLASS 1/2" PG 58H-22NTSHMA REPAIR7
12"
drawn by:checkedby:printedname:reg. #:signdate:
date:project #:
signature:
2532303/10/2026JJBJFD
3/10/2026
Brule PublicWorksGarage
sheet title:sheetnumber:
revision / issueno.date
www.dsgw.com
SEWER DETAILSC620
1TYPICAL SEWER SERVICE DETAILSCALE: NO SCALE2SEWER CLEANOUT DETAILSCALE: NO SCALE
4"6"8"RISER PIPE SIZECASTING (NEENAH OR APPROVED EQUAL)R - 1973-1R - 1974AR - 1975A
END OF LINE CLEANOUTIN LINE CLEANOUTCASTING, SEE TABLEPVC THREADED PLUG3" BELOW CASTINGLONG SWEEP BEND,PVC SDR-35 ORACCEPTED EQUALCOMBINATION WYE,PVC SDR-35 ORACCEPTED EQUALENCASE LONG SWEEP BEND ORCOMBINATION WYE IN CONCRETE.(1/3 CU. YD. MINIMUM)
SCH 40 PVC RISER(MATCH HORIZONTALPIPE SIZE)1/8" PER FOOTMINIMUM SLOPE
3UTILITY TRENCHINGSCALE: NTS
3/4" DENSE GRADED BASEPER WISDOT SPEC 305 WARNING TAPELOCATE WIREUTILITY PIPE6" BEDDINGSAND OR NATIVEGRANULAR
1.5'1.5'3.0'MIN
PAVEMENT SECTIONPAVED AREASOUT OF PAVED AREASLANDSCAPED SECTION
GENERAL
ALL TYPICAL DETAILS AND NOTES SHOWN ON DRAWINGS SHALL APPLY
UNLESS NOTED OTHERWISE. TYPICAL DETAILS MAY NOT NECESSARILY BE
INDICATED ON THE PLANS BUT SHALL STILL APPLY AS SHOWN OR
DESCRIBED IN THE DETAILS. WHERE TYPICAL DETAILS ARE NOTED ON
THE DRAWINGS, THE SPECIFIED TYPICAL DETAIL SHALL BE USED. WHERE
NO DETAIL IS NOTED, IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY
TO CHOOSE THE APPROPRIATE TYPICAL DETAIL FROM THOSE PROVIDED.
THE CONTRACTOR SHALL SUBMIT ALL PROPOSED ALTERNATE TYPICAL
DETAILS TO THOSE PROVIDED WITH RELATED CALCULATIONS TO THE
ENGINEER FOR APPROVAL PRIOR TO SHOP DRAWING PRODUCTION AND
FIELD USE.
BUILDING CODE
ALL CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE BUILDING
CODE. THE PUBLICATIONS LISTED BELOW ARE THE GOVERNING CODES
AND STANDARDS AND ARE REFERENCED BY THEIR BASIC DESIGNATION.
IN THE CASE OF CONFLICTING REQUIREMENTS, THE BUILDING CODE
SHALL GOVERN.
APPLICABLE CODES AND STANDARDS
BUILDING CODE INTERNATIONAL BUILDING CODE (IBC), 20 21 EDITION,
INCLUDING ADDITIONS PER THE 2025 WISCONSIN
COMMERCIAL BUILDING CODE
ACI 318 AMERICAN CONCRETE INSTITUTE, "BUILDING CODE
REQUIREMENTS FOR STRUCTURAL CONCRETE "
2019 EDITION
AISC AMERICAN INSTITUTE OF STEEL CONSTRUCTION, "STE EL
CONSTRUCTION MANUAL”, 2016 EDITION
AISC 360 AMERICAN INSTITUTE OF STEEL CONSTRUCTION,
"SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS”,
2016 EDITION
AISI S100 AMERICAN IRON AND STEEL INSTITUTE, "NORTH
AMERICAN SPECIFICATION FOR THE DESIGN OF COLD-
FORMED STEEL STRUCTURAL MEMBERS", 2016(2020)
EDITION W/ S2 - 20
ASCE 7 AMERICAN SOCIETY OF CIVIL ENGINEERS, "MINIMU M
DESIGN LOADS FOR BUILDINGS AND OTHER
STRUCTURES", 2016 EDITION
ASTM AMERICAN SOCIETY FOR TESTING AND MATERIALS
(ASTM INTERNATIONAL)
AWS A2.4 AMERICAN WELDING SOCIETY, "SYMBOLS FOR WEL DING
AND NONDESTRUCTIVE TESTING”, 2018 EDITION
AWS D1.1 AMERICAN WELDING SOCIETY, "STRUCTURAL WELD ING
CODE – STEEL," CURRENT EDITION PER IBC
AWS D1.3 AMERICAN WELDING SOCIETY, "STRUCTURAL WELD ING
CODE – SHEET STEEL", CURRENT EDITION PER IBC
AWC SDPWS SPECIAL DESIGN PROVISIONS FOR WIND AND SE ISMIC
(SDPWS), 2021 EDITION
ICC INTERNATIONAL CODE COUNCIL, INTERNATIONAL CODE
COUNCIL - EVALUATION SERVICES (ICC-ES)
STRUCTURAL DESIGN DATA
LOAD COMBINATIONS
LOAD COMBINATIONS ARE IN ACCORDANCE WITH SECTION 1605 OF THE
BUILDING CODE.
LIVE LOADS
LIVE LOADS SHALL BE IN ACCORDANCE WITH THE BUILDING CODE
(SECTION 1607) OR AS NOTED ON THE PLANS.
OFFICE: LL = 50 PSF + 15 PSF PARTITIONS
EQUIPMENT PLATFORM (Non-Occupied) LL = 125 PSF
APPARATUS BAYS = 500 PSF
COLLATERAL ROOF LOAD = 5 PSF
SNOW LOADS
SNOW LOADING AND SNOW DRIFT LOADING SHALL BE IN ACCORDANCE
WITH THE BUILDING CODE (SECTION 1608).
GROUND SNOW LOAD: Pg = 60 PSF
IMPORTANCE FACTOR: Is = 1.0
SNOW EXPOSURE FACTOR: Ce = 1.0
THERMAL FACTOR: Ct = 1.0
FLAT-ROOF SNOW LOAD: Pf = 42 PSF
WIND LOADS
WIND PRESSURE SHALL BE IN ACCORDANCE WITH THE BUILDING CODE
(SECTION 1609).
BASIC WIND SPEED: V_ult = 106 MPH (3-SECOND GUST)
V_asd = 85 MPH (3-SECOND GUST)
RISK CATEGORY: III
EXPOSURE: C
ENCLOSURE CLASSIFICATION: ENCLOSED
INT. PRESSURE COEFFICIENT: GCpi = 0.18
SEISMIC LOADS
SEISMIC LOADING SHALL BE IN ACCORDANCE WITH THE BUILDING CODE
(SECTION 1613).
BUILDING LOCATION: LATITUDE = 46.555
oN
LONGITUDE = -91.568 oW
RISK / OCCUPANCY CATEGORY: II
IMPORTANCE FACTOR: I E = 1.0
SITE CLASS: D
MAPPED SPECTRAL ACCELERATION PARAMETERS: S
S = 0.041g
S 1 = 0.016g
SPECTRAL RESPONSE COEFFICIENTS: SDS = 0.0437g
S D1 = 0.0256g
SEISMIC DESIGN CATEGORY: A
LOAD PATH FOR LATERAL FORCES
LATERAL FORCES ARE CARRIED BY THE PRE-ENGINEERED STEEL
LATERAL SYSTEM, MOMENT FRAMES, ETC. MOMENTS, SHEARS, AND
ROTATIONAL FORCES ARE DELIVERED TO THE FOUNDATION BY THE,
MOMENT FRAMES, ETC.
CONCRETE
1. MIXING, BATCHING, TRANSPORTING, PLACING, AND CURING OF ALL
CONCRETE, AND SELECTION OF CONCRETE MATERIALS, SHALL
CONFORM TO ACI 301, "SPECIFICATION FOR STRUCTURAL CONCRETE
FOR BUILDINGS," EXCEPT AS NOTED BELOW. PROPORTIONS OF
AGGREGATE TO CEMENTITIOUS PASTE SHALL BE SUCH AS TO
PRODUCE A DENSE, WORKABLE MIX THAT CAN BE PLACED WITHOUT
SEGREGATION OR EXCESS FREE SURFACE WATER.
2. ALL CONCRETE USED IN HORIZONTAL SURFACES EXPOSED TO THE
WEATHER SHALL CONTAIN AN ACCEPTABLE ADMIXTURE TO PRODUCE
AIR-ENTRAINED CONCRETE WITH TOTAL AIR CONTENT, AS NOTED IN
THE CONCRETE MIX SPECIFICATION TABLE. TOLERANCE FOR AIR
CONTENT SHALL BE +/-1 PERCENT. AIR CONTENT SHALL BE MEASURED
AT THE DISCHARGE OF THE TRUCK. IF CONCRETE IS PUMPED, AIR
CONTENT SHALL BE MEASURED AT THE DISCHARGE END OF THE PUMP
LINE. TESTS FOR AIR CONTENT SHALL MEET ASTM C172
REQUIREMENTS.
3. MIX DESIGNS LISTED BELOW SHALL BE SUBMITTED TO THE ARCHITECT
AND APPROVED PRIOR TO USE. SUBMITTALS SHALL INCLUDE TEST
DATA THAT CONFIRMS THE STRENGTH OF EACH MIX PER ACI 318
CHAPTER 5. SELECTION OF CONCRETE MIX PROPORTIONS SHALL BE IN
ACCORDANCE WITH ACI 301. MIX PROPORTIONS SHALL MEET OR
EXCEED THE REQUIREMENTS LISTED BELOW FOR THE LOCATIONS
NOTED. THE MORE STRINGENT OF THE REQUIREMENTS LISTED SHALL
GOVERN.
4. MAXIMUM SIZE OF AGGREGATE SHALL BE AS LISTED BELOW. MAXIMUM
FLY ASH AS A PERCENTAGE OF TOTAL WEIGHT OF CEMENTITIOUS
MATERIAL SHALL BE 25 PERCENT. FLY ASH SHALL BE CLASS C OR F,
MEETING ASTM C618 REQUIREMENTS. WATER/CEMENT RATIO SHALL
BE BASED ON TOTAL CEMENTITIOUS MATERIAL, INCLUDING FLY ASH
AND OTHER POZZOLANIC MATERIALS.
5. THE CONTRACTOR SHALL DETERMINE SLUMP. EACH CONCRETE MIX
SUBMITTED SHALL HAVE THE SLUMP SPECIFIED. SLUMP SHALL BE
MEASURED AT THE DISCHARGE OF THE TRUCK. IF CONCRETE IS
PUMPED, SLUMP SHALL BE MEASURED AT THE DISCHARGE END OF THE
PUMP LINE. SLUMPS SHALL BE WITHIN +1 INCH AND -2 INCHES OF THE
SPECIFIED SLUMP.
6. THE USE OF SUPER PLASTICIZERS AND WATER REDUCERS IS
ALLOWED, BUT NOT REQUIRED. ALL ADMIXTURES SHALL BE CHLORIDE
FREE UNLESS OTHERWISE APPROVED BY THE ENGINEER.
CONCRETE MIX DESIGN TABLE
LOCATION
f
c’
(PSI)
TEST
AGE
(DAYS)
MAX
W/C
RATIO
AIR
CONTENT
(%)
MAX.
AGGREGATE
SIZE
MISCELLANEOUS
CONCRETE,
CURBS,
SIDEWALKS
4,500 28 0.45 6.0 1”
EXTERIOR
SLABS ON
GRADE
4,500 28 0.45 6.0 1”
INTERIOR SLABS
ON GRADE
4,000 28 0.45 - 1”
WALLS AND
FOOTINGS
4,000 28 0.44 - 1”
REINFORCING STEEL
1. ALL REINFORCING SHALL BE NEW BILLET STOCK ASTM A615, GRADE 60,
UNLESS NOTED OTHERWISE. BARS SHALL BE SECURELY TIED IN
PLACE WITH #16 DOUBLE-ANNEALED IRON WIRE. BARS SHALL BE
SUPPORTED ON ACCEPTABLE CHAIRS. REINFORCING STEEL SHALL BE
DETAILED IN ACCORDANCE WITH THE ACI "MANUAL OF STANDARD
PRACTICE FOR DETAILING OF REINFORCED CONCRETE STRUCTURES."
CONTRACTOR SHALL COORDINATE REINFORCING STEEL PLACEMENT
DETAILS AND PROVIDE TEMPLATES FOR PLACING STEEL IN
CONGESTED AREAS AS NECESSARY. SHOP DRAWINGS (INCLUDING
PLACING PLANS AND ELEVATIONS) SHALL BE SUBMITTED TO, AND
REVIEWED BY, THE ARCHITECT/ENGINEER BEFORE STARTING
FABRICATION.
2. NO REINFORCING BARS SHALL BE SPLICED BY WELDING. .
REINFORCING BARS SHALL BE LAP SPLICED FOR TENSION (LSB)
UNLESS NOTED OTHERWISE ON THE DRAWINGS.
3. WELDING OR TACK WELDING OF REINFORCING BARS TO OTHER BARS
OR TO PLATES, ANGLES, ETC, IS PROHIBITED.
4. MINIMUM CAST-IN-PLACE CONCRETE COVER OVER REINFORCING
STEEL, UNLESS NOTED OTHERWISE, SHALL BE AS FOLLOWS:
A. CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH:
ALL SIZES: 3 INCHES
B. CONCRETE EXPOSED TO EARTH OR WEATHER:
#5 BAR OR SMALLER: 1 1/2 INCHES
#6 BAR OR LARGER: 2 INCHES
C. OTHER CONCRETE:
WALLS - INTERIOR FACE:
#14 AND #18 BARS: 1 1/2 INCHES
#11 BARS AND SMALLER: 3/4 INCH
SLABS:
#14 AND #18 BARS: 1 1/2 INCHES
#11 BARS AND SMALLER: 3/4 INCH
CONSTRUCTION JOINTS
1. ALL CONSTRUCTION JOINTS IN WALLS SHALL BE KEYED IN
ACCORDANCE WITH THE TYPICAL CONSTRUCTION JOINT DETAILS
SHOWN ON THE STRUCTURAL DRAWINGS OR, AT THE CONTRACTOR'S
OPTION, SHALL BE INTENTIONALLY ROUGHENED IN ACCORDANCE WITH
THE FOLLOWING: THE SURFACE OF ROUGHENED JOINTS SHALL BE
SAND BLASTED OR ROUGHENED WITH A CHIPPING HAMMER TO
EXPOSE THE AGGREGATE EMBEDDED IN THE PREVIOUS POUR. THE
EXPOSED AGGREGATE SHALL PROTRUDE A MINIMUM OF 1/4 INCH. ALL
SURFACES OF CONSTRUCTION JOINTS SHALL BE CLEANED AND
LAITANCE REMOVED. IMMEDIATELY BEFORE NEW CONCRETE IS
PLACED, ALL CONSTRUCTION JOINTS SHALL BE WETTED AND
STANDING WATER REMOVED.
2. VERTICAL CONSTRUCTION JOINTS AND CONTROL JOINTS IN CONCRETE
AND CMU WALLS SHALL BE HELD TO A MAXIMUM SPACING OF 30'-0".
JOINTS SHALL BE PLACED WITHIN 15’-0” OF WALL CORNERS WHERE
POSSIBLE.
3. ALL CONSTRUCTION JOINTS IN SLABS, JOISTS, BEAMS, AND GIRDERS
SHALL BE SUBMITTED TO THE STRUCTURAL ENGINEER FOR REVIEW
BEFORE STARTING CONSTRUCTION.
4. ALL CONSTRUCTION, CONTROL, AND ISOLATION JOINTS FOR SLABS ON
GRADE SHALL BE IN ACCORDANCE WITH THE TYPICAL SLAB ON GRADE
DETAILS.
5. THE CONTRACTOR SHALL SUBMIT THE PROPOSED LOCATIONS OF
CONSTRUCTION JOINTS TO THE ENGINEER FOR ACCEPTANCE BEFORE
STARTING CONSTRUCTION.
SLEEVES
1. EXCEPT AS DETAILED ON STRUCTURAL DRAWINGS, NO CONCRETE
FOOTINGS, BEAMS, OR GIRDERS SHALL BE SLEEVED FOR PIPING OR
DUCTS, UNLESS APPROVED BY THE ENGINEER.
ANCHORAGE TO HARDENED CONCRETE
1. ANCHORAGE TO HARDENED CONCRETE SHALL INCLUDE MECHANICAL
AND ADHESIVE ANCHORS OF SIZE, NUMBER, AND SPACING AS SHOWN
ON THE DRAWINGS.
2. HOLES SHALL BE DRILLED AND CLEANED AND ANCHORS SHALL BE
INSTALLED IN STRICT ACCORDANCE WITH THE MANUFACTURER’S
PUBLISHED INSTRUCTIONS AND AN APPROVED ICC-ES REPORT.
3. INSPECTION AND TESTING SHALL BE PROVIDED IN ACCORDANCE WITH
THE GENERAL NOTES AND THE APPROVED ICC-ES REPORT.
4. WHERE A SPECIFIC TYPE OF ANCHORAGE IS SPECIFIED ON THE
DRAWINGS, SUBSTITUTION FOR A DIFFERENT TYPE OF ANCHORAGE
(INCLUDING SUBSTITUTING FOR CAST-IN-PLACE ANCHORAGE) SHALL
NOT BE PERMITTED WITHOUT PRIOR WRITTEN APPROVAL.
MECHANICAL ANCHORS
1. MECHANICAL ANCHORS SHALL BE USED ONLY WHERE SHOWN ON
THESE DRAWINGS. PRIMARY BUILDING FRAME ANCHORS MUST BE
CAST-IN-PLACE PER THESE DRAWINGS.
2. ACCEPTABLE MECHANICAL ANCHORS SHALL BE AS FOLLOWS:
A. INSTALLED IN CONCRETE:
- HILTI “KWIK BOLT TZ” (ICC-ES ESR-19)
- SIMPSON STRONG-TIE “STRONG-BOLT-2” (ICC-ES ESR-3037)
- APPROVED ALTERNATE WITH A CURRENT ICC-ES REPORT
B. INSTALLED IN GROUT FILLED MASONRY:
- HILTI “KH-EZ” (ICC-ES ESR-3056)
- SIMPSON STRONG-TIE “TITEN HD” (ICC-ES ESR-1056)
- APPROVED ALTERNATE WITH A CURRENT ICC-ES REPORT
3. UNLESS NOTED OTHERWISE ON THE DRAWINGS, MINIMUM EFFECTIVE
ANCHOR EMBEDMENT DEPTH SHALL BE 6.5 ANCHOR DIAMETERS,
MINIMUM DISTANCE TO THE NEAREST CONCRETE EDGE SHALL BE 12
ANCHOR DIAMETERS, AND MINIMUM ANCHOR SPACING SHALL BE 8
ANCHOR DIAMETERS.
4. STAINLESS STEEL ANCHORS SHALL BE USED AT ALL EXTERIOR
LOCATIONS AND WHERE SPECIFICALLY INDICATED ON THE DRAWINGS.
5. NO STEEL REINFORCEMENT SHALL BE CUT TO INSTALL ANCHORS.
ADHESIVE ANCHORS
1. ADHESIVE ANCHORS SHALL BE USED ONLY WHERE SHOWN ON THESE
DRAWINGS. PRIMARY BUILDING FRAME ANCHORS MUST BE CAST-IN-
PLACE PER THESE DRAWINGS
2. ACCEPTABLE ADHESIVE (EPOXY) ANCHORS SHALL BE AS FOLLOWS:
A. INSTALLED IN CONCRETE:
- HILTI “HIT-HY 200” (ICC-ES ESR-4868)
- SIMPSON STRONG-TIE “SET-3G” (ICC-ES ESR-4057)
- APPROVED ALTERNATE WITH A CURRENT ICC-ES REPORT
B. INSTALLED IN BRICK MASONRY:
- HILTI “HIT-HY 270” (ICC-ES ESR-4143)
- APPROVED ALTERNATE WITH A CURRENT ICC-ES REPORT
3. UNLESS NOTED OTHERWISE, ANCHORS SHALL BE ASTM A36 THREADED
ROD OR ASTM A615, GRADE 60 REINFORCING STEEL DOWELS.
4. UNLESS NOTED OTHERWISE ON THE DRAWINGS, MINIMUM EFFECTIVE
ANCHOR EMBEDMENT DEPTH SHALL BE 6.5 ANCHOR DIAMETERS, AND
MINIMUM ANCHOR SPACING SHALL BE 6 ANCHOR DIAMETERS.
5. HOLES SHALL BE DRILLED WITH ROTARY IMPACT HAMMER OR
EQUIVALENT METHOD TO PRODUCE A HOLE WITH A ROUGH INSIDE
SURFACE. CORE DRILLING HOLES IS NOT PERMITTED.
6. NO REINFORCING SHALL BE CUT TO INSTALL ADHESIVE ANCHORS.
7. TWO-PART ADHESIVES SHALL BE MIXED, APPLIED, AND CURED IN
STRICT ACCORDANCE WITH THE MANUFACTURER’S PUBLISHED
INSTALLATION INSTRUCTIONS IN THE ICC-ES REPORT. ALL PLACEMENT
AND CURING SHALL BE CONDUCTED WITH CONCRETE AND AIR
TEMPERATURES ABOVE 50 DEGREES FAHRENHEIT. ADHESIVE SHALL
BE APPLIED ONLY TO CLEAN, DRY CONCRETE. POSITIVE PROTECTION
SHALL BE PROVIDED SO THAT ANCHORS ARE NOT DISTURBED DURING
THE CURING PERIOD.
NONSHRINK GROUT FOR BASE PLATES, SLEEVES, AND EMBEDDED STEEL
1. GROUT SHALL BE AN APPROVED NONSHRINK CEMENTITIOUS GROUT
CONTAINING NATURAL AGGREGATES DELIVERED TO THE JOB SITE IN
FACTORY PREPACKAGED CONTAINERS REQUIRING ONLY THE
ADDITION OF WATER.
2. THE MINIMUM 28-DAY COMPRESSIVE STRENGTH SHALL BE AT LEAST
1,000 PSI HIGHER THAN THE SUPPORTING CONCRETE STRENGTH,
UNLESS NOTED OTHERWISE.
3. GROUT SHALL BE MIXED, APPLIED, AND CURED STRICTLY IN
ACCORDANCE WITH THE MANUFACTURER'S PRINTED INSTRUCTIONS.
FOR GROUTING UNDER BASE PLATES, GROUT SHALL BE
PROPORTIONED AS A FLOWABLE MIX. WHEN A FLOWABLE MIX DOES
NOT PROVIDE THE REQUIRED STRENGTH OR WHEN A MINIMUM
STRENGTH OF 10,000 PSI IS REQUIRED, AN EPOXY GROUT SHALL BE
USED.
STRUCTURAL STEEL
ALL STEEL SHALL CONFORM TO THE FOLLOWING:
W-SHAPES ASTM A992, Fy=50 KSI
HP-SHAPES ASTM A572, Fy=50 KSI
ANGLES, CHANNELS & PLATES ASTM A36, Fy=36 KSI
UNLESS NOTED OTHERWISE
SQUARE OR RECTANGULAR ASTM A500, GRADE B,
STRUCTURAL TUBE (HSS) Fy=46 KSI
ROUND STRUCTURAL TUBE ASTM A500, GRADE B,
(HSS) Fy=42 KSI
STEEL PIPE DIAMETER LESS ASTM A53, TYPE E OR S,
THAN OR EQUAL TO 12 INCHES GRADE B, Fy=35 KSI
ALL OTHER STEEL UNLESS ASTM A572, Fy=50 KSI
NOTED OTHERWISE ASTM A588, Fy=50 KSI
ASTM A441, Fy=50 KSI
1. GENERAL NOTES FOR STEEL CONNECTIONS SHALL APPLY TO ALL
STEEL CONNECTIONS UNLESS NOTED OTHERWISE.
2. ALL WORK SHALL BE IN ACCORDANCE WITH THE AISC SPECIFICATION.
SHOP DRAWINGS SHALL BE SUBMITTED AND REVIEWED BY THE
ARCHITECT/ENGINEER BEFORE COMMENCING FABRICATION.
3. ALL STEEL ANCHORS AND TIES AND OTHER MEMBERS EMBEDDED IN
CONCRETE OR MASONRY SHALL BE LEFT UNPAINTED. DIMENSIONAL
TOLERANCE FOR BUILT-UP MEMBERS SHALL BE PER AWS D1.1.
4. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL ERECTION AIDS
THAT INCLUDE, BUT ARE NOT LIMITED TO, ERECTION ANGLES, LIFT
HOLES, AND OTHER AIDS.
ANCHOR RODS
1. ANCHOR RODS SHALL BE ASTM F1554 GRADE 36 WITH CLASS 1A
THREADS, UNLESS NOTED OTHERWISE.
2. ANCHOR RODS MAY BE HEADED BOLT OR UNHEADED ROD MATERIAL.
PROVIDE HEAVY HEX NUT ON THE EMBEDDED END OF THE UNHEADED
ROD AND WELD IN PLACE TO PREVENT IT FROM TURNING.
3. FURNISH HARDENED PLATE WASHERS, LOCK WASHERS, AND
MATCHING HEAVY HEX NUTS FOR SECURING THE BASE PLATE TO THE
ANCHOR RODS.
4. HOOKED ANCHOR RODS SHALL NOT BE USED EXCEPT WHERE NOTED.
5. A RIGID STEEL TEMPLATE SHALL BE USED TO LOCATE ANCHOR RODS
WHILE PLACING CONCRETE.
6. ANCHOR RODS SHALL HAVE SUFFICIENT LENGTH TO PROVIDE THE
MINIMUM EMBEDMENT SHOWN ON THE DRAWINGS, MEASURED FROM
THE FACE OF THE CONCRETE TO THE NEAR FACE OF THE DOUBLE NUT,
WITH ADEQUATE EXTENSION AS REQUIRED TO RECEIVE THE BASE
PLATE WITH FULL THREAD PROJECTION FOR NUT INSTALLATION.
7. ANCHOR ROD INSTALLATION SHALL BE COORDINATED WITH
REINFORCING AND FORMWORK.
8. LEVELING NUTS SHALL NOT BE USED EXCEPT AFTER EVALUATION BY
THE CONTRACTOR'S ERECTION ENGINEER.
9. AFTER BASE INSTALLATION, ANCHOR ROD NUTS SHALL BE INSTALLED
TO A SNUG-TIGHT CONDITION.
10. NO HEATING OR BENDING OF THE ANCHOR RODS IS PERMITTED.
11. HOLES IN THE BASE MATERIAL SHALL NOT BE ENLARGED BY BURNING.
STEEL ROOF DECK
1. THE STEEL ROOF DECK SHALL BE OF DEPTH SHOWN ON THE
STRUCTURAL DRAWINGS, HAVE A MINIMUM YIELD STRENGTH OF 50 KSI,
AND COMPLY WITH THE “STEEL DECK INSTITUTE” (SDI) STANDARDS.
2. STEEL DECK TYPES SHALL BE VULCRAFT TYPE B, VERCO TYPE HSB-36,
ACS TYPE B, OR APPROVED EQUAL, UNLESS NOTED OTHERWISE.
MINIMUM GAUGE IS 20.
3. THE SIDE LAPS OF ADJACENT UNITS SHALL BE FASTENED BETWEEN
SUPPORTS BY #10 TEK SCREWS AT A MAXIMUM SPACING OF 2’-0” ON
CENTER UNLESS NOTED OTHERWISE.
4. DECK UNITS SHALL BE CONNECTED WITH #10 TEK SCREWS TO ALL THE
STEEL AND CFS STEEL SUPPORTS AT A MAXIMUM SPACING OF 1’-0” ON
CENTER UNLESS NOTED OTHERWISE.
5. SHOP DRAWINGS SHALL BE SUBMITTED SHOWING DECK GAUGE,
LAYOUT, CONNECTIONS, AND CLOSURES.
6. WHERE SPECIFIED AS GALVANIZED, ROOF DECK AND ALL OF ITS
ACCESSORIES SHALL CONFORM TO ASTM A653 STRUCTURAL QUALITY
GRADE SS33. GALVANIZING SHALL CONFORM TO ASTM A924 WITH A
MINIMUM COATING CLASS OF G30 AS DEFINED BY ASTIM A653.
7. ALL WELDING SHALL BE IN ACCORDANCE WITH AWS D1.3.
8. UNITS SHALL SPAN OVER FOUR SUPPORTS, CONTINUOUS OVER THREE
OR MORE SPANS, EXCEPT WHERE THE FRAMING DOES NOT PERMIT.
9. WHERE STEEL MEMBERS ARE PARALLEL TO THE DECK FLUTES AND AT
THE SAME ELEVATION OF THE BOTTOM OF THE DECK, ADJUST DECK
LAYOUT AND WELD DECK TO STEEL WITH SAME WELDING AS
REQUIRED FOR SIDE BOUNDARIES.
GAUGE STEEL FRAMING
1. THE CONTRACTOR SHALL PROVIDE FULL-TIME QUALITY CONTROL
OVER ALL FABRICATION AND ERECTION ACTIVITY THROUGH THE USE
OF AN INDEPENDENT TESTING AGENCY AND/OR A QUALIFIED
REPRESENTATIVE OF THE STEEL MANUFACTURER.
2. THE CONTRACTOR SHALL OBTAIN MILL CERTIFICATION FROM THE
GAUGE STEEL MANUFACTURER OR SHALL SUBMIT TENSILE TESTS AND
GALVANIZATION TESTS TO THE ENGINEER OF RECORD TO VERIFY THE
ADEQUACY OF THE GAUGE MATERIALS.
3. GAUGE MATERIAL SHALL BE FORGED FROM GALVANIZED ASTM A653
STEEL. 54 MIL (16 GA.), 68 MIL (14 GA.) AND 97 MIL (12 GA.) MATERIAL
SHALL BE GRADE 50 WITH A MINIMUM YIELD STRESS OF 50 KSI. 43 MIL
(18 GA.) AND LIGHTER MATERIAL SHALL BE GRADE 33 WITH A MINIMUM
YIELD STRESS OF 33 KSI. ALL MEMBERS TO BE GALVANIZED PER ASTM
A653 WITH A MINIMUM G60 COATING
4. FRAMING MEMBERS SHALL HAVE THE MINIMUM EFFECTIVE PHYSICAL
AND STRUCTURAL PROPERTIES AS PUBLISHED BY THE STEEL STUD
MANUFACTURER’S ASSOCIATION (ICC ES ER-4943P) OR EQUIVALENT
ICBO APPROVED FRAMING MEMBERS AT THE CONTRACTOR’S OPTION.
5. MEMBER DESIGNATION:
600 S 162 - 54
DEPTH MEMBER FLANGE MATERIAL
(INCHES) TYPE WIDTH THICKNESS
(INCHES) (MILS)
6. WALL STUDS AND FRAMING AT WALL OPENINGS SHALL BE PER THE
DRAWINGS. STUDS SHALL BE SHEATHED ON BOTH SIDES EXCEPT
WHERE NOTED. COLD ROLLED CHANNEL OR OTHER
BRIDGING/BRACING SHALL BE PROVIDED WHERE SHEATHING ONLY
OCCURS ON ONE SIDE. SEE TYPICAL DETAILS FOR ADDITIONAL
INFORMATION.
7. WALL STUD BRIDGING SHALL BE INSTALLED IN A MANNER TO PREVENT
STUD ROTATION. BRIDGING ROWS SHALL BE SPACED PER THE
MANUFACTURER’S PUBLISHED RECOMMENDATIONS. THE MAXIMUM
SPACING FOR BRIDGING SHALL BE 5’-0” ON CENTER FOR WALLS
RESISTING HORIZONTAL WIND LOADS ONLY AND 3’-4” ON CENTER FOR
AXIAL LOADED WALLS
8. SPLICES IN AXIALLY LOADED STUDS SHALL NOT BE PERMITTED.
9. GAUGE STEEL ACCESSORIES SHALL OF THE TYPE, SIZE AND SPACING
SHOWN ON THE DRAWINGS, 54 MIL (16 GA.) MINIMUM UNLESS DETAILED
OTHERWISE.
10. ERECT FRAMING PLUMB, LEVEL AND SQUARE IN ACCORDANCE WITH
THE APPROVED SHOP DRAWINGS.
11. TEMPORARY BRACING OF WALL FRAMING SHALL BE PROVIDED BY THE
CONTRACTOR AS REQUIRED AND REMOVED ONLY AFTER THE FRAMING
HAS BEEN SECURED WITH PERMANENT SUPPORT.
GAUGE STEEL FASTENERS
1. FASTENING OF GAUGE STEEL COMPONENTS SHALL BE BY WELDING OR
SCREWING OR BY OTHER MEANS OF FASTENING AS INDICATED IN THE
DRAWINGS.
2. ALL FASTENERS SHALL BE OF THE TYPE AND SIZE SHOWN IN THE
DRAWINGS TO ACCOMMODATE THE CONNECTIONS. FASTENERS
INSTALLED IN CONCRETE SHALL BE INSTALLED ONLY AFTER THE
SPECIFICED 28-DAY COMPRESSIVE STRENGTH OF THE CONCRETE HAS
BEEN OBTAINED.
3. SCREWS:
A. ALL SCREWS (REFFERRED TO AS TEK) SHALL BE SELF-TAPPING
SELF-DRILLING FASTENERS THAT ARE ZINC COATED AS
MANUFACTURED BY ITW BUILDEX TEK/TRAXX, ELCO DRIL-FLEX,
HILTI KWIK-FLEX, OR APPROVED EQUAL.
B. THE MINIMUM SCREW SIZE/TYPE/POINT SHALL BE #8-18 (#2 POINT)
OR #10-16 (#2 POINT) TEK FOR USE IN 33 MIL (20 GA.) THROUGH 54
MIL (16 GA.) MATERIAL, AND #10-16 (#3 POINT) OR #12-14 (#2 OR #3
POINT) TEK FOR MATERIAL HEAVIER THAN 54 MIL (16GA.) UNLESS
NOTED OTHERWISE.
C. SCREWS FOR SHEATHING CONNECTIONS SHALL BE OF THE PROPER
SIZE AND TYPE FOR A POSITIVE SHEATHING-TO-METAL
CONNECTION.
D. ALL SCREW CONNECTIONS SHALL BE MADE FROM THE LIGHTER
MATERIAL INTO THE HEAVIER MATERIAL UNLESS NOTED
OTHERWISE.
E. SCREWS SHALL HAVE A MINIMUM PROJECTION OF 3 THREADS
THROUGH THE LAST MATERIAL JOINED AND SHALL HAVE MINIMUM
EDGE DISTANCES AND CENTER-TO-CENTER SPACINGS OF ½ INCH.
F. ALL SCREWS SHALL CONFORM TO SAE J78 AND SHALL BE COATED
WITH A CORROSIVE-RESISTANT COATING. THE SCREW
MANUFACTURER SHALL PROVIDE VERIFICATION OF THE FASTENERS
RESISTANCE TO HYDROGEN EMBRITTELMENT.
4. WELDS:
A. WELDS SHALL BE OF THE TYPE, SIZE AND SPACING SHOWN ON THE
DRAWINGS AND OF SUFFICIENT SIZE TO INSURE THE STRENGTH OF
THE CONNECTION.
B. ALL WELDING OF GAUGE STEEL MATERIAL SHALL BE IN
ACCORDANCE WITH AWS D1.3.
C. WIRE TYING OF COMPONENTS SHALL NOT BE PERMITTED.
D. ALL WELDS SHALL BE TOUCHED UP WITH A ZINC-RICH PAINT.
5. POWDER DRIVEN FASTENERS (P.D.F.):
A. POWDER DRIVEN FASTENERS INSTALLED IN CONCRETE OR STEEL
SHALL BE AS MANUFACTURED BY HILTI, INC. (ICC ES ESR-2269) OR
APPROVED EQUAL AND INSTALLED IN CONFORMANCE WITH THE
MANUFACTURER’S PUBLISHED RECOMMENDATIONS AND THE
GUIDELINES OF THE EVALUATION REPORT.
FLOOR SHEATHING
1. PROVIDE 3/4-INCH TONGUE AND GROOVE CDX PLYWOOD, INDEX 40/20,
UNBLOCKED, LAID UP WITH FACE GRAIN PERPENDICULAR TO FRAMING
BELOW. STAGGER PANEL END JOINTS. PROVIDE 1/8-INCH GAP
BETWEEN ALL ABUTTING PANEL EDGES:
FOUNDATIONS
1. COLUMN DOWELS SHALL BE INSTALLED WITH A TEMPLATE TO HOLD
BARS IN THE PROPER POSITION AND SHALL BE PLACED WITH A
TOLERANCE OF +/- 1/4 INCH.
2. SPREAD FOOTINGS:
A. DESIGN SOIL BEARING PRESSURE = 3,000 PSF.
B. ALL FOOTINGS SHALL BEAR ON UNDISTURBED NATIVE SOIL OR
COMPACTED ENGINEERED FILL PER THE RECOMMENDATIONS
LISTED IN SECTION 6 OF THE GEOTECHNICAL REPORT.
C. REFER TO THE PROJECT GEOTECHNICAL EVALUATION REPORT FOR
SOIL CONDITIONS AND RECOMMENDATIONS
- PREPARED BY: TWIN PORTS TESTING.
- PROJECT NO.: 25G2116
- DATED: DECEMBER 5, 2025
D. SITE AND BUILDING SUBGRADE SHALL BE PREPARED IN
ACCORDANCE WITH THE RECOMMENDATIONS OF THE PROJECT
GEOTECHNICAL REPORT.
STRUCTURAL FILL
1. ALL STRUCTURAL FILL MATERIAL SHALL BE IMPORTED INCLUDING
MATERIAL PLACED TO SUPPORT SLABS ON GRADE, BEHIND
PERMANENT WALLS, AND AROUND ALL DRAINS. THE FILL MATERIAL
SHALL CONSIST OF WELL GRADED, GRANULAR MATERIAL PER
RECOMMENDATIONS OF THE GEOTECHNICAL ENGINEERING REPORT
SECTION 6.2 (SITE PREPARATION)
2. SOILS FOR STRUCTURAL FILL SHALL BE SUBMITTED TO AND APPROVED
BY THE GEOTECHNICAL ENGINEER.
3. STRUCTURAL FILL SHALL BE PLACED ON SOUND NATIVE MATERIAL.
4. PROOF-ROLL CUT AREAS WHICH PROVIDE SUPPORT FOR PERMANENT
STRUCTURES.
5. AREAS WHICH ARE EXCESSIVELY YIELDING, AS DETERMINED BY THE
CONTINUOUS OBSERVATION OF THE GEOTECHNICAL ENGINEER, SHALL
BE OVEREXCAVATED AND REPLACED WITH STRUCTURAL FILL.
PRE-ENGINEERED METAL BUILDING FOUNDATION
1. FOUNDATION DESIGN FOR THE PRE-ENGINEERED METAL BUILDING IS
BASED ON BUILDING REACTIONS PROVIDED BY BUTLER
MANUFACTURING DATED 12-27-2025. SEE FOUNDATION PLAN SHEET
FOR A SUMMARY OF THE BUILDING LOAD REACTIONS. ALL METAL
BUILDING COLUMNS ASSUMED TO BE PIN CONNECTED AT THE
FOUNDATION.
2. PRE-ENGINEERED METAL BUILDING DRAWINGS AND CALCULATIONS
SHALL BE CERTIFIED BY A PROFESSIONAL ENGINEER LICENSED IN THE
STATE OF WISCONSIN.
3. CONSTRUCTION OF THE PRE-ENGINEERED METAL BUILDING
FOUNDATION IS NOT PERMITTED UNTIL FINAL CERTIFIED DRAWINGS
AND CALCULATIONS HAVE BEEN REVIEWED AND APPROVED.
MISCELLANEOUS METALS
1. THE CONTRACTOR SHALL DESIGN AND SUPPLY ALL ADDITIONAL
MISCELLANEOUS METALS THAT ARE INDICATED IN THE
ARCHITECTURAL DRAWINGS OR THOSE METALS WHICH ARE FOUND TO
BE NECESSARY TO SUPPORT THE ARCHITECTURAL FINISHES OR
OTHER BUILDING SYSTEMS.
2. ALL FRAMING AND CONNECTIONS DESIGNED BY THE CONTRACTOR
SHALL NOT RESULT IN ECCENTRIC LOADS BEING APPLIED TO THE
PRIMARY STRUCTURE NOR LATERAL LOADS BEING APPLIED TO THE
BOTTOM FLANGE OF STEEL BEAMS. THE CONTRACTOR’S DESIGN
SHALL VERIFY THAT THE CONNECTIONS DO NOT RESULT IN ADVERSE
LOCAL CONNECTION STRESSES OCCURRING WITHIN THE PRIMARY
STRUCTURE. SUBMIT CALCULATIONS STAMPED BY A STRUCTURAL
ENGINEER LICENSED TO PERFORM THE WORK IN THE JURISDICTION
WHERE THE PROJECT IS LOCATED AND SHOP DRAWINGS INDICATING
IMPOSED LOADS ON THE PRIMARY STRUCTURE.
MECHANICAL/ELECTRICAL/PLUMBING SYSTEM SUPPORTS
1. THE CONTRACTOR SHALL DESIGN AND SUPPLY ALL ADDITIONAL
MISCELLANEOUS METALS AND SYSTEM SUPPORT COMPONENTS THAT
ARE NECESSARY TO SUPPORT ALL MECHANICAL, ELECTRICAL
(TELECON, AUDIO VISUAL, ETC.), AND PLUMBING/FIRE-PROTECTION
SYSTEMS. SUCH METALS AND SUPPORT COMPONENTS AND THEIR
CONNECTIONS SHALL BE PROVIDED AS NECESSARY TO DIRECTLY AND
CONCENTRICALLY IMPOSE LOADS ON THE PRIMARY STRUCTURE.
2. STEEL ROOF DECK SHALL NOT DIRECTLY SUPPORT THESE SYSTEMS.
3. THE CONNECTIONS TO THE PRIMARY STRUCTURE ARE SUBJECT TO
THE REQUIREMENTS OF THE MISCELLANEOUS METALS SECTION
ABOVE.
SECONDARY SUPPORT FRAMING
1. SECONDARY SUPPORT FRAMING FOR CONNECTING NON-STRUCTURAL
COMPONENTS TO THE PRIMARY STRUCTURE SHALL BE DESIGNED,
SUPPLIED AND INSTALLED BY OTHERS.
2. SHOP DRAWINGS FOR SECONDARY SUPPORT FRAMING SHALL BE
SUBMITTED FOR REVIEW ALONG WITH THE SUPPORTING CERTIFIED
STRUCTURAL CALCULATIONS. SUBMITTAL SHALL IDENTIFY THE LOADS
IMPOSED UPON THE PRIMARY STRUCTURE AT THE CONNECTION
POINTS OF THE SECONDARY SUPPORT FRAMING.
3. UNISTRUT, OR EQUIVALENT, AND ITS CONNECTIONS SHALL BE
CONSIDERED SECONDARY SUPPORT FRAMING, UNLESS SPECIFICALLY
NOTED OTHERWISE.
INTERIOR STEEL STUD FRAMING
1. INTERIOR PARTITIONS SHALL CONSIST OF METAL STUD TYPE FRAMING
THAT HAS CURRENT ICC-ES EVALUATION REPORTS.
2. CONNECTION OF STUDS, TRACK, AND OTHER ITEMS BY MEANS OF
EITHER DRILLED-IN ANCHORAGE OR POWDER DRIVEN FASTENERS
SHALL OCCUR WITH FASTENERS AS INDICATED IN THE METAL STUD
ICC-ES REPORTS. CONNECTIONS SHALL ALLOW FOR THE BUILDING
MOVEMENTS CITED ABOVE.
3. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE STRUCTURAL
DESIGN OF SOFFITS, SUSPENDED WALLS, CEILINGS, OR CONDITIONS
WHERE THE STUD FRAMING IS USED TO SUPPORT CASEWORK OR
SIZEABLE DOOR/WINDOW HARDWARE; THE METAL STUD FRAMING; AND
ANY MISCELLANEOUS STEEL FRAMING THAT IS DETERMINED TO BE
NECESSARY BASED ON THE CONTRACTOR’S DESIGN. SUBMIT DESIGN
CALCULATIONS AND SHOP DRAWINGS INDICATING IMPOSED LOADS ON
THE PRIMARY STRUCTURE FOR THESE CONDITIONS. SUBMITTED
DOCUMENTS SHALL BEAR THE STAMP AND SIGNATURE OF AN
ENGINEER LICENSED TO PERFORM THE WORK IN THE JURISDICTION
WHERE THE PROJECT IS LOCATED.
BUILDING TOLERANCES
1. STANDARD TOLERANCES SHALL BE BASED ON THE REQUIREMENTS OF
THE AISC CODE OF STANDARD PRACTICE AND ACI 117, "STANDARD
SPECIFICATIONS FOR TOLERANCES FOR CONCRETE CONSTRUCTION
AND MATERIALS."
DEFERRED STRUCTURAL SUBMITTALS
1. SOME STRUCTURAL SYSTEMS ARE DEFINED AS VENDOR-DESIGNED
COMPONENTS PER THE STRUCTURAL DOCUMENTS. THESE ELEMENTS
OF THE DESIGN ARE DEFERRED SUBMITTAL COMPONENTS AND HAVE
NOT BEEN PERMITTED UNDER THE BASE BUILDING APPLICATION. THE
CONTRACTOR WILL BE REQUIRED TO SUBMIT THE STAMPED
COMPONENT SYSTEM DOCUMENTS TO THE BUILDING OFFICIAL FOR
APPROVAL.
2. DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED
TO THE ARCHITECT, WHO SHALL REVIEW THEM FOR GENERAL
CONFORMANCE TO THE DESIGN OF THE BUILDING. THE CONTRACTOR
SHALL SUBMIT THESE REVIEWED DEFERRED SUBMITTAL DOCUMENTS
TO THE BUILDING OFFICIAL. THE DEFERRED SUBMITTAL ITEMS SHALL
NOT BE INSTALLED UNTIL THE DESIGN AND SUBMITTAL DOCUMENTS
HAVE BEEN APPROVED BY THE BUILDING OFFICIAL.
3. THE FOLLOWING LIST INCLUDES THE ITEMS THAT ARE DEFINED AS
DEFERRED STRUCTURAL SUBMITTAL COMPONENTS. REFER TO THE
ARCHITECTURAL, MECHANICAL, ELECTRICAL, AND CIVIL DRAWINGS
FOR ADDITIONAL DEFERRED SUBMITTAL COMPONENTS.
4. DEFERRED STRUCTURAL SUBMITTAL COMPONENTS:
A. PRE-ENGINEERED METAL BUILDING
B. SECONDARY SUPPORT FRAMING AND CONNECTIONS
MISCELLANEOUS
1. REFER TO ARCHITECTURAL, MECHANICAL, ELECTRICAL, CIVIL, OR
OTHER SPECIALTY ENGINEERING DRAWINGS FOR DIMENSIONS NOT
SHOWN, INCLUDING BUT NOT LIMITED TO: SIZE AND LOCATION OF
CURBS, EQUIPMENT HOUSEKEEPING PADS, WALL AND FLOOR
OPENINGS, BLOCKOUTS, FLOOR DEPRESSIONS, SUMPS, DRAINS,
ANCHOR BOLTS, EMBEDDED ITEMS, ARCHITECTURAL TREATMENT, ETC.
THE CONTRACTOR SHALL VERIFY DIMENSIONS AND RESOLVE
DISCREPANCIES OR CONFLICTS PRIOR TO CONSTRUCTION.
2. WHERE SECTIONS ARE INDICATED ON THE PLAN BY A NUMBER AND A
DRAWING NUMBER THUS, 1/S5.01, THE INDICATED SECTION (1) IS
SHOWN ON STRUCTURAL DRAWING S5.01.
SPECIAL INSPECTION
1. THE FOLLOWING ITEMS REQUIRE SPECIAL INSPECTION AND TESTING
PER IBC SECTION 1704.
2. THIS WORK SHALL BE PERFORMED BY A SPECIAL INSPECTOR
CERTIFIED BY THE GOVERNING BUILDING OFFICIAL TO PERFORM THE
TYPES OF INSPECTIONS AND TESTS SPECIFIED.
3. THE FREQUENCY OF INSPECTIONS AND TESTING SHALL BE AS
OUTLINED IN THE IBC TABLE ITEMS LISTED BELOW.
4. DEFICIENCIES SHALL BE REPORTED DAILY TO THE CONTRACTOR.
5. SUMMARY REPORTS SHALL BE DISTRIBUTED WEEKLY TO THE OWNER,
ARCHITECT, CONTRACTOR, BUILDING OFFICIAL, AND STRUCTURAL
ENGINEER. THE CONCRETE SUPPLIER SHALL BE INCLUDED IN THE
DISTRIBUTION OF ALL SUMMARY REPORTS FOR CONCRETE TESTING.
6. SEE THE SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS FOR
SPECIAL INSPECTION AND TESTING.
SPECIAL INSPECTION TABLE
ITEM
DESCRIPTION
(SEE IBC SECTS. 1704 & 1705)
IBC
REQUIREMENT
CONCRETE CONCRETE THAT IS PART OF
THE STRUCTURE
TABLE 1705.3
ITEMS 5, 6, 7, 8,
AND 1 4
BOLTS INSTALLED IN
CONCRETE
ANCHOR BOLTS, HEADED
STUDS (EXCEPT AT BEAM-TO-
DECK INSTALLATION)
TABLE 1705.3
ITEM 3
REINFORCING STEEL A. PLACEMENT OF
REINFORCING STEEL
TABLE 1705.3
ITEM 1
PRE-ENGINEERED
METAL BUILDING
ERECTION
SEE STRUCTURAL STEEL AND
WELDING SECTION ABOVE
SEE METAL BUILDING
MANUFACTURER’S
DRAWINGS FOR ANY
ADDITIONAL INSPECTION
REQUIREMENTS
STEEL OTHER THAN
STRUCTURAL STEEL
A. COLD-FORMED STEEL
DECK THAT IS PART OF
THE STRUCTURE
B. WELDING OF COLD-
FORMED STEEL DECK
IBC SECTION
1705.2.2
IBC SECTION
1705.2.2
SOILS, SPECIAL
GRADING,
EXCAVATION AND
FILLING
A. FOUNDATION
EXCAVATIONS AND
BEARING STRATA
B. TESTING, PREPERATION,
PLACEMENT, AND
COMPACTION
TABLE 1705.6
ITEMS 1 AND 2
TABLE 1705.6
ITEMS 3, 4, AND
5
POST INSTALLED
ANCHORS OR
DOWELS
ALL POST-INSTALLED ANCHORS/ DOWELS
SHALL BE SPECIALLY INSPECTED AS REQUIRED
BY TABLE 1705.3 ITEM 4 AND AS REQUIRED BY
THE APPROVED ICC -ES REPORT
EPOXY OR CEMENT
GROUTED DOWELS
OR ANCHORS
-OBSERVE DRILLED HOLES AFTER CLEANING
AND INSTALLATION OF ANCHOR
-ANCHORS SUBJECT TO SUSTAINED TENSION
SHALL BE CONTINUOUSLY INSPECTED AND
INSTALLED BY A CERTFIED INSTALLER IN
ACCORDANCE WITH THE MANUFACTUREER’S
PRINTED INSTALLATION INSTRUCTIONS AND ACI
318, 26.7
SHOP DRAWINGS
1. SHOP DRAWINGS FOR THE FOLLOWING ITEMS SHALL BE SUBMITTED
FOR REVIEW PRIOR TO FABRICATION:
A. REINFORCING STEEL
B. SECONDARY SUPPORT FRAMING AND CONNECTIONS
2. DIMENSIONS AND QUANTITIES ARE NOT REVIEWED BY THE ENGINEER
OF RECORD; THEREFORE, THEY SHALL BE VERIFIED BY THE
CONTRACTOR. THE CONTRACTOR SHALL REVIEW AND STAMP
DRAWINGS PRIOR TO REVIEW BY THE ENGINEER OF RECORD.
CONTRACTOR SHALL REVIEW DRAWINGS FOR CONFORMANCE WITH
THE MEANS, METHODS, TECHNIQUES, SEQUENCES, AND OPERATIONS
OF CONSTRUCTION, AND ALL SAFETY PRECAUTIONS AND PROGRAMS
INCIDENTAL THERETO. SUBMITTALS SHALL INCLUDE ONE ELECTRONIC
COPY TO BE MARKED AND RETURNED.
3. SHOP DRAWING SUBMITTALS PROCESSED BY THE ENGINEER ARE NOT
CHANGE ORDERS. THE PURPOSE OF SHOP DRAWING SUBMITTALS BY
THE CONTRACTOR IS TO DEMONSTRATE TO THE ENGINEER THAT THE
CONTRACTOR UNDERSTANDS THE DESIGN CONCEPT, BY INDICATING
WHICH MATERIAL IS INTENDED TO BE FURNISHED AND INSTALLED, AND
BY DETAILING THE INTENDED FABRICATION AND INSTALLATION
METHODS. IF DEVIATIONS, DISCREPANCIES, OR CONFLICTS BETWEEN
SHOP DRAWINGS SUBMITTALS AND THE CONTRACT DOCUMENTS ARE
DISCOVERED EITHER PRIOR TO OR AFTER SHOP DRAWING
SUBMITTALS ARE PROCESSED BY THE ENGINEER, THE DESIGN
DRAWINGS AND SPECIFICATIONS SHALL CONTROL AND SHALL BE
FOLLOWED.
4. SHOP DRAWINGS FOR DEFERRED SUBMITTALS THAT ARE DEFINED AS
DESIGN-BUILD COMPONENTS IN THE CONSTRUCTION DOCUMENTS
SHALL INCLUDE THE DESIGNING PROFESSIONAL ENGINEER'S STAMP
FOR THE JURISDICTION WHERE THE PROJECT IS LOCATED AND SHALL
BE APPROVED BY THE COMPONENT DESIGNER PRIOR TO CURSORY
REVIEW BY THE ENGINEER OF RECORD FOR LOADS IMPOSED ON THE
BASIC STRUCTURE. THE COMPONENT DESIGNER IS RESPONSIBLE FOR
CODE CONFORMANCE AND ALL NECESSARY CONNECTIONS NOT
SPECIFICALLY CALLED OUT ON ARCHITECTURAL OR STRUCTURAL
DRAWINGS. SHOP DRAWINGS SHALL INDICATE MAGNITUDE AND
DIRECTION OF ALL LOADS IMPOSED ON BASIC STRUCTURE. DESIGN
CALCULATIONS SHALL BE INCLUDED IN THE SUBMITTAL.
WINTER CONSTRUCTION
1. ALL SOIL BELOW FOOTINGS SHALL BE PROTECTED FROM FREEZING BY
ALL NECESSARY MEANS (e.g. TEMPORARY HEAT AND BLANKETS,
TEMPERATURE PROBES, ETC.).
2. ALL CONCRETE SHALL BE PREVENTED FROM FREEZING AFTER
POURING, AS DIRECTTED BY THE CONCRETE SPECIAL INSPECTOR, BY
ALL NECESSARY MEANS (e.g. TEMPORARY HEAT, BLANKETS, ETC.).
3. ALL BACKFILL MUST BE PLACED ON UNFROZEN GROUND, IN UNFROZEN
STATE AND COMPACTED PER THE GEOTECHNICAL REPORT.
REF.
Wall Types
Exterior Wall Assemblies
A5.1 3
A5.1
A5.1
A5.1
1
4
2
N
1
meeting room
105
garage
100
A2.1
2
staff tlt
103
staff area
104
2
A6.1
52'-6"
1 1
9 9
7 7
A
A
B
B
6 6
1
A6.1
4
A6.1
103
100B
108
107
106
110 112
3
A6.1
mech/elec
101
storage
102
101
A2.1
1
102
99'-7"
8 8
6" 6" 8'-0" 22'-6" 1'-0"
14'-0" 15'-0" 23'-6"
26'-0" 26'-6"
8'-6"
9'-9"
1
8"
1'-0"
52'-6"
31'-6"
GIRT FACE
GIRT FACE GIRT FACE
2
9'-10"
FLOOR SLOPE FLOOR SLOPE
FLOOR SLOPE
FLOOR SLOPE
100'-0"
100'-0"
100'-0" 100'-0"
99'-7"
GIRT FRAMING
2 2
3 3
4 4
23'-9" 21'-0" 21'-0"
5 5
23'-0" 8'-6"
7'-3" 1'-5"
1'-4"
1
1
1
1
1
1
1
1
97'-3" 30'-6"
Toilet Rm
106
Utility
107
Toilet Rm
108
Hallway
109
Office
110
Storage
112
6'-0" 1'-0"
4'-0" 3'-4" 1'-2"
WD-W1
108A
100A
3'-4" 2'-6"
17'-4 3/8" 9'-5 1/8" 7'-3"
1'-5"
7'-2 1/2"
3'-3" 6'-11" 2'-6"
7A
7B
1"
1'-0"
6'-0" 6'-0" 3'-0" 3'-4" 3'-0" 6'-0" 16'-2" 6'-0" 3'-0"
105
109
WD-W1 WD-W1 WD-W1
EX2
EX1
EX2
EX2
EX1
EX1
A1 A2
A1 A2
3
4A
4A
5A
5A
4A
5A
4A
5A
2'-6" 3'-4" 2'-6" 16'-0"
15'-3 7/8" 5'-7"
3'-4" 10'-2" 7'-10 1/2"
13'-1 3/8"
9'-7"
5'-6"
4 4
4
4
4
4B
4B
5B 5B
7B
4
4
131'-5"
5
5
5
EXT WALL
TYPE TRANSITION
5
5
5
6
6
6
6
6
6
6
11'-3 7/8"
4'-0"
OH1
OH2
OH3
OH4
OH5
16'-0" 5'-0" 16'-0" 5'-0" 16'-0" 5'-0" 16'-0" 4'-6" 5'-3"
7
7
7
7
5B
8
8
8
8
8
9
9
9
9
9
9
4
-fd
-fd -fd
-fd
8 1/2" 8 1/2"
GIRT FACE
8
DAYLIGHT DT
DOWN GRADE;
SEE CIVIL &
STRUCTURAL
10
5A
3 5/8" METAL STUD @
16" O.C.
5/8" GYP.BD. EA. SIDE
BATT INSULATION
METAL STUD WALL TO ROOF
PMB STRUCTURE
5B 5/8" FIBERGLASS FACED MOISTURE REST.
GB. IN LIEU OF STANDARD GB.
3 5/8" METAL STUD
CHANNEL
BASE - SEE
SCHEDULE
CLG WHERE APPLICABLE;
SEE RCP
7A
6" METAL STUD
@ 16" O.C.
BATT INSULATION
6" METAL STUD CHANNEL
FLOOR STRUCTURE
5/8" FIBERGLASS FACED
MOISTURE REST. GB.
METAL STUD WALL TO
FLOOR STRUCTURE
4 7/8"
6 5/8"
SECTION
@ FLOOR
PLAN
VIEW
SECTION
@ HEAD
SECTION
@ FLOOR
PLAN
VIEW
SECTION
@ HEAD
4A
3 5/8" METAL STUD @
16" O.C.
5/8" GYP.BD.
METAL STUD WALL
GYPSUM BOARD ONE SIDE
CLG WHERE APPLICABLE;
SEE RCP
SECTION
@ FLOOR
PLAN
VIEW
SECTION
@ HEAD
STOP WALL 6" ABOVE CEILING
2"
CONT
DEFLECTION TRACK
3 5/8" STUD BLOCKING @ 4' -0" OC
FASTENED TO GIRTS
DOUBLE 3 5/8" STUD
FASTENED TO STUD BLOCKING
5/8" FIBERGLASS FACED MOISTURE REST.
GB. IN LIEU OF STANDARD GB.
4B
EX1 PRE -MANUFACTURED BUILDING
(PMB) WALL SYSTEM W/
INTERIOR LINER PANEL
GRID
PMB METAL WALL PANEL
8.5" PMB GIRTS
PMB FULL CAVITY
INSULATION SYSTEM
PMB METAL LINER
PANEL
INSULATION CONT.
VAPOR BARRIER
PMB OUTER
INSULATION SYSTEM
EX2 PRE -MANUFACTURED BUILDING
(PMB) WALL SYSTEM
GRID
PMB METAL WALL PANEL
8.5" PMB GIRTS
PMB FULL CAVITY
INSULATION SYSTEM
INSULATION CONT.
VAPOR BARRIER
PMB OUTER
INSULATION SYSTEM
THERMAL BLOCK THERMAL BLOCK
NOTE: INSULATION SYSTEM TO MEET REQUIREMENTS NOTED ON G1.1 LIFE
SAFETY & ENERGY CODE ANAYLSIS
Çê~ïå=ÄóW
ÅÜÉÅâÉÇ=ÄóW
éêáåíÉÇ=
å~ãÉW
êÉÖK=@W
ëáÖå=Ç~íÉW
Ç~íÉW
éêçàÉÅí=@W
ëÜÉÉí=íáíäÉW
ëÜÉÉí=
åìãÄÉêW
www.dsgw.com
John E. Erickson, NCARB, LEED AP
9676
3/10/2026 9:08:16 AM
025170.00
JMG
JMG
3/10/2026
Brule Public
Works
Garage
A2.0
Floor Plan
Town of Brule, Wisconsin
1/8" = 1'-0" A2.0
1 Floor Plan
Floor Plan Notes
1 8" O.D. Steel Pipe Bollard filled with concrete
2 12" Trench Drain -- See Mechanical
3 Fire Rated Metal Panel Wall by PMB Contractor
4 Fur Around Steel Frame - Leave 1" Clearance
5 P/F Metal PMB Downspout
6 24" x 36" x 4" Concrete Spash pad sloped 1/2"-12" Away from Building
7 Concrete Stoop @ 1/4"-12" down slope -- See Struct ural
8 4" Drain Tile - Drain to Daylight see Civil
9 PMB Structural Frame -- See PMB Documents
10 Coordinate blocking for gas meter and electrical CT cabinet with PEMB manufacturer êÉîáëáçå=L=áëëìÉ åçK Ç~íÉ
REF.
7
B
6
staff tlt
103
staff area
104
A2.1
3
5
6
A2.1 8
9
10
A2.1 12
13
14
A2.1
15
103
100B
108 106
107
4B
8A
5A
5A
5A
8
5
Toilet Rm
106
Toilet Rm
108
Hallway
109
Utility
107 4A
5A
5A
7'-3"
7'-11 3/8"
4B 5B
7A
7B
6'-6"
6'-6"
103
108A
1'-5" 17'-0 1/2"
2'-6"
1"
7B
EX1
EX2
A1 A2
EXTERIOR WALL
TYPE TRANSITION
PMB GIRT FRAMING
4
4
4'-9" 1'-6" 1'-6" 4'-9"
1'-4"
15"x15"x78" LOCKERS --
3 SUCH
4'-0" 1'-4"
7'-6" 6'-10 1/4" 7'-6"
5'-0"
5A
1'-11"
1'-11"
7' -2" HEAD AT OPNG
DRINKING
FTN
-fd
-fd -fd
A2.1 4
4
9
3
1
6" EPOXY BASE
(TYP)
7
103
6" EPOXY BASE
(TYP)
6
8
5
1 6" EPOXY BASE
(TYP)
1
4
9
3
6" EPOXY BASE
(TYP)
3
6
5
1
8
6" EPOXY BASE
(TYP)
5
7
106
6" EPOXY BASE
(TYP)
108
7
5
6" EPOXY BASE
(TYP)
5
8
6
1
6" EPOXY BASE
(TYP) 1
3
4
9
6" EPOXY BASE
(TYP)
3'-0"
2'-6" 4'-6"
W18 W30 W18
B18 SB30 B18
2'-10"
8'-0" SS COUNTER W/
4" BS
REFRIG
100B
103
102
101
FRP PANELS IN ALCOVE
LINER PANEL
SINK
EMERGENCY
EYE WASH
8" VINYL WALL BASE
IN ALCOVE
LINER PANEL TRIM
8" VB
STOP LINER
PANEL AT TOP
OF VB LINER PANEL TRIM
LINER PANEL
TOP OF PLATFORM
LINER PANEL TRIM
REFRIG N.I.C.
BY OWNER
COUNTER
BRACKET
WALL CLEAT
COUNTER ANCHOR
4" LOCKER BASE
BY LOCKER MTG.
SS COUNTER W/
4" B.S.
LOCKER
3 SUCH
6'-6" 4"
1'-3" 3'-6"
3'-0"
Çê~ïå=ÄóW
ÅÜÉÅâÉÇ=ÄóW
éêáåíÉÇ=
å~ãÉW
êÉÖK=@W
ëáÖå=Ç~íÉW
Ç~íÉW
éêçàÉÅí=@W
ëÜÉÉí=íáíäÉW
ëÜÉÉí=
åìãÄÉêW
www.dsgw.com
John E. Erickson, NCARB, LEED AP
9676
3/10/2026 9:08:17 AM
025170.00
JMG
JMG
3/10/2026
Brule Public
Works
Garage
A2.1
Enlarged Plans
& Interior
Elevations
Town of Brule, Wisconsin
1/4" = 1'-0" A2.1
1 Level 1 Enlarged Floor Plan
1/4" = 1'-0" A2.1
3 Toilet 103 - South
1/4" = 1'-0" A2.1
5 Toilet 103 - North
1/4" = 1'-0" A2.1
6 Toilet 103 - East
1/4" = 1'-0" A2.1
8 Toilet 106 - West
1/4" = 1'-0" A2.1
9 Toilet 106 - North
1/4" = 1'-0" A2.1
10 Toilet 106 - East
1/4" = 1'-0" A2.1
12 Toilet 108 - West
1/4" = 1'-0" A2.1
13 Toilet 108 - North
1/4" = 1'-0" A2.1
14 Toilet 108 - East
1/4" = 1'-0" A2.1
15 Lobby Kitchen
Fixtures & Accessories
1 TOILET - ADA
3 GRAB BARS
4 TOILET PAPER DISPENSER
5 SINK - ADA WITH PROTECTIVE SKIRT
6 24" X 36" MIRROR
7 PAPER TOWEL DISPENSER
8 SOAP DISPENSER
9 NAPKIN DISPOSAL
1/4" = 1'-0" A2.1
2 Garage - South
SEE SHEET G1.2 FOR MOUNTING LOCATIONS
1/4" = 1'-0" A2.1
4 Staff Area 104 - West
êÉîáëáçå=L=áëëìÉ åçK Ç~íÉ
Reflected Ceiling Plan Legend
1
2
A6.1
1
9
7
A B
6
1
A6.1
4
A6.1
3
A6.1
8
2
3
4
5
1
1" / 12" 1" / 12"
1" / 12" 1" / 12"
2
2
3
4
2
2
3
4
4
4
4
4
4
2
A6.1
1
A6.1
4
A6.1
8'-0" 8'-0"
8'-0"
8'-0"
8'-0" 8'-0"
garage
100
staff tlt
103
staff area
104
3
A6.1
8'-8"
8'-0"
5/8" GB ON BTM OF JSTS.
ALL EXPOSED ROOF AND WALL
STRUCTURE TO BE PAINTED
8'-6"
GYPSUM BOARD
SACT -1
2' -0" X 2' -0" SUSPENDED
ACOUSTICAL CEILING TILE
AND GRID
LIGHT FIXTURES - SEE ELECT
MECHANICAL FIXTURES - SEE
MECH
SACT -2
WASHABLE 2' -0" X 2' -0"
SUSPENDED ACOUSTICAL
CEILING TILE AND GRID
Çê~ïå=ÄóW
ÅÜÉÅâÉÇ=ÄóW
éêáåíÉÇ=
å~ãÉW
êÉÖK=@W
ëáÖå=Ç~íÉW
Ç~íÉW
éêçàÉÅí=@W
ëÜÉÉí=íáíäÉW
ëÜÉÉí=
åìãÄÉêW
www.dsgw.com
John E. Erickson, NCARB, LEED AP
9676
3/10/2026 9:08:18 AM
025170.00
JMG
Checker
3/10/2026
Brule Public
Works
Garage
A2.2
Roof Plan / RCP
Plan
Town of Brule, Wisconsin
Roof Plan General Notes
1 Flashing of all roof penetrations, equipment curbs and roofing materials installation to
follow manufacturers recommendations.
2 All Mechanical and Electrical rooftop equipment, p iping, conduit, etc. to be painted. All
M&E items on roof plan are for reference only. Refer to consultant drawings for size,
location and extent of equipment.
Roof Plan Notes
1 PMB Standing Seam Roof System; Insulation system to meet energy code requirements
as noted in G1.1 life safety analysis
2 PMB Metal Roof Edge
3 PMB Metal Gutter System Sized by Mfg.
4 PMB Metal Downspout System Sized by Mfg.
1/8" = 1'-0" A2.2
1 Roof Plan
1/8" = 1'-0" A2.2
2 Level 1 RCP
RCP General Notes
1. Coordinate final locations of ceiling mounted equ ipment w/ owner and architect.
2. See M&E drawings for lighting, grills, and diffus er locations.
3. Suspended acoustical ceiling tile grid is to be c entered in rectangular room or centered
between the longest walls of irregularly shaped rooms unless otherwise noted.
4. Verify gypsum board control joint locations with architect prior to installation.
5. Ceiling heights indicated are from finished floor of current level shown.
RCP Notes
êÉîáëáçå=L=áëëìÉ åçK Ç~íÉ
Door Types Frame Types Window Types
Glazing Types
HM-D1
Insulated
Hollow Metal
G1
HM-D3
Hollow Metal
WD-D1
Solid Core
Wood Flush
OH-D1
Overhead
Sectional Door
G1
G1
1'-6"
2'-0"
6" 6" 1'-6" 6" 1'-6"
HM-D2
Insulated
Hollow Metal
G1
G1
1'-6"
2'-0"
6" 6" 1'-6" FULL WDW
FULL WDW
3
A4.1
3
A4.1
5
A4.1 HM-F1
Hollow Metal
2" X 5 3/4"
2" Head
SEE SCHEDULE
SEE SCHED.
**All Exterior HM
Frames to be Filled w/
Foam Inulation
DIMENSIONS ARE ACTUAL SIZE -- FRAME OPENING SIZE PER MFG'S
RECOMENDATION
AL-W1
Aluminum -
Thermally Broken
6'-0"
4
A4.1
4
A4.1
4
A4.1
5'-0"
EQ EQ
EQ EQ
G3
G3
G3
G3
DIMENSIONS ARE ACTUAL SIZE -- FRAME OPENING SIZE PER MFG'S
RECOMENDATION
G1: 1" INSULATED, TEMPERED GLAZING
G2: 1/4" TEMPERED, CLEAR GLAZING
G3: 1" INSULATED GLAZING
G4: 1/4" CLEAR GLAZING
G5: FIRE -RATED SAFETY GLAZING
G6: 1" INSULATED, TEMPERED, SPANDREL GLAZING
G7: 1" INSULATED, SPANDREL GLAZING
G8: 1/2" TEMPERED, LAMINATED GLAZING
G9: BALLISTIC GLAZING
G10: 1" INSULATED, TEMPERED SILKSCREEN GLAZING
CONT. SEALANT BOTH SIDES
HM FRAME; SEE TYPES
LINTEL - SEE STRUCT.
5A
5A
CONT. SEALANT ALL SIDES
HM FRAME; SEE TYPES
(2) METAL STUDS @ JAMB
OVERHEAD DOOR
OVERHEAD DOOR
Head
Jamb
OH DOOR CONTR. TO
PROVIDE ALL STEEL STRUC
AS NEEDED FOR DOOR
ASSEMBLY ATTATCHMENT
OH DOOR CONTR. TO
PROVIDE ALL STEEL STRUC
AS NEEDED FOR DOOR
ASSEMBLY ATTATCHMENT
PANEL CLOSURE
PMB HEAD FLASHING
STL. OPENING FRAME
BY PMB
P/F MTL CLOSURE
CONT SEALANT
PMB WALL PANEL
PMB CLOSURE FLASHING
STL. OPENING FRAME
BY PMB
P/F MTL CLOSURE
PMB WALL PANEL
CONT SEALANT
INSTALL LINER PANEL AS
REQ'D TO FIT AROUND
OH DOOR FRAMING
INSTALL LINER PANEL AS
REQ'D TO FIT AROUND
OH DOOR FRAMING
CONT SEALANT
Head
Jamb
PMB Wall
PANEL CLOSURE
PMB HEAD FLASHING
STL. OPENING FRAME
BY PMB
P/F MTL CLOSURE
CONT SEALANT
FULL SPRAY FOAM INSUL
CONT SEALANT OUTSIDE/INSIDE
P/F MTL CLOSURE
PMB LINER PANEL
PMB WALL PANEL
PANEL CLOSURE
PMB CLOSURE FLASHING
STL. OPENING FRAME
BY PMB
P/F MTL CLOSURE
FULL SPRAY FOAM INSUL
CONT SEALANT OUTSIDE/INSIDE
P/F MTL CLOSURE
PMB LINER PANEL
PMB WALL PANEL
CONT SEALANT
O.H. GARAGE DOOR
CAULK W/ BACKER ROD
CONC APRON - SEE STRUCT
1/2" EXPANSION JOINT SLOPE
R-20 RIGID INSULATION
R-20 RIGID
INSULATION
COMPACTED SAND BASE
Head
Jamb
PANEL CLOSURE
PMB HEAD FLASHING
STL. OPENING FRAME
BY PMB
P/F MTL CLOSURE
CONT SEALANT
CONT SPRAY FOAM INSUL
AROUIND PERIMETER
GB WALL FURRING
PMB WALL PANEL
PANEL CLOSURE
PMB CLOSURE FLASHING
STL. OPENING FRAME
BY PMB
P/F MTL CLOSURE
PMB WALL PANEL
RETURN GB TO FRAME AND
FINISH WITH J -BEAD
GB WALL FURRING
RETURN GB TO FRAME AND
FINISH WITH J -BEAD
CONT SPRAY FOAM INSUL
AROUIND PERIMETER
Sill
PANEL CLOSURE
PMB SILL FLASHING
STL. OPENING FRAME
BY PMB
CONT SEALANT OUTSIDE/INSIDE
PMB WALL PANEL
GB WALL FURRING
CONT SPRAY FOAM INSUL
AROUIND PERIMETER
S0LID SURFACE SILL
SEALANT
SEALANT
SEALANT
CONT SEALANT
OUTSIDE/INSIDE
CONT SEALANT
OUTSIDE/INSIDE
CONT SEALANT
CONT SEALANT
Head
Jamb
PMB Wall w/ GB Wall
PANEL CLOSURE
PMB HEAD FLASHING
STL. OPENING FRAME
BY PMB
P/F MTL CLOSURE
CONT SEALANT
FULL SPRAY FOAM INSUL
CONT SEALANT FRONT/BACK
GB WALL FURRING
PMB WALL PANEL
PANEL CLOSURE
PMB CLOSURE FLASHING
STL. OPENING FRAME
BY PMB
P/F MTL CLOSURE
FULL SPRAY FOAM INSUL
CONT SEALANT FRONT/BACK
PMB WALL PANEL
CONT SEALANT RETURN GB TO HM AND
FINISH WITH J -BEAD
GB WALL FURRING
RETURN GB TO HM AND
FINISH WITH J -BEAD
CONT SEALANT
Çê~ïå=ÄóW
ÅÜÉÅâÉÇ=ÄóW
éêáåíÉÇ=
å~ãÉW
êÉÖK=@W
ëáÖå=Ç~íÉW
Ç~íÉW
éêçàÉÅí=@W
ëÜÉÉí=íáíäÉW
ëÜÉÉí=
åìãÄÉêW
www.dsgw.com
John E. Erickson, NCARB, LEED AP
9676
3/10/2026 9:08:19 AM
025170.00
JMG
JMG
3/10/2026
Brule Public
Works
Garage
A4.1
Schedules and
Types
Town of Brule, Wisconsin
ROOM FINISH SCHEDULE
NO. NAME
FLOOR WALL FINISH
NOTES FINISH BASE NORTH EAST SOUTH WEST
100 garage SEALED CONCRETE **8" VB Liner Panel Liner Pan el Liner Panel Liner Panel Install south wall liner pa nel ovver 5/8" gb; **8" VB only on South Wall
101 mech/elec SEALED CONCRETE 4" VB PNT PNT PNT Liner Pane l
102 storage SEALED CONCRETE -- FRP FRP FRP FRP
103 staff tlt EPOXY 6" Epoxy Epoxy PNT Epoxy PNT Epoxy PN T Epoxy PNT
104 staff area SEALED CONCRETE 4" VB PNT Liner Panel PNT P NT No wall base at liner panel
105 meeting room VCT 4" VB PNT PNT PNT PNT
106 Toilet Rm EPOXY 6" Epoxy Epoxy PNT Epoxy PNT Epoxy PN T Epoxy PNT
107 Utility VCT 4" VB PNT PNT PNT PNT
108 Toilet Rm EPOXY 6" Epoxy Epoxy PNT Epoxy PNT Epoxy PN T Epoxy PNT
109 Hallway VCT 4" VB PNT PNT PNT PNT
110 Office VCT 4" VB PNT PNT PNT PNT
111 Secure Str VCT 4" VB PNT PNT PNT PNT
112 Storage VCT 4" VB PNT PNT PNT PNT
DOOR AND FRAME SCHEDULE
DOOR FRAME
FIRE
LABEL
HDW.
NO. NOTES NO. WIDTH HEIGHT TYPE TYPE
DETAIL
HEAD JAMB SILL
100A 3'-0" 7'-0" HM-D2 HM-F1 1/A4.1 1/A4.1 -- 01
100B 3'-0" 7'-0" HM-D2 HM-F1 1/A4.1 1/A4.1 -- 01
101 3'-0" 7'-0" HM-D3 HM-F1 6/A4.1 6/A4.1 -- 03
102 3'-0" 7'-0" HM-D3 HM-F1 6/A4.1 6/A4.1 -- 03
103 3'-0" 7'-0" HM-D3 HM-F1 6/A4.1 6/A4.1 -- 06
105 3'-0" 7'-0" HM-D1 HM-F1 2/A4.1 2/A4.1 -- 02
106 3'-0" 7'-0" WD-D1 HM-F1 6/A4.1 6/A4.1 -- 06
107 3'-0" 7'-0" WD-D1 HM-F1 6/A4.1 6/A4.1 -- 03
108 3'-0" 7'-0" WD-D1 HM-F1 6/A4.1 6/A4.1 -- 01
108A 3'-0" 7'-0" HM-D1 HM-F1 1/A4.1 1/A4.1 -- 01
109 3'-0" 7'-0" HM-D1 HM-F1 2/A4.1 2/A4.1 -- 02
110 3'-0" 7'-0" WD-D1 HM-F1 6/A4.1 6/A4.1 -- 05
112 6'-0" 7'-0" WD-D1 HM-F1 6/A4.1 6/A4.1 -- 04
OH1 16'-0" 16'-0" OH-D1 3/A4.1 3/A4.1 5/A4.1 High Lift Bre akaway Track
OH2 16'-0" 16'-0" OH-D1 3/A4.1 3/A4.1 5/A4.1 High Lift Bre akaway Track
OH3 16'-0" 16'-0" OH-D1 3/A4.1 3/A4.1 5/A4.1 High Lift Bre akaway Track
OH4 16'-0" 16'-0" OH-D1 3/A4.1 3/A4.1 5/A4.1 High Lift Bre akaway Track
OH5 16'-0" 16'-0" OH-D1 3/A4.1 3/A4.1 5/A4.1 - 15" Radius T rack
1 1/2" = 1'-0" A4.1
6 Door - HM Interior Detail
1 1/2" = 1'-0" A4.1
3 Door - OH Door Details
1 1/2" = 1'-0" A4.1
1 Door - HM Exterior Detail
1 1/2" = 1'-0" A4.1
5 Door - Overhead Door @ Grade
1 1/2" = 1'-0" A4.1
4 Window - Alum Detail
1 1/2" = 1'-0" A4.1
2 Door - HM Exterior Detail
êÉîáëáçå=L=áëëìÉ åçK Ç~íÉ
Level 1
100' -0"
Garage T/O Girt
121' -0"
Office T/O Girt
111' -0"
AB
12
3
4
6
7
20'-0"
5
A5.1 12
5
A5.1
sim
T/O GRADE
4
10
13 13
11
16'-0"
1"
12"
Level 1
100' -0"
Garage T/O Girt
121' -0"
9
Office T/O Girt
111' -0"
A B
1
2
6
6
1
7
7
T/O GRADE
11
10
5
A5.1 12
8'-0"
WD-W1 WD-W1
105
WD-W1
1"
12"
1"
12"
7'-2"
7'-2"
Level 1
100' -0"
Garage T/O Girt
121' -0"
1
19 7
6
1
A6.1
4
A6.1
3
A6.1
8
2
3
4
5 6
6
9
222
22
1
2
2345
5'-6"
WD-W1
109 108A
OH1 OH2 OH3 OH4
10
11
T/O GRADE
10
5
A5.1 12
5
A5.1 12
5
A5.1
SIM
12
13
13
13
8'-0"
Level 1
100' -0"
Garage T/O Girt
121' -0"
Office T/O Girt
111' -0"
1 97
6
1
A6.1
4
A6.1
3
A6.1
8
1
7
7
8
8
1
2 3 4 5
10
13
13
13
11 11
T/O GRADE
4
14
1
14
14
Çê~ïå=ÄóW
ÅÜÉÅâÉÇ=ÄóW
éêáåíÉÇ=
å~ãÉW
êÉÖK=@W
ëáÖå=Ç~íÉW
Ç~íÉW
éêçàÉÅí=@W
ëÜÉÉí=íáíäÉW
ëÜÉÉí=
åìãÄÉêW
www.dsgw.com
John E. Erickson, NCARB, LEED AP
9676
3/10/2026 9:08:20 AM
025170.00
JMG
JMG
3/10/2026
Brule Public
Works
Garage
A5.1
Exterior
Elevations
Town of Brule, Wisconsin
Exterior Elevation Notes
1 Insulated Metal Panel Type-1 Color #A
2 Insulated Metal Panel Type-2 Color #B
3 Overhead Door
4 8" Pipe Bollard Embedd in 16" DIA Conc Pier to 48" below grade; Fill Pipe Solid
with Concrete
5 Metal Signage; 24" High --
6 PMB Metal Roof Edge --
7 PMB Metal Roof Gutter - Sized by PMB mfg. --
8 PMB Standing Seam Roof System --
9 Aluminum Window --
10 Concrete Foundation - See Structural --
11 Prefinished Metal Insulation Closure
12 P/F Metal Wall Panel Flashing
13 PMB Metal Corner Trim - Match Siding Color --
14 PMB Metal Downspout- sized by PMB mfg. --
1/8" = 1'-0" A5.1
1 North Elevation
1/8" = 1'-0" A5.1
2 South Elevation
1/8" = 1'-0" A5.1
3 East Elevation
1/8" = 1'-0" A5.1
4 West Elevation
êÉîáëáçå=L=áëëìÉ åçK Ç~íÉ
Çê~ïå=ÄóW
ÅÜÉÅâÉÇ=ÄóW
éêáåíÉÇ=
å~ãÉW
êÉÖK=@W
ëáÖå=Ç~íÉW
Ç~íÉW
éêçàÉÅí=@W
ëÜÉÉí=íáíäÉW
ëÜÉÉí=
åìãÄÉêW
www.dsgw.com
John E. Erickson, NCARB, LEED AP
9676
3/10/2026 9:08:21 AM
025170.00
JMG
JMG
3/10/2026
Brule Public
Works
Garage
A5.2
Exterior
Elevations 3D
Town of Brule, Wisconsin
A5.2
1 3D NW View
A5.2
2 3D SE View
êÉîáëáçå=L=áëëìÉ åçK Ç~íÉ
Level 1
100' -0"
Garage T/O Girt
121' -0"
Office T/O Girt
111' -0"
1 97
6
1
A6.1
4
A6.1
3
A6.1
A6.2
3
A6.2
2
8
T/O Wall Brg
110' -0"
2 3 4 5
A6.2
2 Sim
Level 1
100' -0"
Garage T/O Girt
121' -0"
2
A6.1
A B
A6.2
1
A6.2
4
Level 1
100' -0"
Office T/O Girt
111' -0"
2
A6.1
A B
1"
12"
A6.1
6
A6.1
5
Level 1
100' -0"
Garage T/O Girt
121' -0"
2
A6.1
AB
T/O Wall Brg
110' -0"
LINER PANEL
3-HR FIRE PANEL Level 1
100' -0"
Office T/O Girt
111' -0"
B
PMB ROOF GIRTS
PMB LS -ROOF DOUBLE LAYER
INSULATION SYSTEM
PMB ROOF FASCIA
PMB METAL ROOF SYSTEM
CONC FDN -SEE STRUC
P/F METAL INSULATION
COVER TO 6" BELOW GRADE
GRADE
R-20 RIGID INSULATION
EX2
4" DIA DRAIN TILE --
DAYLIGHT TO DRAIN
PEA GRAVEL BASE COVERED
WITH FILTER FABRIC -- INSTALL
LEVEL ON SOLID SOIL
CONC FLR -- SEE STRUC
2" RIGID INSUL OVER V.B.
4'-0"
11'-0"
4A
1"
12"
Level 1
100' -0"
Office T/O Girt
111' -0"
A
PMB ROOF GIRTS
PMB LS -ROOF DOUBLE LAYER
INSULATION SYSTEM
PMB ROOF GUTTER
PMB METAL ROOF SYSTEM
CONC FDN -SEE STRUC
P/F METAL INSULATION
COVER TO 6" BELOW
GRADE
GRADE
R-20 RIGID INSULATION
EX2
11'-0"
4" DIA DRAIN TILE --
DAYLIGHT TO DRAIN
PEA GRAVEL BASE COVERED
WITH FILTER FABRIC -- INSTALL
LEVEL ON SOLID SOIL
4'-0"
1"
12"
CONC FLR -- SEE STRUC
2" RIGID INSUL OVER V.B.
Çê~ïå=ÄóW
ÅÜÉÅâÉÇ=ÄóW
éêáåíÉÇ=
å~ãÉW
êÉÖK=@W
ëáÖå=Ç~íÉW
Ç~íÉW
éêçàÉÅí=@W
ëÜÉÉí=íáíäÉW
ëÜÉÉí=
åìãÄÉêW
www.dsgw.com
John E. Erickson, NCARB, LEED AP
9676
3/10/2026 9:08:23 AM
025170.00
JMG
JMG
3/10/2026
Brule Public
Works
Garage
A6.1
Building
Sections & Wall
Sections
Town of Brule, Wisconsin
1/8" = 1'-0" A6.1
2 Section N-S
1/8" = 1'-0" A6.1
3 Section @ Garage
1/8" = 1'-0" A6.1
1 Section @ Office
1/8" = 1'-0" A6.1
4 Section @ Garage Platform
1/2" = 1'-0" A6.1
6 Seciton - Office High
1/2" = 1'-0" A6.1
5 Section - Office Low
êÉîáëáçå=L=áëëìÉ åçK Ç~íÉ
Level 1
100' -0"
Garage T/O Girt
121' -0"
1
21'-0"
PMB METAL WALL
PANEL
PMB ROOF GIRTS
PMB LS -ROOF DOUBLE LAYER
INSULATION SYSTEM
PMB FRAME
PMB ROOF FASCIA
PMB METAL ROOF SYSTEM
EX1
P/F METAL
INSULATION
COVER TO 6"
BELOW GRADE
GRADE
R-20 RIGID INSULATION
CONC FLOOR -SEE STRUC
4" DIA DRAIN TILE --
DAYLIGHT TO DRAIN
PEA GRAVEL BASE COVERED
WITH FILTER FABRIC -- INSTALL
LEVEL ON SOLID SOIL
Level 1
100' -0"
Garage T/O Girt
121' -0"
A
PMB ROOF GIRTS
PMB LS -ROOF DOUBLE LAYER
INSULATION SYSTEM
PMB ROOF GUTTER
PMB METAL ROOF SYSTEM
CONC FDN -- SEE
STRUC
2" RIGID INSUL OVER
CONT V.B.
GRAN BASE -
SEE STRUC
P/F METAL INSULATION
COVER TO 6" BELOW GRADE
GRADE
R-20 RIGID INSULATION
21'-0"
EX1
4'-0"
4" DIA DRAIN TILE --
DAYLIGHT TO DRAIN
PEA GRAVEL BASE COVERED
WITH FILTER FABRIC -- INSTALL
LEVEL ON SOLID SOIL
1"
12"
4'-0"
Level 1
100' -0"
Garage T/O Girt
121' -0"
B
21'-0"
CONC APRON -- SEE STRUC
PIPE BOLLARD
OH DOOR
R-20 RIGID INSULATION
CONC FDN -SEE STRUC
EX1
PMB METAL WALL
PANEL
PMB ROOF GIRTS
PMB LS -ROOF DOUBLE
LAYER INSULATION
SYSTEM
PMB ROOF FASCIA
PMB METAL ROOF SYSTEM
4" DIA DRAIN TILE --
DAYLIGHT TO DRAIN
PEA GRAVEL BASE COVERED
WITH FILTER FABRIC -- INSTALL
LEVEL ON SOLID SOIL
Level 1
100' -0"
Garage T/O Girt
121' -0"
76
T/O Wall Brg
110' -0"
3-HR FIRE RATED CLOSURE
TO ROOF DECK --
BY PMB CONTR.
PMB METAL WALL PANEL
PMB ROOF GIRTS
PMB LS -ROOF INSULATION SYSTEM
PMB ROOF GIRTS
LS ROOF INSULATION SYSTEM
FIRE BARRIER PANEL TO
BE SUPPORTED OFF GRID -7
PMB FRAME
PMB FRAME
PMB FRAME
PMB ROOF GIRTS
ROOF FLASHING BY
PMB CONTR.
6"
1" 6"
CONT 16 GA. MTL
CLOSURE
ANCHORED TO GIRTS AND
FIRE SAFED TO ROOF
DECK
3-HR FIRE PANEL CONT FROM
FLOOR TO BOTTOM OF
ROOF DECK -- BY PMB CONTR.
6" HIGH LAYER CONT.
R-24 SPRAY FOAM
INSUL
7B
4A
10'-0"
PMB METAL LINER PANEL
FLOOR SYSTEM -
SEE STRUC
3/4" T&G DECK
GLUED AND SCREWED
EX1
FTG -- SEE STRUC
21'-0"
PANEL CLOSURE
PMB HEAD FLASHING
STL. SUB FRAME
BY PMB
CONT SEALANT
PMB WALL PANEL
PANEL CLOSURE
PMB CLOSURE
PMB WALL GIRT
Çê~ïå=ÄóW
ÅÜÉÅâÉÇ=ÄóW
éêáåíÉÇ=
å~ãÉW
êÉÖK=@W
ëáÖå=Ç~íÉW
Ç~íÉW
éêçàÉÅí=@W
ëÜÉÉí=íáíäÉW
ëÜÉÉí=
åìãÄÉêW
www.dsgw.com
John E. Erickson, NCARB, LEED AP
9676
3/10/2026 9:08:24 AM
025170.00
JMG
JMG
3/10/2026
Brule Public
Works
Garage
A6.2
Wall Sections
Town of Brule, Wisconsin
1/2" = 1'-0" A6.2
3 Section - Fire Barrier
1/2" = 1'-0" A6.2
2 Seciton - Gable Wall
1/2" = 1'-0" A6.2
1 Section - Garage Low
1/2" = 1'-0" A6.2
4 Seciton - Garage High
1 1/2" = 1'-0" A6.2
5 Wall - Siding Flashing Detail
êÉîáëáçå=L=áëëìÉ åçK Ç~íÉ
M
M
VD
VD
BDD
FD
SD
M
FSD
VD
REFER TO LIFE SAFETY PLANS FOR LOCATIONS AND RATINGS OF W ALL TYPES.
SMOKE PARTITION
SMOKE DAMPERS REQUIRED AT TRANSFER AIR OPENINGS ONLY.
FIRE BARRIERS (1 -HR)
1.5 -HR FIRE DAMPER REQUIRED AT TRANSFER AIR OPENINGS ONLY. DUCTS SHALL NOT PENETRATE
EXIT PASSAGEWAY OR STAIRWAY ENCLOSURE.
SMOKE BARRIER (1 -HR)
SMOKE DAMPERS REQUIRED AT ALL DUCT PENETRATIONS. TRANSFER AIR OPENINGS REQUIRE A 1.5 -HR
COMBINATION FIRE/SMOKE DAMPER.
FIRE BARRIER (2 -HR)
1.5 -HR FIRE DAMPER AT ALL DUCT PENETRATIONS.
FIRE/SMOKE BARRIER (2 -HR)
1.5 -HR COMBINATION FIRE/SMOKE DAMPERS ARE REQUIRED AT ALL DUCT PENETRATIONS.
SHAFT ENCLOSURES:
1.5 -HOUR COMBINATION FIRE/SMOKE DAMPER IS REQUIRED AT EACH PENETRATION OF A SHAFT
ENCLOSURE. IF THE SHAFT DOES NOT EXTEND ALL THE WAY TO THE BOTTOM OF THE BUILDING, PLACE
A HORIZONTAL FIRE/SMOKE DAMPER AT THE FLOOR LEVEL WHERE THE DUCT EMERGES FROM THE
BOTTOM OF THE SHAFT.
LIFE SAFETY NOTES
Ø ROUND
AC AIR CONDITIONING
ADD ADDENDUM
AFF ABOVE FINISHED FLOOR
AFUE ANNUAL FUEL UTILIZATION EFFICIENCY
ALT ALTERNATE
AP ACCESS PANEL
ARCH ARCHITECT/ARCHITECTURAL
BFF BELOW FINISHED FLOOR
BTU BRITISH THERMAL UNITS
BTUH BRITISH THERMAL UNITS PER HOUR
CAP CAPACITY
CFM CUBIC FEET PER MINUTE
CO CLEAN OUT
D DEGREE
DB DRY BULB
DIA DIAMETER
DN DOWN
EAT ENTERING AIR TEMPERATURE
ELEC ELECTRICAL
EQUIP EQUIPMENT
EWC ELECTRIC WATER COOLER
EWT ENTERING WATER TEMPERATURE
E/A EXHAUST AIR
(E) EXISTING
°F DEGREES FAHRENHEIT
FD FIRE DAMPER
FL FLOOR
FO FUEL OIL
FOV FUEL OIL VENT
FOR FUEL OIL RETURN
FOS FUEL OIL SUPPLY
FPM FEET PER MINUTE
FS FLOOR SINK
FT FOOT/FEET
GAL GALLON
GC GENERAL CONTRACTOR
GPM GALLONS PER MINUTE
HP HORSE POWER
ID INDIRECT
IN INCH
INV INVERT
LB POUND
LB/HR POUNDS PER HOUR
LAT LEAVING AIR TEMPERATURE
LP LOW PRESSURE
LPG LIQUEFIED PETROLEUM GAS
LVR LOUVER
LWT LEAVING WATER TEMPERATURE
M/A MIXED AIR
MAX MAXIMUM
ABBREVIATIONS
MBH ONE THOUSAND BTU PER HOUR
MCF ONE THOUSAND CUBIC FEET
MD MOTORIZED DAMPER
MECH MECHANICAL
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MUA MAKE -UP/AIR
NC NOISE CRITERIA
NC NORMALLY CLOSED
NIC NOT IN CONTRACT
NO NUMBER
NO NORMALLY OPEN
NTS NOT TO SCALE
O OXYGEN
O/A OUTSIDE AIR
PD PRESSURE DROP
PRESS PRESSURE
PRV PRESSURE REDUCING VALVE
PSI POUNDS PER SQUARE INCH
PSIG POUNDS PER SQUARE INCH GAUGE
PWR POWER
(R) RELOCATE
R/A RETURN AIR
RCP RADIANT CEILING PANEL
REC RECESSED
RED REDUCER
RH RELATIVE HUMIDITY
RL/A RELIEF AIR
RM ROOM
RPM REVOLUTIONS PER MINUTE
SF SQUARE FOOT
S/A SUPPLY AIR
SF SQUARE FOOT
SD SMOKE DAMPER
SM SURFACE MOUNT
SP STANDPIPE
SP STATIC PRESSURE
STM STEAM
T THERMOSTAT
TD TEMPERATURE DROP
TEMP TEMPERATURE
TYP TYPICAL
UG UNDERGROUND
VAC VACUUM
V VENT
VAV VARIABLE AIR VOLUME
VENT VENTILATION
WB WET BULB
(X) DEMOLISH
GENERAL SYMBOLS
DETAIL/PLAN CALLOUT
REVISION CLOUD
REVISION TAG
KEYNOTE 1
X
XXX
X
NORTH ARROW
N
MATCHLINE
POINT OF CONNECTION
POINT OF DEMOLITION
CONTINUATION SYMBOL
AREA TO BE DEMOLISHED
AREA NOT IN CONTRACT
HVAC SYMBOLS & TAGS
T THERMOSTAT
TH TEMPERATURE & HUMIDITY
SENSOR
HS HUMIDITY SENSOR
MS MANUAL SWITCH
S SENSOR
H HUMIDISTAT
CO2 CARBON DIOXIDE (CO 2) SENSOR
NO2 NITROGEN DIOXIDE (NO 2) SENSOR
CO CARBON MONOXIDE (CO) SENSOR
DOOR UNDERCUT U
EQUIPMENT TAG
SIZE
TYPE
CFM
AHU-101
DIFFUSER TAG
PIPING SYSTEMS
REF
CD
REFRIGERANT
CONDENSATE DRAIN
G NATURAL GAS
HEAT PUMP UNIT/ENERGY RECOVERY UNIT SYSTEMS
SYSTEMS COMPRISED OF HEAT PUMPS AND ENERGY RECOVERY VENTILATORS SHALL OPERATE AS
FOLLOWS:
1. VENTILATION: ENERGY RECOVERY VENTILATORS SHALL PROVIDE VENTILATI ON DURING
OCCUPIED HOURS PER TIME -CLOCK OR OCCUPANCY SENSOR. A DUCT HEATER SHALL PREHEAT
OUTSIDE AIR AS NEEDED TO ACHIEVE THE SPECIFIED MINIMUM AIR TEMPE RATURE DELIVERED
INTO THE CONDITIONED SPACE.
2. CONDITIONING: CONDITIONING OF AIR TO BE ACCOMPLISHED V IA A ZONE THERMOSTAT.
THERMOSTAT SHALL INCLUDE CODE REQUIRED DEAD BAND BETWEEN SETPOIN TS. UPON A
CALL FOR HEATING OR COOLING, THE HEAT PUMP WILL BE ENERGIZED AND OPERATE TO
MAINTAIN SPACE TEMPERATURE SETPOINT.
GARAGE EXHAUST SYSTEMS
1. FANS TO BE INTERLOCKED WITH CO AND NO2 SENSORS.
2. FANS SHALL RUN AT MINIMUM TURNDOWN CFM AT ALL TIMES.
A. CO SENSOR - FANS RAMP TO MAX CAPACITY ONCE A VALUE OF 35 PPM IS DETECTED AND
OPERATE UNTIL CO LEVELS DROP BELOW 25 PPM BEFORE RETURNING TO MINIMUM TURNDOWN
CFM.
B. NO2 SENSOR - FANS RAMP TO MAX CAPACITY ONCE A VALUE OF 5 PPM IS DETECTED AND
OPERATE UNTIL NO2 LEVELS DROP BELOW 1 PPM BEFORE RETURNING TO MINIMUM TURNDOWN
CFM.
CONTROL SEQUENCE OF OPERATION
BUILDING DESCRIPTION
NEW CONSTRUCTION OF A PUBLIC WORKS GARAGE FOR TOWN OF BRULE, CONSISTING
OF APPROXIMATELY 6,000 SF. THE PROJECT IS LOCATED IN BRULE, WI.
NOTABLE MECHANICAL DESIGN APPROACHES
INCLUDING BUT NOT LIMITED TO THE FOLLOWING:
OFFICE SPACES:
• VENTILATION: HEAT RECOVERY VENTILATORS IN AMENITY SPACE.
• HEATING AND COOLING: DUCTED FAN COIL UNIT SPLIT SYSTEM.
GARAGE ROOM:
• VENTILATION: SIDE WALL EXHAUST FAN AND INTAKE LOUVER.
• HEATING ONLY VIA GAS UNIT HEATER.
ELEVATOR ROOM:
• COOLING VIA MINI -SPLIT AC.
CODES AND STANDARDS
BUILDING MECHANICAL SYSTEMS ARE DESIGN IN ACCORDANCE WITH THE FOLLOWING
CODES AND STANDARDS:
• 2021 WISCONSIN BUILDING CODE
• 2021 WISCONSIN MECHANICAL CODE
• 2021 WISCONSIN ENERGY CODE (2019 ASHRAE 90.1)
• 2023 WISCONSIN PLUMBING CODE
• 2021 WISCONSIN FIRE CODE
HVAC DESIGN CRITERIA
SUPERIOR BONG
ASHRAE FUNDAMENTALS 2021
ELEVATION: 674'
LAT: 46.689 N
LONG: 92.094 W
OUTDOOR DESIGN CONDITIONS
WINTER: -14.7°F DB (99.6%)
SUMMER: 90.8°F DB (0.4%)
74.9°F WB (0.4%)
INDOOR DESIGN CONDITIONS
OFFICE SPACES
COOLING: 75°F +/ - 2°F
HEATING: 70°F +/ - 2°F
HEATING -ONLY SPACES
GARAGE: 50°F +/ - 2°F
VENTILATION CRITERIA
COMPLY WITH 2021 WISCONSIN STATE MECHANICAL CODE CHAPTER 4 VIA 403.3.1.1
EXHAUST CRITERIA (MINIMUM RATES)
PUBLIC RESTROOMS: PER WATER CLOSET / URINAL AS PER IMC
PARKING GARAGE: 0.06 CFM/FT 2 MIN. / 0.75 CFM/FT 2 MAX.
BUILDING ENVELOPE
ROOF: R-30 CI (U -0.032)
STEEL FRAMED WALLS: R-13 + R -12.5 c.i. (U -0.049)
6” WOOD FRAMED WALLS: R-13 + R -7.5 c.i. (U -0.051)
MASS WALLS: R-13.3 CI (U -0.080)
UNHEATED SLAB: F-0.510
SWINGING DOOR: U-0.370
NONSWINGING DOOR: U-0.310
FIXED WINDOW: U-0.34
OPERABLE WINDOW: U-0.42
DUCTWORK DESIGN CRITERIA
DUCT STATIC PRESSURE FRICTION LOSS SHALL NOT EXCEED THE FOLLOWING:
• LOW PRESSURE SUPPLY: 0.08" W.C. PER 100 FEET
• MEDIUM PRESSURE SUPPLY: 0.1" W.C. PER 100 FEET
• LOW PRESSURE RETURN AND EXHAUST: 0.06" W.C. PER 100 FEET
• MECHANICAL ROOMS AND SHAFTS: 0.2" W.C. PER 100 FEET
SUPPLY, RETURN AND EXHAUST DUCT AIRFLOW VELOCITIES SHALL NOT EXCEED THE
FOLLOWING:
• MAINS ABOVE CEILING: 1,750 FPM
• MAINS ABOVE OPEN OCCUPIED SPACES: 1450 FPM
• BRANCHES ABOVE OPEN OCCUPIED SPACES: 1150 FPM
• RUN -OUTS TO DIFFUSERS: 725 FPM
• IN SHAFTS: 2,500 FPM
• IN MECHANICAL ROOMS: 3,000 FPM
MECHANICAL BASIS OF DESIGN
PIPE ACCESSORIES
BALANCING VALVE
BALL VALVE
BUTTERFLY VALVE
CHECK VALVE
GATE VALVE
GLOBE VALVE
LOCKED SHIELD VALVE
PLUG VALVE
PRESSURE REDUCING VALVE
QUICK OPENING VALVE
FLUID STRAINER
MOTORIZED 2 -WAY VALVE
MOTORIZED 3 -WAY VALVE
HOSE BIBB
DUCTWORK LEGEND
MITERED ELBOW
36x18 S/A 30x18 S/A
SC -1
400
DUCT END CAP
10"Ø S/A
24x18 S/A 20x18 S/A
BEVELED FITTING
DUCT MOUNTED DIFFUSER
BALANCE DAMPER
DUCT REDUCER
CEILING DIFFUSER
DUCT SYSTEMS
24x18 S/A 23 - SUPPLY AIR
23 - RETURN AIR
23 - OUTSIDE AIR
23 - CONDITIONED OUTSIDE AIR 24x18 S -O/A
23 - EXHAUST AIR
23 - FLUE GAS VENT
24"Ø C/A 23 - COMBUSTION AIR
24x18 R/A
24x18 O/A
24x18 E/A
24x18 FLUE
DOWN UP
WALL MOUNTED DIFFUSER
DUCT ACCESSORIES
BACKDRAFT DAMPER
FIRE DAMPER
MOTORIZED DAMPER
SMOKE DAMPER
FIRE SMOKE DAMPER
VOLUME DAMPER
1. THESE DRAWINGS ARE DIAGRAMMATIC IN NATURE AND INDICATE THE GENERAL ARRANGEMENT OF
SYSTEMS AND EQUIPMENT. FINAL LOCATIONS OF EQUIPMENT SHALL BE FIELD DETERMINED. ALL
DISCREPANCIES IN THE DRAWINGS SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT IN
WRITING PRIOR TO SUBMISSION.
2. COORDINATE INSTALLATION OF PIPING, DUCTWORK, CONDUIT, LIGHTS, CABLE TRAY, STRUCTURE,
AND EQUIPMENT TO PREVENT CONFLICTS.
3. THE CONTRACTOR SHALL BE FAMILIAR WITH ALL THE CONDITIONS ILLUSTRATED BY THESE
DOCUMENTS AS WELL AS THOSE WHICH CAN BE REASONABLY ANTICIPATED INCLUDING, BUT NOT
LIMITED TO ARCHITECTURAL, ELECTRICAL, VENTILATION, PLUMBING, AND OTHER SYSTEMS
INVOLVED ON THIS PROJECT.
4. FINAL PRODUCT SHALL BE A COMPLETE AND FUNCTIONING SYSTEM, AND SHALL CONFORM TO ALL
REQUIREMENTS OF APPLICABLE FEDERAL, STATE AND LOCAL CODES, INCLUDING BUT NOT LIMITED
TO THE INTERNATIONAL BUILDING CODE AND INTERNATIONAL MECHANICAL CODE.
5. EQUIPMENT FOR OTHER DISCIPLINES MAY BE SHOWN FOR REFERENCE ONLY. REFER TO OTHER
DISCIPLINES' DRAWINGS FOR MORE DETAIL REGARDING EQUIPMENT SPECIFICATIONS AND
INFORMATION.
6. PLANS SHALL GOVERN IN MATTERS OF QUANTITY, SPECIFICATIONS SHALL GOVERN IN MATTERS
OF QUALITY. IN CASE OF DISCREPANCY BETWEEN DRAWINGS AND SPECIFICATIONS, THE
SPECIFICATIONS SHALL GOVERN. PLANS ARE TO BE TIED TO SPECIFICATIONS FOR A COMPLETE
DESIGN PACKAGE. NOTIFY ENGINEER OF ANY DISCREPANCY BETWEEN DRAWINGS AND
SPECIFICATIONS.
7. ANYTHING MENTIONED IN THE SPECIFICATIONS AND NOT SHOWN ON THE DRAWINGS, OR SHOWN
ON THE DRAWINGS AND NOT MENTIONED IN THE SPECIFICATIONS, SHALL BE OF LIKE EFFECT AS IF
SHOWN OR MENTIONED IN BOTH.
8. LOCATE EQUIPMENT REQUIRING ACCESS 2' -0" MAXIMUM ABOVE CEILING.
9. ALL ROOF MOUNTED EQUIPMENT SHALL BE A MINIMUM 10' -0" FROM EDGE OF ROOF.
10. LOCATE DUCTWORK, PIPING AND MECHANICAL EQUIPMENT AWAY FROM THE SPACE ABOVE
ELECTRICAL PANELS, TRANSFORMERS AND OTHER ELECTRICAL EQUIPMENT.
11. PROVIDE FIRE PROOFING FOR ALL PENETRATIONS OF FIRE RATED ASSEMBLIES. FIRE PROOFING
MUST BE EQUIVALENT OR HIGHER TO THAT OF THE PENETRA TED ASSEMBLY. REFER TO
ARCHITECTURAL PLANS.
12. PROVIDE SLEEVES AND/OR OPENINGS TO RUN PIPES AND DUCTS THROUGH FOUNDATIONS,
FLOORS, WALLS, AND ROOF. CONSULT STRUCTURALLY ENGINEER OF RECORD FOR ALL
STRUCTURAL PENETRATIONS. PROVIDE WATER -PROOFING AS NEEDED FOR ALL EXTERIOR
PENETRATIONS.
13. ADJUST PIPING AND DUCTWORK SIZES TO PROPERLY CONNECT TO MECHANICAL EQUIPMENT.
14. REFER TO PLUMBING SERIES DRAWINGS FOR GAS PIPING.
15. PIPE AND DUCTWORK SIZES SHOWN SHALL BE CONTINUED IN THE DIRECTION OF FLOW UNTIL
ANOTHER SIZE IS SHOWN.
16. FOR DETAILS, EQUIPMENT CONNECTIONS, DUCT AND PIPE SIZES NOT SHOWN ON THE SEGMENTS,
REFER TO DETAILS, SCHEDULES, AND SPECIFICATIONS.
17. INSTALL ALL EQUIPMENT IN ACCORDANCE WITH THE RESPECTIVE MANUFACTURER'S WRITTEN
INSTALLATION INSTRUCTIONS, AT A LEVEL OF QUALITY AND WORKMANSHIP CONSISTENT WITH THE
SPECIFICATIONS.
18. LOCATIONS OF PIPING, DUCTWORK AND EQUIPMENT AS INDICATED ON THE DRAWINGS, ARE
APPROXIMATE AND SUBJECT TO MINOR ADJUSTMENTS IN THE FIELD. WORK SHALL BE
COORDINATED WITH ALL OTHER TRADES TO AVOID INTERFERENCE IN THE FIELD.
19. INSTALL EXPOSED PIPING AND DUCTWORK AS HIGH AS PRACTICAL IN ROOMS WITHOUT CEILINGS.
20. THE MECHANICAL CONTRACTOR SHALL PROVIDE AND INSTALL ALL NECESSARY CONDUIT, WIRING,
CONTROLS, AND APPURTENANCES FOR A COMPLETE AND OPERABLE HVAC SYSTEM.
21. INSULATE DUCTWORK AND PIPING SYSTEMS TO MEET LOCAL ENERGY CODE REQUIREMENTS.
A. SUPPLY AND RETURN DUCTS FOR HEATING AND COOLING:
• EXTERIOR: R -12
• UNCONDITIONED SPACE AND BURIED DUCTS: R -6
• INDIRECTLY CONDITIONED SPACE: R -1.9
B. SUPPLY AND RETURN DUCTS FOR HEATING ONLY:
• EXTERIOR: R -12
• UNCONDITIONED SPACE AND BURIED DUCTS: R -6
• INDIRECTLY CONDITIONED SPACE: R -1.9
C. SUPPLY AND RETURN DUCTS FOR COOLING ONLY:
• EXTERIOR: R -8
• UNCONDITIONED SPACE AND BURIED DUCTS: R -6
• INDIRECTLY CONDITIONED SPACE: R -1.9
22. SEISMIC ANCHORAGE AND RESTRAINTS MUST BE COORDINATED WITH STRUCTURAL ENGINEER
AND AUTHORITY HAVING JURISDICTION.
23. LOCATE THERMOSTATS AND TEMPERATURE SENSORS A MINIMUM OF 8" AWAY FROM LIGHT
SWITCHES. MOUNTING HEIGHT SHALL BE PER ARCHITECT AND IN CONFORMANCE WITH ADA
GUIDELINES.
24. DIVISION 23 CONTRACTOR SHALL PROVIDE AND INSTALL ALL CONTROL WIRING.
25. CONDENSATE DRAINS SHALL BE SUPPLIED FOR ALL COOLING AND GAS EQUI PMENT. CONTRACTOR
SHALL ENSURE PROPER INSTALLATION AND DRAINAGE AS REQUIRED BY FED ERAL, STATE, AND
LOCAL CODES. CONDENSATE PIPING SHALL BE SCHEDULE 40 PVC.
26. PROVIDE A 4" HOUSEKEEPING PAD FOR EACH PIECE OF FLOOR -MOUNTED ME CHANICAL
EQUIPMENT. COORDINATE SIZES WITH MECHANICAL EQUIPMENT SELECTED.
27. ALL SUPPLY, RETURN, AND EXHAUST DUCTWORK SHALL BE RATED FOR PRES SURE CLASS OF 2"
W.G. UNLESS NOTED OTHERWISE.
28. CONTRACTOR SHALL BE REQUIRED TO REPLACE FILTERS ON HVAC EQUIPMEN T AFTER ALL DUST
PRODUCING CONSTRUCTION HAS BEEN COMPLETED AND PRIOR TO THE FINAL PUNCH.
29. PROVIDE ACCESS PANELS FOR SERVICING, ADJUSTING AND REPLACING INCLUDING BUT NOT
LIMITED TO ALL EQUIPMENT, DAMPERS AND VALVING.
30. THERMOSTATS TO BE PROGRAMMABLE, HAVE 5°F DEADBAND, AUTOMATIC TIME -CLOCK, 2 -HOUR
OCCUPANT OVERRIDE, 10 -HOUR BACKUP, SETBACKS TO 55°F (HEATING) AND 85°F (COOLING).
31. CONTRACTOR TO PROVIDE OPERATION & MAINTENANCE MANUALS AND AS -BUILT DRAWINGS FOR
NEW SYSTEMS AND EQUIPMENT WITHIN 90 DAYS OF COMPLETION.
32. PROVIDE CODE REQUIRED DOOR SWITCH TO CONTROL HVAC SYSTEM OPERATION AND DE -
ENERGIZE HVAC SYSTEM FUNCTIONS IF DOOR IS FOUND TO BE OPEN LONGER THAN CODE
ALLOWED TIMEFRAME. REFER TO 2019 WISCONSIN ENERGY CODE 6.5.10 FOR SPECIFIC
REQUIREMENTS.
33. CONDENSATE DRAIN LINES SHALL BE CONFIGURED OR PROVIDED WITH CLEANOUT TO PERMIT THE
CLEARING OF BLOCKAGES AND FOR MAINTENANCE WITHOUT REQUIRING THE DRAIN LINE TO BE
CUT.
* NOTE *
ALL OF GENERAL NOTES ON THIS SHEET ARE TO BE APPLIED TO ALL OTHER DRAWINGS IN THIS SET.
THE SYMBOLS AND ABBREVIATIONS SHOWN ON THIS SHEET MAY OR MAY NOT BE USED IN THIS SET OF
DRAWINGS.
GENERAL NOTES
drawn by:
checked by:
date:
project #:
sheet title:
sheet
number:
www.dsgw.com
03/10/2026
25323
MEP
KWP
Brule Public
Works
Garage
M0.1
COVER SHEET
HVAC SHEET INDEX
M0.1 COVER SHEET - MECHANICAL
M0.2 SCHEDULES - MECHANICAL
M2.1 FLOOR PLAN - MECHANICAL
M2.2 MEZZANINE PLAN - MECHANICAL
M5.1 DETAILS - MECHANICAL
revision / issue no. date
CALENN
HEPPNER
E-48270
03/09/2026
drawn by:
checked by:
date:
project #:
sheet title:
sheet
number:
www.dsgw.com
03/10/2026
25323
MEP
CDH
Brule Public
Works
Garage
M0.2
SCHEDULES
1. PROVIDE 208V-115V STEPDOWN TRANSFORMER (CG1), AND TWO STATE THERMOSTAT.
NOTES:
GUH-2 GARAGE GAS UNIT HEATER WHITE 200 MBH 166 MBH 2562 60 83 1/2" 193 LBS 1/6 HP 115 REZNOR UDX200 ALL
GUH-1 GARAGE GAS UNIT HEATER WHITE 200 MBH 166 MBH 2562 60 83 1/2" 193 LBS 1/6 HP 115 REZNOR UDX200 ALL
MOTOR VOLT MANUFACTURER MODEL TAG LOCATION STYLE FINISH INPUT CAPACITY OUTPUT CAPACTIY AIRFLOW HEAT RISE THERMAL
EFFICIENCY %
GAS
CONNECTION WEIGHT ELECTRICAL BASIS OF DESIGN NOTES
GAS UNIT HEATER
4. PROVIDE WITH OUTDOOR AIR SENSOR.
3. USE MANUFACTURER APPROVED POLYPROPYLENE EXHAUST FLUE SYSTEM.
2. UNIT TO BE CAPABLE OF HANDLING 50% PROPYLENE GLYCOL.
1. PROVIDE WITH FLOW SWITCH, SIDEWALL VENT TERMINATION, NEUTRALIZER FOR CONDENSATE DRAIN AND ROUTE TO AN APPROVED LOCATION PER LOCAL CODE.
NOTES:
B-1 230 MBH 95.0 1-1/4" 1/2" 3" 3" 120°F 100°F 25 GPM GAS 29 MBH 2 85 MBH 247 MBH 10:1 120 1 LOCHINVAR WHB285N 200 LBS ALL
WATER GAS INTAKE VENT LWT EWT FLOW FUEL SOURCE MIN INPUT MAX INPUT REQUIRED
OUTPUT
TURN DOWN
RATIO VOLTS PH. MANUFACTURER MODEL TAG NET AHRI AFUE, %
CONNECTIONS PUMP HEATING CAPACITY ELECTRICAL BASIS OF D ESIGN
WEIGHT NOTES
BOILER SCHEDULE
1. PROVIDE FAN WITH MOTION SENSOR. COORDINATE LOCATION WITH ELECTRICAL CONTRACTOR.
NOTES:
CEF-02 TOILET SINGLE SPEED EXHAUST FAN 50 CFM 0.5" W.C. NO 13" 11.4 DIRECT 120 1 20 LBS PANASONIC FV-0511VK3 1
CEF-02 TOILET SINGLE SPEED EXHAUST FAN 50 CFM 0.5" W.C. NO 13" 11.4 DIRECT 120 1 20 LBS PANASONIC FV-0511VK3 1
CEF-01 STAFF TOILET SINGLE SPEED EXHAUST FAN 50 CFM 0.5 " W.C. NO 13" 11.4 DIRECT 120 1 20 LBS PANASONIC FV-0511VK3 1
AIRFLOW ESP DRIVE VOLT PH MANUFACTURER MODEL TAG AREA SERVED TYPE PERFORMANCE FIXTURE INCLUDES
LED LIGHT GRILLE SIZE EFFICIENCY
CFM/WATT
ELECTRICAL WEIGHT BASIS OF DESIGN NOTES
CEILING EXHAUST FANS
2. PROVIDE LOW AMBIENT KIT FOR OPERATION DOWN TO -10°F.
1. PROVIDE LINESET, DISCONNECT, EQUIPMENT, AND WIND BAFFLE.
NOTES:
CU-02 9 MBH 12 MBH R454B 65 FT 14.3/7.5 21/11.8 85 LBS 230 V 1 Ø FC-02 MITSUBISHI SUZ-AA09NL ALL
CU-01 24 MBH 25 MBH R454B 165 FT 14.3/7.5 21.2/10 120 LBS 2 30 V 1 Ø FC-01 MITSUBISHI SUZ-AA24NL ALL
COOLING HEATING MAX LENGTH REQUIRED ACTUAL VOLTAGE PHASE M ANUFACTURER MODEL TAG CAPACITY REFRIG. TYPE PIPING EFFICIENCY (SEER2/HSPF2) WEIGHT ELECTRICAL INTERLOCK BASIS OF DESIGN NOTES
CONDENSING UNITS
1. PROVIDE ECM MOTOR WITH SPEED CONTROLLER.
NOTES:
EF-02 GARAGE SIDEWALL 200 CFM 0.75" W.C. DIRECT 1/10 HP 11 5 V 1 Ø 25 LBS GREENHECK CSP-A390-VG 1
EF-01 GARAGE SIDEWALL 3000 CFM 0.75" W.C. DIRECT 1 HP 115 V 1 Ø 110 LBS GREENHECK SQ-15-M2-VG 1
DRIVE POWER VOLT PH MANUFACTURER MODEL TAG AREA SERVED TYPE AIRFLOW ESP ELECTRICAL WEIGHT BASIS OF DESIGN NOTES
FANS
NOTES:
ERV-02 SOUTH 415 CFM 0.75" W.C. 222 W 415 CFM 0.75" W.C. 2 12 W STATIC PLATE 75.60% 90.8/-14.7°F 79.3/46.8°F MERV-1 0 160 LBS 120 V 1 Ø RENEWAIRE HE07-JINV-S11AA---GNT---L
ERV-01 NORTH 50 CFM 5" W.C. 135 W 50 CFM 5" W.C. 135 W STAT IC PLATE 79.20% 90.8/-14.7°F 78.3/52.3°F MERV-10 100 LBS 120 V 1 Ø RENEWAIRE SL75
AIRFLOW ESP POWER AIRFLOW ESP POWER TYPE EFFICIENCY EAT DB
(SUMMER/WINTER)
LAT DB
(SUMMER/WINTER) VOLTAGE PHASE MANUFACTURER MODEL TAG AREA SERVED
SUPPLY FAN EXHAUST FAN ENERGY RECOVERY CORE
FILTER WEIGHT
ELECTRICAL BASIS OF DESIGN
NOTES
ENERGY RECOVERY VENTILATORS
4. WALL HEATER TO BE HIGH IN WALL.
3. PROVIDE HEATER ASSEMBLY WITH A WALL CAN AND GRILLE KIT.
2. ELECTRIC UNIT HEATER SHALL BE CONTROLLED WITH 60/30/20/10 MINUTE WALL TIMER.
1. ELECTRIC UNIT HEATERS SHALL HAVE AN INTEGRAL MECHANICAL THERMOSTAT.
NOTES:
EUH-04 MECHANICAL ROOM WALL WHITE 1 KW 120 V 8.3 CADET COM- PAK 1,2,3
EUH-03 STORAGE 113 WALL WHITE 1 KW 120 V 8.3 CADET APEX-72 A LL
EUH-02 TLT 108 WALL WHITE 0.5 KW 120 V 2.1 CADET COM-PAK 1,2 ,3
EUH-01 STAFF AREA WALL WHITE 1 KW 120 V 8.3 CADET COM-PAK 1, 2,3
WATT VOLT AMP MANUFACTURER MODEL TAG AREA SERVED STYLE FINISH ELECTRICAL BASIS OF DESIGN NOTES
ELECTRIC UNIT HEATER
2. PROVIDE ASPEN MINI CONDENSATE PUMP (OR EQUAL). 230V, 1Ø, 0.11A.
1. POWER AND CONTROL WIRING FROM CONDENSING UNIT.
NOTES:
FCU-02 OFFICE CASSETTE 300 CFM - 9 MBH 11 MBH 30 LBS 230 V 1 Ø MITSUBISHI SLZ-AF09NL ALL
FCU-01 MEETING ROOM DUCTED 742 CFM 0.6" W.C. 24 MBH 27 MB H 67 LBS 230 V 1 Ø MITSUBISHI PEAD-AA24NL ALL
AIRFLOW FAN ESP COOLING HEATING VOLTAGE PHASE MANUFACTURE R MODEL TAG AREA SERVED TYPE SUPPLY FAN CAPACITY (MBH) WEIGHT ELECTRICAL BASIS OF DESIGN NOTES
FAN COILS
1. PROVIDE WITH MOTORIZED DAMPER WITH 120 VOLT ACTUATOR.
NOTES:
LV-05 MECHANICAL ROOM 50 CFM EXHAUST 645 FPM 0.1 SQFT 8x8 GREENHECK ESD-202 -
LV-04 MEETING ROOM 105 415 CFM INTAKE 380 FPM 1.1 SQFT 24 x18 GREENHECK ESD-635 -
LV-03 MEETING ROOM 105 415 CFM EXHAUST 635 FPM 0.7 SQFT 2 0x14 GREENHECK EDJ-401 -
LV-02 STAFF AREA 104 3000 CFM INTAKE 390 FPM 7.7 SQFT 48x 40 GREENHECK ESD-635 1
LV-01 STAFF AREA 104 50 CFM INTAKE 335 FPM 0.1 SQFT 10x10 GREENHECK ESD-202 -
MANUFACTURER MODEL TAG LOCATION AIRFLOW TYPE VELOCITY REQUIRED FREE
AREA WIDTH / HEIGHT
BASIS OF DESIGN
NOTES
LOUVERS
TOTAL (ALL FLOORS) 1735 34 50 50
STORAGE STORAGE 70 0 0 0 0.12 0.8 11 20 - - - -
STAFF TLT TOILETS-PUBLIC (CONTINUOUS OPERATION) 70 0 0 0 0 0.8 0 0 50 1 - 50
STAFF AREA OFFICE SPACE 140 5 2 5 0.06 0.8 23 30 - - - -
ERV-02
405 415 100
OFFICE OFFICE SPACE 195 5 2 5 0.06 0.8 27 30 - - - -
STORAGE STORAGE 80 0 0 0 0.12 0.8 12 15 - - - -
LOBBY MAIN ENTRY LOBBIES 165 10 2 5 0.06 0.8 25 25 - - - -
TLT TOILETS-PUBLIC (CONTINUOUS OPERATION) 70 0 0 0 0 0.8 0 0 50 1 - 50
TLT TOILETS-PUBLIC (CONTINUOUS OPERATION) 70 0 0 0 0 0.8 0 0 50 1 - 50
MEETING ROOM CONFERENCE/MEETING 875 50 44 5 0.06 0.8 341 345 - - - -
ERV-01
SPACE NAME OCCUPANCY TYPE AREA
(FT2)
OCCUPANT
DENSITY
#/1000 SQ FT
NUMBER
OF PEOPLE
OSA AIRFLOW
PER PERSON
(CFM)
OSA AIRFLOW
PER UNIT AREA
(CFM/FT2)
EFFECTIVENESS
REQUIRED
OSA
AIRFLOW
(CFM)
TOTAL
SUPPLIED OSA
AIRFLOW
(CFM)
UNIT EXHAUST
(CFM/UNIT) UNITS
EXHAUST
AIRFLOW
PER UNIT
AREA
(CFM/FT2)
MINIMUM
EXHAUST
AIRFLOW
(CFM)
WMC 2021 403.3 VENTILATION AND EXHAUST CALCULATION
TOTALS: 3000 200
GARAGE 4000 0.75 3000 0.05 200 8 7
OSA PER UNIT AREA
(CFM/FT2)
OSA CAPACITY
(CFM)
OSA PER UNIT AREA
(CFM/FT2)
REQUIRED VENTILATION
CAPACITY (CFM)
INTAKE LOUVER SIZE
@ 50% FREE AREA (FT2)
EXHAUST LOUVER SIZE
@ 50% FREE AREA (FT2)
SPACE NAME TOTAL AREA
(FT2)
MAX. CAPACITY REQUIRED MINIMUM TURNDOWN REQUIRED LOUV ER FREE AREA
PARKING GARAGE VENTILATION CALCULATION
1. PROVIDE WITH HOSE REEL (HRM-02-0630-WT), MOTORIZED HOSE REEL SWITCH (HRCM-4B), TAPERED CONE (TPA 04-06), FAN CONTROL BOX (CBS-1-230-1-L) AND LIFTING POLE (LP-10-ADJ).
NOTES:
VEF-1 GARAGE PRESSURE BLOWER - TOP DISCHARGE 6" 25 FT MO TORIZED 580 CFM 4" W.C. 120 V 1 Ø 70 LBS FUME-A-VENT PB10- 1-1-T 1
DIAMETER LENGTH DRUM STORAGE VOLT PH MANUFACTURER MODEL TAG SERVES TYPE EXHAUST HOSE/DRUM AIRFLOW TSP ELECTRICAL WEIGHT BASIS OF DESIGN NOTES
VEHICLE EXHAUST SOURCE CAPTURE SYSTEM SCHEDULE
1. PROVIDE WITH ECM MOTOR, BACNET CARD.
NOTES:
P-4 IN-LINE (WET-ROTOR) INLINE 7.96 GPM 16 FT 1/12 HP 115 V 1 Ø BELL & GOSSETT ECOCIRC XL 20-35 25 LBS 1
P-3 IN-LINE (WET-ROTOR) INLINE 5.93 GPM 16 FT 1/12 HP 115 V 1 Ø BELL & GOSSETT ECOCIRC XL 20-35 25 LBS 1
P-2 IN-LINE (WET-ROTOR) INLINE 5.89 GPM 15 FT 1/12 HP 115 V 1 Ø BELL & GOSSETT ECOCIRC XL 20-35 25 LBS 1
P-1 IN-LINE (WET-ROTOR) INLINE 4.95 GPM 22 FT 1/12 HP 115 V 1 Ø BELL & GOSSETT ECOCIRC XL 20-35 25 LBS 1
BP-1 IN-LINE (WET-ROTOR) INLINE 25 GPM 5 FT 1/12 HP 115 V 1 Ø BELL & GOSSETT ECOCIRC XL 20-35 25 LBS 1
DESIGN FLOW HEAD POWER VOLT PHASE MANUFACTURER MODEL TAG DESCRIPTION TYPE
PUMP ELECTRICAL BASIS OF DESIGN
WEIGHT NOTES
PUMP SCHEDULE
4. THROW VALUES GIVEN FOR TERMINAL VELOCITIES 150, 100, AND 50 FPM FOR ISOTHERMAL CONDITIONS.
3. NOISE CRITERIA (NC) BASED ON ROOM ABSORPTION OF 10 DB, MEASURED PER ANSI/ASHRAE STANDARD 70.
2. DIFFUSER, GRILLE, OR REGISTER TO BE SIZED AS LISTED ON SCHEDULE UNLESS OTHERWISE DIRECTED ON FLOOR PLAN.
1. APPEARANCE SHALL BE APPROVED BY ARCHITECT PRIOR TO PURCHASING DIFFUSER OR GRILLE.
NOTES:
RW-1 SIDEWALL RETURN/EXHAUST GRILLE 0 DEGREE DEFLECTI ON 0 900 18x12 18x12 18x12 25 - SURFACE MOUNT - TITUS 350RS AL L
300 750 14 24x24 12x12 29 - - ALL
100 300 12x12 24x24 12x12 - - - ALL RC-1 PASSIVE CEILING RETURN GRILLE PERFORATED, EGG CR ATE
0 100 6x6 24x24 12x12 - -
SURFACE MOUNT
-
TITUS PAR-AA
ALL
SC-2 CEILING SUPPLY SQUARE FOUR-WAY 200 350 12 24x24 24x24 18 3-5-15 SURFACE MOUNT PERFORATED TITUS PCS-AA ALL
121 200 8 24x24 12x12 12 3-5-9 4-WAY ALL SC-1 CEILING SUPPLY SQUARE FOUR-WAY 0 120 6 24x24 12x12 - 2-3-7 SURFACE MOUNT 4-WAY TITUS TMS-AA ALL
TAG TYPE FACE MIN CFM MAX CFM NECK SIZE T-BAR HARDLID NC THR OW FRAME DEFLECTION BASIS OF DESIGN NOTES
DIFFUSERS, REGISTERS AND GRILLES
1. PROVIDE WITH BUILT-IN AIR FLOW SENSOR, TEMPERATURE SENSOR, AUTOMATIC RESET, TEMPERATURE CONTROLLER, AND SINGLE POINT POWER CONNECTION.
NOTES:
EDH-2 THERMOLEC TER-10-4208 ERV-02 THERMOAIR 10" 3.24 KW 4 .0 KW 120 CFM 415 CFM 240 1 1
EDH-1 THERMOLEC TER-6-1120 ERV-01 THERMOAIR 6" 0.39 KW 1.0 KW 30 CFM 50 CFM 120 1 1
MANUFACTURER MODEL SERVES TYPE SIZE REQUIRED POWER ACTUAL POWER MIN. DESIGN VOLTAGE PHASE TAG BASIS OF DESIGN HEATING ELEMENT AIRFLOW REQ'S ELECTRIC AL NOTES
ELECTRIC DUCT HEATER SCHEDULE
1. PROVIDE A SURFACE MOUNT ENCLOSURE.
NOTES:
MF-4 GARAGE ZONE 4 1-1/4" 5 FT 5 337 FT 5/8" 12" 7.96 GPM 1. 6 GPM 12.5 FT 79600 BTU 120 °F 100 °F WATTS D38030X5SS BAR RIER PEX 5/8" 1
MF-3 GARAGE ZONE 3 1" 5 FT 5 346 FT 5/8" 12" 5.93 GPM 1.2 GP M 13.0 FT 59300 BTU 120 °F 100 °F WATTS D38030X5SS BARRIER PEX 5/8" 1
MF-2 GARAGE ZONE 2 1" 5 FT 5 333 FT 5/8" 12" 5.89 GPM 1.2 GP M 12.0 FT 58900 BTU 120 °F 100 °F WATTS D38030X5SS BARRIER PEX 5/8" 1
MF-1 OFFICE AREA ZONE 1 1" 5 FT 4 378 FT 5/8" 12" 4.95 GPM 1 .2 GPM 18.0 FT 50100 BTU 120 °F 100 °F WATTS D38030X4SS BA RRIER PEX 5/8" 1
MANUFACTURER MANIFOLD MODEL TUBING MODEL TAG RESPECTIVE ROOMS MANIFOLD SIZE MAX. MANIFOLD
PRESSURE DROP CURCUITS APPROX. LOOP
LENGTHS TUBING SIZE SPACING TOTAL FLOW
(GPM)
FLOW PER
LOOP (GPM)
TUBING
PRESSURE DROP
RADIANT HEAT
LOAD MAX EWT LWT BASIS OF DESIGN NOTES
RADIANT FLOOR MANIFOLD & ZONE SCHEDULE
revision / issue no. date
CALENN
HEPPNER
E-48270
03/09/2026
REF.
VD
VD VD
VD VD
VD
VD
VD
VD
BDD
BDD
VD
VD
REF.
1
2
3
4
5
7
8
A B
meeting room
105
garage
100
staff tlt
103
staff area
104
6
storage
102
CO
NO2
CO
NO2
R 50
'-0"
R 50'-0"
12"Ø S/A
SC -1
185
SC -1
185
8"Ø S/A
8"Ø S/A
SC -1
185
8"Ø S/A
SC -2
345
6"Ø O/A
ERV-02
FC-1
CU-1
CU-2
EUH-02
EUH-03
FC-2
EUH-01
CEF-01
6"Ø E/A
CEF-02
6"Ø E/A
LV-03
LV-04
LV-05
SC -1
15
4"Ø O/A
SC -1
25
SC -1
20 SC -1
30
RC -2
50
SC -1
185
GARAGE VENTILATION FAN
VFD
8"Ø E/A
6"Ø O/A
4"Ø O/A 6"Ø R/A
ERV-01
6"Ø E/A
LV-01
RC -1
740
RC -1
370
RC -2
45
SC -1
30
12"Ø O/A
Office
110
Hallway
109
Toilet Rm
108
Toilet Rm
106 Utility
107
EUH-04
6"Ø O/A
4"Ø O/A
9
MOTORIZED HOSE REEL
SWITCH (HRCM -4B)
EDH-01
EDH-02
14x10 R/A
3/4" CD DN
1 3/4" CD
2
3
3
4
4
10"Ø S/A
8"Ø O/A
8"Ø S/A
42x8 S/A
42x12 R/A
6"Ø O/A
10"Ø R/A
6"Ø R/A
1
8"Ø E/A
5
5
MOTORIZED HOSE REEL
SWITCH (HRCM -4B)
3"Ø C/A UP
3"Ø FLUE UP
mech/elec
101 B-1
RW -1
750
RW -1
750
14x10 E/A UP
14x10 E/A UP
6
6
12"Ø R/A
12"Ø O/A
11
M5.1
11
M5.1
1
2
3
4
5
7
8
A B
6
9
garage
100
B-1
RADIANT ZONE 4
120 °F EWT
100 °F LWT
7.96 GPM
1,542 SQ FT
79,567 BTU/HR
RADIANT ZONE 3
120 °F EWT
100 °F LWT
5.93 GPM
1,550 SQ FT
59,294 BTU/HR
RADIANT ZONE 2
120 °F EWT
100 °F LWT
5.89 GPM
1,630 SQ FT
58,876 BTU/HR
RADIANT ZONE 1
120 °F EWT
100 °F LWT
4.95 GPM
1,495 SQ FT
49,471 BTU/HR
1 1/4" HWR
1 1/4" HWS
1 1/2" HWR (14 GPM)
1 1/2" HWS (14 GPM)
1 1/2" HWS (20 GPM)
1 1/2" HWR (20 GPM)
1" HWS
1" HWR
P-1
P-2
P-3
P-4
2" HWR (25 GPM)
2" HWS (25 GPM)
MF-02
1" HWR DN
1" HWS DN
MF-03
1 1/4" HWR DN
1 1/4" HWS DN
9
M5.1
MF-04
BP-1
MF-04
drawn by:
checked by:
date:
project #:
sheet title:
sheet
number:
www.dsgw.com
03/10/2026
25323
MEP
KWP
Brule Public
Works
Garage
M2.1
FLOOR PLAN
SCALE: 1/8" = 1'-0" 1 FLOOR PLAN - MECHANICAL
KEYNOTES:
1 ROUTE 3/4" CONDENSATE AT A MINIMUM SLOPE OF 1/8" P ER FOOT TO MOP
SINK LOCATED IN JANITOR ROOM. SEE PUBLING DRAWINGS FOR FINAL
LOCATION.
2 PROVIDE 8" WALL VENT WITH INSECT SCREEN AND BACKDR AFT DAMPER.
EXHAUST LOCATION SHALL BE MINIMUM 10 FEET FROM MECHANICAL AIR
INTAKES, 3 FEET FROM PROPERTY LINES AND 3 FEET FROM OPERABLE
OPENINGS, PER IMC 501.3.1 (#3)
3 INSTALL CONDENSATE PUMP. SEE FAN COIL SCHEDULE FOR MORE DETAIL.
4 ROUTE AND CONNECT REFRIGERANT LINESET FROM FAN COI L TO
ASSOCIATED CONDENSING UNIT.
5 ROUTE REFRIGERANT LINESET FROM CONDENSING UNIT TO ASSOCIATED
FAN COIL.
6 INSTALL GRILLE MAXIMUM 18" AFF.
SCALE: 1/8" = 1'-0" 2 FLOOR PLAN - HYDRONIC / IN-FLOOR HEAT
revision / issue no. date
CALENN
HEPPNER
E-48270
03/09/2026
M
1
2
3
4
5
7
8
A B
6
1
M2.2
6"Ø E/A
6"Ø E/A
1
1
6"Ø C/A
6"Ø FLUE
COMBINATION C/A &
FLUE THRU WALL
5
M5.1
6"Ø FLUE
6"Ø C/A
COMBINATION C/A &
FLUE THRU WALL
5
M5.1
GUH-1
GUH-2
COMBINATION C/A &
FLUE THRU WALL
5
M5.1
3"Ø FLUE
LV-02
9
VEF-1
VEF-2
6
M5.1
6
M5.1
3"Ø FLUE DN
3"Ø C/A DN
EF-01
EF-02
RW-1
750
RW-1
750
14x10 E/A
18x16 E/A
22x20 E/A
22x20 E/A
8x8 E/A
2
2
14x10 E/A DN
14x10 E/A DN
3
LEVEL 1
0"
ROOF
20'-0"
4
LEVEL 1 9'
9'-0"
VEF-1
HRCM-4B
CONTROLLER
6"Ø E/A
drawn by:
checked by:
date:
project #:
sheet title:
sheet
number:
www.dsgw.com
03/10/2026
25323
MEP
KWP
Brule Public
Works
Garage
M2.2
MEZZANINE
PLAN
SCALE: 1/4" = 1'-0"1 SOURCE CAPTURE SYSTEM (VEF-1)
SCALE: 1/8" = 1'-0"2 OVERHEAD PLAN - MECHANICAL
KEYNOTES:
1 PROVIDE DUCT TURN DOWN WITH BIRD-SCREEN AT EXHAUST TERMINATION.
2 PROVIDE WEATHER HOOD WITH MOTORIZED BACKDRAFT DAMP ER.
3 PROVIDE MESH OVER DUCT OPENING.
revision / issue no. date
CALENN
HEPPNER
E-48270
03/09/2026
OIL TRAP
DRIER
SERVICE VALVE IF NOT
FURNISHED WITH UNIT
AIR COOLED
CONDENSING
UNIT
COOLING
COIL
LIQUID LINE
EXPANSION VALVE
SUCTION LINE
TOP VIEW
OUTDOOR AIR INTAKE
(INSULATED)
EXHAUST AIR TO OUTDOORS
(INSULATED)
EXHAUST AIR FROM ROOMS
OUTDOOR AIR TO ROOMS
EXHAUST AIR FROM BATHROOMS
MANUAL DAMPER TYP.
THRU WALL TO LOUVER OR UP
TO HOOD.
ERV -X
LOW LEAKAGE MOTORIZED
BACKDRAFT DAMPER IF
REQUIRED PER CODE. (TYP.)
PROVIDE PROPER SUPPORTS
FOR ALL REFRIGERANT PIPE
ALL OUTDOOR REFRIGERANT
PIPING INSULATED AND JACKETED
(ALL LINES)
DISCONNECT AND HIGH VOLTAGE WIRING
4" CONCRETE HOUSEKEEPING
PAD AND VIBRATION ISOLATORS.
CONDENSING UNIT PAD TO BE 4"
LARGER ON ALL SIDES THAN
CONDESING UNIT.
SLOPE
BUILT IN LIFT PUMP DISCHARGE, CONNECT WITH
DRAIN SOCKET PROVIDED, MAINTAIN FULL LINE
SIZE (DO NOT TRAP) UP TO RATED MAX LIFT, THEN
IMMEDIATELY INTO GRAVITY VENTED MAIN DRAIN.
REF MANF INSTALL MANUAL.
VENT
TYPICAL -THREADED HANGING ROD
SECURELY ANCHORED TO
STRUCTURE - REF MANF. INSTALL
AND DIV 23 SPECS.
FRESH AIR DUCT CONNECTION (IF
USED/SHOWN ON PLANS) FROM
FAN FORCED & FILTERED FRESH
AIR SYSTEM ONLY - REF MANF.
INSTALL MANUAL.
SOFT ACR COPPER TUBE LINES (LIQUID &
GAS) TO INDOOR UNIT, ALL LINES (LIQUID &
GAS) FULLY INSULATED AND PROPERLY
SUPPORTED - REF DIV 23 SPECS
CONTROL PANEL (NOT PRESENT ON ALL
MODELS) - PROVIDE ACCESS THIS SIDE
WHEN REQUIRED - REF MANF. INSTALL
MANUAL.
FRONT BEZEL PLATE - ADJUST HANGER ROD TO
ENSURE FLUSH FIT WITH CEILING - COORDINATE
WITH OTHER TRADES/CIELIGN GRID LAYOUT - REF
MANF. INSTALL.
SLOPE
TYPICAL -THREADED HANGING ROD
SECURELY ANCHORED TO
STRUCTURE
ALTERNATE HIGH LEVEL
OVERFLOW DRAIN TO APPROVED
LOCATION WHEN
SPECIFIED/REQUIRED BY CODE.
FLEXIBLE CANVAS DUCT
CONNECTOR
SOFT ACR COPPER TUBE LINES (LIQUID &
GAS) TO INDOOR UNIT, ALL LINES (LIQUID &
GAS) FULLY INSULATED AND PROPERLY
SUPPORTED
1-1/4" PRIMARY GRAVITY DRAIN CONNECTION
WHEN USED IN LIEU OF BUILT IN LIFT
PUMP -ROUTE TO APPROVED LOCATION.
CONNECT WITH MANF. PROVIDED FLEXIBLE
HOSE.
PROVIDE TRAP WITH
CLEAN -OUT, SIZE PER
CODE FOR POSITIVE
PRESSURE (BLOW
THROUGH) COIL
OPERATION.
BUILT IN LIFT PUMP DISCHARGE, WHEN
USED (IF PRESENT ON MODEL),
MAINTAIN FULL LINE SIZE (DO NOT
TRAP) UP TO RATED MAX LIFT, THEN
IMMEDIATELY INTO GRAVITY VENTED
MAIN DRAIN.
CONTROL/ELEC
PANEL -MAINTAIN
REQUIRED
CLEARANCE
VENT
FLEXIBLE CANVAS DUCT
CONNECTOR
CONCRETE SLAB
WIRE TIE
PEX TUBING
SLAB INSULATION
BASE MATERIAL
WIRE MESH, REBAR, OR
STAPLE TO RIGID FOAM
EDGE INSULATION
SPRING ISOLATOR
GAS FIRED UNIT
HEATER
DOUBLE
DEFLECTION
DIFFUSER
UNION SHUTOFF VALVE
PRESSURE
REDUCING
VALVE
GAS BURNER DIRT LEG CAPPED
DRIP PAN
SEALED
WATERTIGHT
ROOFING
BAR JOIST
5
M5.1
AIR INTAKE DISTANCE ABOVE AVG. SNOW FALL OR
GRADE REF: LOCAL CODE
REQUIREMENTS. MAINTAIN 12"
CLEARANCE ABOVE HIGHEST
ANTICIPATED SNOW LEVEL OR GRADE
WHICHEVER IS GREATER. EXTERIOR WALL
SYSTEM1738
ROUND FACE PLATE
1" MIN, 2" MAX
(FROM WALL OR
FACE PLATE)
CLAMP OR STRAP
(FIELD SUPPLIED)
EXHAUST
AIR INTAKE
EXHAUST
12" MIN
CLEARANCE TO SOFFIT
FRONT VIEW
CONTROLS AT 4' -0" AFF
ELECTRICAL DISCONNECT;
REFERENCE ELECTRICAL
EXHAUST HOSE DRUM
24V TRANSFORMER
ELECTRICAL CONTROL
BOX (FAN); REFERENCE
ELECTRICAL
EXHAUST DUCT;
REFERENCE MECHANICAL PLANS
EXHAUST
HOSE
NOZZLE
ELECTRICAL CONTROL BOX
(REEL); REFERENCE ELECTRICAL
MOUNT REEL BANK
BRACKET BELOW
BRIDGE CRANE
SUPPORT BEAM
BRIDGE CRANE SUPPORT BEAM;
REFERENCE STRUCTURAL
SYSTEM SUPPLY
SENSOR, TYP. ZONE 1 ZONE 3 ZONE 4
MIXING VALVES,
TYP.
T/P
T/P
T/P
DRAIN POINT, TYP.
S
EXPANSION
TANK
DRAIN POINT
(TYP.)
BALL VALVE, TYP.
UNION, TYP.
PRESSURE RELIEF VALVE, TYP.
TEMPERATURE/PRESSURE
GAUGE, TYP.
Y-STRAINER
(RECOMMENDED)
BOILER PUMP (BP -1)
NOT TO EXCEED 4 PIPE DIAMETER
OR MAX. OF 12" APART
PRESSURE
REDUCING VALVE ZONE 2 T/P
TYP.
10
M5.1
TO GLYCOL FILL STATION
ZONE PUMPS, TYP.
DRYWALL
WALL STUD
PLEXIGLASS
ACCESS
PANEL
1/2"
PLYWOOD
BACKING
STUD BAYS
WALL STUD
BALANCE VALVES
AIR VENT
SUPPLY MANIFOLD
RETURN MANIFOLD
SHUTOFF VALVE
SIDE VIEW FRONT VIEW
TO IN -FLOOR HEAT ZONES
(BY OTHERS)
TO IN -FLOOR HEAT ZONES
(BY OTHERS)
9
M5.1
HEAVY DUTY
RETURN GRILLE
FILTER
BALANCING DAMPER
SEE PLANS FOR
DUCT SIZE
AFF.
. MAX 18" FLOOR
drawn by:
checked by:
date:
project #:
sheet title:
sheet
number:
www.dsgw.com
03/10/2026
25323
MEP
KWP
Brule Public
Works
Garage
M5.1
DETAILS
NOT TO SCALE 3 SPLIT SYSTEM FAN COIL UNIT PIPING SCHEMATIC
NOT TO SCALE 4 EXHAUST RECOVERY VENTILATOR
NOT TO SCALE 8 ACCU CONCRETE PAD
NOT TO SCALE 1 MITSUBISHI VRF CASSETTE INDOOR UNIT (PLFY)
NOT TO SCALE 2 FAN COIL - HORIZONTAL DUCTED
NOT TO SCALE 7 IN-FLOOR HEATING - SLAB ON GRADE
NOT TO SCALE 12 GAS FIRED UNIT HEATER
SCALE: NOT TO SCALE 5 CONCENTRIC VENT DETAIL
NOT TO SCALE 6 VEHICLE EXHAUST REEL MOTOR OPERATED SUSPENDED DETAIL
NOT TO SCALE 9 BOILER PIPING
NOT TO SCALE 10 IN-FLOOR HEATING - MANIFOLD
revision / issue no. date
NOT TO SCALE 11 RETURN GRILLE AND AIR FILTER DETAIL
CALENN
HEPPNER
E-48270
03/09/2026
T/P
M
S
T/P
TP
W
IR
EG
S
ETP
G
1. THE CONTRACTOR SHALL PROVIDE COMPLETE PLUMBING SYSTEMS AS DETAIL ED IN THESE
DRAWINGS. WORK CONSISTS OF FURNISHING ALL MATERIALS, EQUIPMENT, AND SERVICES REQUIRED
FOR COMPLETE SYSTEMS. INCLUDE ANY INCIDENTAL APPARATUS, APPLIANC ES, MATERIAL LABOR AND
SERVICES NECESSARY TO MAKE NEW WORK COMPLETE IN ALL RESPECTS AND FULLY READY FOR
OPERATION.
2. UPON COMPLETION OF THE WORK UNDER THIS CONTRACT, THE CONTRACTOR SHALL SUBMIT TO
OWNER A COMPLETE O&M MANUAL, LISTING ALL EQUIPMENT AND FIXTURES INSTALLED.
3. FINAL PRODUCT SHALL CONFORM TO ALL REQUIREMENTS OF APPLICABLE FE DERAL, STATE, AND
LOCAL CODES, INCLUDING BUT NOT LIMITED TO THE UNIFORM PLUMBING C ODE AND/OR
INTERNATIONAL PLUMBING CODE WITH PRIOR AHJ APPROVAL.
4. ALL MATERIALS INSTALLED MUST HAVE PROPER LISTING REQUIRED BY APP LICABLE CODES INCLUDING
BUT NOT LIMITED TO UPC/IAPMO, NSF UNLESS RECEIVING PRIOR APPROVA L IN WRITING FROM
AUTHORITY HAVING JURISDICTION (AHJ).
5. IT IS THE CONTRACTOR'S RESPONSIBILITY TO FOLLOW MANUFACTURER REC OMMENDED
INSTALLATION INSTRUCTIONS AND START -UP PROCEDURES ON ANY EQUIPME NT SPECIFIED SUCH AS
BOILERS, PUMPS AND FIXTURES. ANY DAMAGE TO EQUIPMENT OR PREMISES , PERSONAL INJURY OR
EQUIPMENT FAILURE DUE TO NOT FOLLOWING MANUFACTURER INSTRUCTIONS IS THE INSTALLER'S
RESPONSIBILITY.
6. UPON COMPLETION OF THE WORK UNDER THIS CONTRACT, THE CONTRACTOR SHALL REMOVE ALL
TOOLS, APPLIANCES, SURPLUS MATERIALS, AND SCRAP. ALL IDENTIFIED EXISTING EQUIPMENT TO BE
REMOVED SHALL BE TURNED OVER TO THE OWNER.
7. THESE DRAWINGS ARE DIAGRAMMATIC AND INDICATE THE GENERAL ARRANGEMENT OF SYSTEMS AND
EQUIPMENT. FINAL LOCATIONS OF EQUIPMENT SHALL BE FIELD DETERMINED. ALL DISCREPANCIES IN
THE DRAWINGS SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT IN WRITING BEFORE
SUBMISSION.
8. EQUIPMENT FOR OTHER DISCIPLINES MAY BE SHOWN FOR REFERENCE ONLY. REFER TO OTHER
DISCIPLINES' DRAWINGS FOR MORE DETAIL REGARDING EQUIPMENT SPECIFICATIONS AND
INFORMATION.
9. PLANS SHALL GOVERN IN MATTERS OF QUANTITY; SPECIFICATIO NS SHALL GOVERN IN MATTERS OF
QUALITY. IN CASE OF DISCREPANCY BETWEEN DRAWINGS AND SPECIFICATIONS, THE SPECIFICATIONS
SHALL GOVERN. PLANS ARE TO BE TIED TO SPECIFICATIONS FOR A COMPLETE DESIGN PACKAGE.
10. ANYTHING MENTIONED IN THE SPECIFICATIONS AND NOT SHOWN ON THE DRAWINGS, OR SHOWN ON
THE DRAWINGS AND NOT MENTIONED IN THE SPECIFICATIONS, SHALL BE OF LIKE EFFECT AS IF
SHOWN OR MENTIONED IN BOTH.
11. THE CONTRACTOR SHALL BE FAMILIAR WITH ALL CONDITIONS; BOTH EXISTING AND THOSE
ILLUSTRATED BY THESE DOCUMENTS, AS WELL AS THOSE THAT CAN BE REASONABLY ANTICIPATED
INCLUDING, BUT NOT LIMITED TO ARCHITECTURAL, ELECTRICAL, VENTILATION, PLUMBING, AND OTHER
SYSTEMS INVOLVED IN THIS PROJECT.
12. THE CONTRACTOR SHALL COORDINATE WORK WITH OTHER TRADES TO ENSURE ANY CONFLICT IN
LAYOUT, NEEDED SPACE, SHARED EQUIPMENT REQUIREMENTS ETC. IS ADDRESSED BEFORE
INSTALLATION, SO ADJUSTMENTS CAN BE MADE, IF NECESSARY.
13. LOCATION AND INVERTS OF SITE UTILITIES SHALL BE FIELD VERIFIED BEFORE INSTALLATION. ROUTE
DOMESTIC WATER, SANITARY SEWER, AND STORM SEWER SERVICES TO SITE UTILITIES 5' -0" FROM
BUILDING UNLESS NOTED OTHERWISE. REFER TO CIVIL PLANS FOR CONTINUATION. FIRE PROTECTION
DESIGN IS BY OTHERS.
14. REFER TO ARCHITECTURAL PLANS FOR THE EXACT LOCATION OF PLUMBING FIXTURES AND FLOOR
DRAINS.
15. LOCATE PIPING AND EQUIPMENT AWAY FROM THE SPACE ABOVE ELECTRICAL PANELS,
TRANSFORMERS AND OTHER ELECTRICAL EQUIPMENT.
16. INSTALL EXPOSED PIPING AS HIGH AS PRACTICAL IN ROOMS WITHOUT CEILINGS.
17. WHERE VALVES OCCUR ABOVE DRYWALL OR PLASTER OR ARE CONCEALED BEHIND WALLS, THE
CONTRACTOR SHALL FURNISH AND INSTALL ACCESS PANELS. COORDINATE LOCATION, SIZE, COLOR
AND STYLE WITH ENGINEER/ARCHITECT.
18. PROVIDE FIREPROOFING FOR ALL PENETRATIONS OF FIRE -RATED ASSEMBLIES. FIREPROOFING MUST
BE EQUIVALENT OR HIGHER TO THAT OF THE PENETRATED ASSEMB LY. REFER TO ARCHITECTURAL
PLANS FOR LOCATION OF FIRE -RATED ASSEMBLIES.
19. COORDINATE UNDERGROUND PIPE ROUTING WITH CIVIL AND STRUCTURAL PLANS.
20. CONSULT STRUCTURAL ENGINEER OF RECORD FOR ALL STRUCTURAL PENETRATIONS.
21. COORDINATE LOCATION OF PLUMBING VENTS WITH MECHANICAL INTAKES AN D ARCHITECTURAL
PLANS. NO VENT THROUGH ROOF SHALL TERMINATE CLOSER THAN 10 FT TO ANY OUTSIDE AIR INTAKE
OR VENTILATION LOUVERS, DOORS, WINDOWS, AND OTHER BUILDING OPENI NGS. GROUP PLUMBING
VENTS TOGETHER WHERE PRACTICAL.
22. WHERE FLOOR DRAINS OCCUR WITHIN THE LIMITS OF CONSTRUCTION, PREV ENT CONSTRUCTION
DEBRIS FROM ENTERING THE DRAIN BODY BY SEALING THE DRAIN OPENING BEFORE START OF WORK.
UNSEAL DRAINS AT COMPLETION OF CONSTRUCTION.
23. FLOOR DRAINS SHALL BE PROVIDED WITH TRAP PRIMERS WHERE REQUIRED BY CODE.
24. PIPE SIZES SHOWN SHALL BE CONTINUED IN THE DIRECTION OF FLOW UNT IL ANOTHER SIZE IS
SHOWN.
25. SANITARY WASTE PIPING SHALL BE SLOPED UNIFORMLY NOT LESS THAN 1/ 4 INCH PER FOOT. WHERE
NOTED AND DEEMED NECESSARY AND APPROVED BY AHJ AND ENGINEER OF R ECORD, WASTE PIPING
4" AND LARGER, MAY BE SLOPED NOT LESS THAN 1/8 INCH PER FOOT.
26. ALL SANITARY AND WATER PIPING UNDERGROUND SHALL BE A MINIMUM OF 12 ” BELOW GRADE OR
FINISHED FLOOR UNLESS NOTED OTHERWISE.
27. WASTE AND VENT PIPING BELOW THE FLOOR AND THROUGH THE FLOOR SHAL L BE 2" MINIMUM.
28. CLEANOUTS SHALL BE PROVIDED AS SHOWN AND WHERE REQUIRED BY CODE. INSTALL CLEANOUT IN
ACCESSIBLE LOCATION AT THE BASE OF ALL WASTE PLUMBING RISERS BEF ORE THE ENTRANCE TO
BELOW GRADE. PROVIDE ALL SINKS AND LAVATORIES WITH SLIP JOINT T RAP FITTINGS FOR
CLEANOUT.
29. PROVIDE LOW POINT DRAINS IN MAIN CW AND HW LINES WHEN SHUT OFF, MAY BE DRAINED TO
ELIMINATE THE RISK OF FLOODING IN THE EVENT OF FUTURE UPGRADE OR REPAIR.
30. PROVIDE SHUTOFF VALVES ON ALL EXTERIOR HOSE BIBBS.
31. BALL VALVES SHALL BE INSTALLED SO THAT WHEN OPEN, THE HANDLE POI NTS IN DIRECTION OF
FLOW.
32. ALL HOT WATER PIPING SHALL BE INSULATED PER THE GOVERNING ENERGY CODE.
33. INSULATION AND/OR HEAT TRACE SHALL BE PROVIDED WHERE REQUIRED FO R FREEZE PROTECTION.
34. PROVIDE DIELECTRIC UNIONS AT ALL CONNECTIONS BETWEEN ELECTROLYSI S-PRODUCING
DISSIMILAR PIPING METALS.
35. PROVIDE HAMMER ARRESTORS AT ALL FAST -CLOSING VALVES.
36. PROVIDE DISINFECTION OF POTABLE WATER PIPING SYSTEMS P ER CODE REQUIREMENTS.
* NOTE *
ALL OF THE GENERAL NOTES ON THIS SHEET ARE TO BE APPLIED TO ALL OTHER DRAWINGS IN THIS SET.
THE SYMBOLS AND ABBREVIATIONS SHOWN ON THIS SHEET MAY OR MAY NOT BE USED IN THIS SET OF
DRAWINGS.
PLUMBING GENERAL NOTES
Ø ROUND
AC AIR CONDITIONING UNIT
ACC AIR COOLING CONDENSER
ACCU AIR COOLING CONDENSING UNIT
AD AREA DRAIN
ADD ADDENDUM
AFF ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
ALT ALTERNATE
AP ACCESS PANEL
ARCH ARCHITECT/ARCHITECTURAL
AS AIR SEPARATOR
B BOILER
BFF BELOW FINISHED FLOOR
BTU BRITISH THERMAL UNITS
BTUH BRITISH THERMAL UNITS PER HOUR
CAP CAPACITY
CB CATCH BASIN
CFM CUBIC FEET PER MINUTE
CH CHILLER
CO CLEAN OUT
CT COOLING TOWER
CUH CABINET UNIT HEATER
CW COLD WATER
CWP CONDENSER WATER PUMP
CHWP CHILLED WATER PUMP
D DEGREE
DB DRY BULB
DBP DOMESTIC WATER BOOSTER PUMP
DCP DOMESTIC WATER CIRCULATING PUMP
DIA DIAMETER
DN DOWN
DW DISTILLED WATER
(E) EXISTING
ELEC ELECTRICAL
EQUIP EQUIPMENT
ET EXPANSION TANK
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
°F DEGREES FAHRENHEIT
FCO FLOOR CLEAN OUT
FCU FAN COIL UNIT
FD FLOOR DRAIN
FDV FIRE DEPARTMENT VALVE
FL FLOOR
FO FUEL OIL
FOV FUEL OIL VENT
FOR FUEL OIL RETURN
FOS FUEL OIL SUPPLY
FP FIRE PUMP
FPM FEET PER MINUTE
FS FLOOR SINK
FT FOOT/FEET
FU FIXTURE UNITS
FV FLUSH VALVE
GAL GALLON
GC GENERAL CONTRACTOR
GI GREASE INTERCEPTOR
GPM GALLONS PER MINUTE
GW GREASE WASTE
HB HOSE BIB
HP HORSE POWER
HRU HEAT RECOVERY UNIT
HW HOT WATER
HWP HEATING WATER PUMP
HX HEAT EXCHANGER
HYD HYDRANT
ID INDIRECT
IN INCH
INV INVERT
LB POUND
LP LOW PRESSURE
LPG LIQUEFIED PETROLEUM GAS
LVR LOUVER
MAX MAXIMUM
MBH ONE THOUSAND BTU PER HOUR
MCF ONE THOUSAND CUBIC FEET
MECH MECHANICAL
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MUA MAKE -UP/AIR
NIC NOT IN CONTRACT
NO NUMBER
NTS NOT TO SCALE
O OXYGEN
ORD OVERFLOW ROOF DRAIN
PD PRESSURE DROP
PIV POST INDICATOR VALVE
PRESS PRESSURE
PRV PRESSURE REDUCING VALVE
PSI POUNDS PER SQUARE INCH
PSIG POUNDS PER SQUARE INCH GAUGE
PWR POWER
(R) RELOCATE
RD ROOF DRAIN
REC RECESSED
RED REDUCER
RH RELATIVE HUMIDITY
RL/A RELIEF AIR
RM ROOM
RPM REVOLUTIONS PER MINUTE
RTU ROOF TOP UNIT
RW RAIN WATER
SF SQUARE FOOT
SAN SANITARY
SEP SEWAGE EJECTOR PUMP
SF SQUARE FOOT
SP STANDPIPE
SP STATIC PRESSURE
SP SUMP PUMP
STM STEAM
T THERMOSTAT
TD TEMPERATURE DROP
TDR TRENCH DRAIN
TEMP TEMPERATURE
TYP TYPICAL
UG UNDERGROUND
VAC VACUUM
V VENT
VENT VENTILATION
VTR VENT THROUGH ROOF
W WASTE
WCO WALL CLEAN OUT
WH WALL HYDRANT
WH WATER HEATER
(X) DEMOLITION
ABBREVIATIONS
2"
(E)
CD
G
MG
CA
CW
HW
HW -R
V
W
CONDENSATE DRAINAGE
NATURAL GAS (MEDIUM PRESSURE)
NATURAL GAS
HOT WATER
DOMESTIC COLD WATER
COMPRESSED AIR
HOT WATER RECIRCULATION
SANITARY SEWER (WASTE)
SANITARY VENT
EXISTING PIPE TAG
ABOVE GROUND PIPING
PIPE SIZE TAG (DIAMETER)
BELOW GROUND PIPING
PIPING BEING DEMOLISHED
PIPING SYSTEMS
OW OIL WASTE
OV OIL WASTE VENT
GV NATURAL GAS VENT
SYMBOLS
REVISION CLOUD
REVISION TAG
KEYNOTE 1
X
NORTH ARROW
N
MATCHLINE
POINT OF CONNECTION
POINT OF DEMOLITION
ITEM TO BE DEMOLISHED
AREA NOT IN CONTRACT
ALTERNATE CHECK VALVE
DOUBLE CHECK VALVE
REDUCED PRESSURE ZONE
SWING CHECK
CHECK VALVE
BALANCING VALVE
CIRCUIT SETTER
GATE VALVE
QUICK OPENING VALVE
BALL VALVE
FLUID STRAINER
THERMOSTATIC VALVE
TRAP PRIMER
ELEC. CONTROL VALVE
MIXING VALVE
WATER METER
IRRIGATION METER
GAS SHUTOFF COCK
PLUG VALVE
PLUMBING VALVES
SOLENOID VALVE
ELECTRIC TRAP PRIMER
GAS METER
EMERGENCY GAS SHUTOFF
PRESSURE REGULATOR
TEMP/PRESSURE RELIEF
PARKING DECK DRAIN
COMBINATION DRAIN
HOSE BIBB
WALL HYDRANT
PLUMBING FIXTURES
OUTLET BOX
CONDENSATE BOX
ROOF DRAIN
VENT THROUGH ROOF
OVERFLOW DRAIN
TRENCH DRAIN
WALL CLEANOUT
DOWNSPOUT NOZZLE
FLOOR CLEANOUT
CLEANOUT TO GRADE
FLOOR DRAIN
AREA DRAIN
HUB DRAIN (FUNNEL TYPE)
EQUIPMENT
RISER
DWV
0
WTR
0
PLUMBING TAGS
FIXTURE
X
XXX
EQUIPMENT TYPE
FLOOR UNIT IS
LOCATED ON
UNIT NUMBER
FIXTURE UNITS
FIXTURE TYPE/NUMBER
RISER NUMBER
SYSTEM TYPE
DETAIL CALLOUT
SHEET NUMBER
VIEW NUMBER OR DETAIL NUMBER
EQUIPMENT BY OTHERS
TAG NUMBER
XX-XXX
XX DFU
2" X-XX
XXX
MISC. FITTINGS & SYMBOLS
DIRECTION OF FLOW
1/8" PIPE SLOPE TAG
PIPE SLEEVE
HEAT TRACE
PIPE REDUCER
1/8"/FT
ELBOW UP
TEE DOWN
DROP TO LOWER ELEVATION
ELBOW DOWN TO LEVEL BELOW
PIPE CONTINUATION
ELBOW UP TO LEVEL ABOVE
RISER
90 DEGREE ELBOW
45 DEGREE ELBOW
CAP
JOINT OR COUPLING POINT
1/4" PIPE SLOPE TAG
1/4"/FT
UNION
1. DOMESTIC WELL PRODUCTION ASSUMED AT 8 GPM. WELLS AROUND THE AREA VARY IN PRODUCTION.
2. NO WATER STORAGE IN THE WELL CASING IS ASSUMED BASED ON THE VARIATION IN WELL DEPTHS IN
THE AREA. WELLS IN THE AREA VARY IN DEPTH.
3. DOMESTIC WELL WATER EXPANSION TANK SIZED BASED ON ESTIMATED FLOW AND REQUIRED
VOLUME FOR BUILDING. MAY REQUIRE MODIFICATION UPON FINAL WELL CONDITIONS.
4. DOMESTIC WELL WATER QUALITY ASSUMED TO BE WITHIN THE LIMITS OF EQUIPMENT MANUFACTURER
AND THE STATE AND FEDERAL REQUIREMENTS . WATER TREATMENT MAY BE REQUIRED BASED UPON
FINAL WELL CONDITIONS.
* NOTE *
DOMESTIC WELL WATER DESIGN AND EQUIPMENT SELECTED ARE BASED ON THE ASSUMPTIONS ABOVE.
WELL DESIGN AND FINAL EQUIPMENT SELECTIONS MAY CHANGE BASED ON FINAL WELL CONDITIONS.
DOMESTIC WELL AND WATER NOTES
drawn by:
checked by:
date:
project #:
sheet title:
sheet
number:
www.dsgw.com
03/10/2026
25323
AWM
CDH
Brule Public
Works
Garage
P0.1
COVER SHEET
PLUMBING SHEET INDEX
P0.1 COVER SHEET
P0.2 SCHEDULES
P0.3 SCHEDULES
P2.1 UNDERFLOOR PLAN
P2.2 FLOOR PLAN
P3.1 ENLARGED FLOOR PLAN
P5.1 DETAILS
P5.2 DETAILS
P6.1 DIAGRAMS
revision / issue no. date
CALENN
HEPPNER
E-48270
03/09/2026
drawn by:
checked by:
date:
project #:
sheet title:
sheet
number:
www.dsgw.com
03/10/2026
25323
AWM
CDH
Brule Public
Works
Garage
P0.2
SCHEDULES
B. PROVIDE TRAP PRIMER TO ALL FLOOR SINKS NOT RECEIVING DISCHARGE FROM A LISTED PLUMBING FIXTURE.
A. PROVIDE TRAP PRIMER TO ALL FLOOR DRAINS.
GENERAL NOTES:
WCO-1 WALL CLEANOUT JAY R SMITH 4530 SERIES - CAST IRON BODY, TAPERED BRONZE PLUG, HUBLESS CONNECTIONS, SS COVER WITH SCREW
FCO-1 FLOOR CLEANOUT JAY R SMITH 4020 SERIES - CAST IRON BODY, TAPERED BRONZE PLUG, FLASHING FLANGE, VANDAL RESISTANT
TD-1 TRENCH DRAIN JAY R SMITH 9872 SERIES N ON GRADE OR LOADING DOCK, POLYMER CONCRETE CHANNEL, INTEGRAL GALVANIZED RAIL, DUCTILE IRON GATE
FS-1 FLOOR SINK JAY R SMITH 3101 SERIES Y FINISHED AREAS, ACID RESISTANT COATED, VANDAL PROOF, 1/2 GRATE, CAST IRON BODY, SEDIMENT BUCKET,
FLASHING COLLAR, ALUMINUM STRAINER, NO-HUB OUTLET
FD-1 FLOOR DRAIN JAY R SMITH 2005 SERIES Y FINISHED AREAS, ROUND NICKEL BRONZE VANDAL RESISTANT GRATE, CAST IRON BODY, FLASHING COLLAR,
ADJUSTABLE STRAINER, NO-HUB OUTLET
ID DESCRIPTION MANUFACTURER
& MODEL
TRAP PRIMER
CONNECTION (Y/N) NOTES
DRAINS AND CLEANOUTS SCHEDULE
E. DISCONNECT FURNISHED AND INSTALLED BY DIVISION 26.
D. ALL COMPONENTS TO CONFORM TO NSF-61 LEAD CONTENT STANDARDS.
C. WATER HEATERS TO BE PERMITTED AND INSPECTED FOR COMPLIANCE UNDER LOCAL BOILER CODE.
B. PROVIDE NEUTRALIZER FOR WATER HEATER CONDENSATE DRAINS AND ROUTE TO NEARBY FLOOR SINK.
A. PROVIDE TEMPERATURE AND PRESSURE RELIEF AND ROUTE TO NEARBY FLOOR SINK. PROVIDE VACUUM RELIEF FOR WATER HEATERS LOCATED ABOVE FIXTURES SERVED.
GENERAL NOTES:
GWH-101 MECHANICAL ROOM DOMESTIC HOT WATER GAS WATER H EATER A.O. SMITH ATHR-199MX 95 90 3/4" 1/2 3.5-10.5 199 120/ 0 110 ALL
INLET
PRESSURE (W.C.)
FLOW
(CFH) VOLT/PHASE ID LOCATION AREA SERVED WATER HEATER TYPE MANUFACTURER M ODEL EFFICIENCY
(%)
DESIGN TEMP
RISE (°F)
WATER
CONNECTION
SIZE (IN)
GAS
CONNECTION
SIZE (IN)
FUEL ELECTRICAL DRY
WEIGHT
(LBS)
NOTES
GAS WATER HEATER SCHEDULE
A. FINAL FIXTURE SELECTION TO BE COORDINATED WITH INTERIORS AND OWNER.
GENERAL NOTES:
WH-3 - WALL HYDRANT HOT AND COLD CONNECTION, INTERIOR SURFACE MOUNT,
VACUUM BREAKER - CHICAGO FAUCET 835-CF - - 3/4 - - - - -
WH-2 - WALL HYDRANT FREEZE PROOF, INTEGRAL VACUUM BREA KER - WOODFORD MODEL 14 - - 3/4 - - - - -
WH-1 - WALL HYDRANT INTEGRAL VACUUM BREAKER - WOODFORD MO DEL 26 - - 3/4 - - - - -
EWS-1 - EMERGENCY EYEWASH WALL MOUNTED, LEFT SIDE MOUNTING, HAND OPERATED, SINGLE
ACTION OPERATION - GUARDIAN G1750 - - - - 1/2 - - -
SB-1 - SUPPLY BOX (REFRIGERATOR) 1/4 TURN BOTTOM VALV SUPPLY, WATER HAMMER
ARRESTOR, COPPER SWEAT
ICE MAKER
OUTLET... OATEY 39140 - - 1/2 - - - - -
DF-1 Y DRINKING FOUNTAIN WALL HUNG, SINGLE, ADA, BOTTL E FILLER - ELKAY LZS8WSSP 2 1-1/2 1/2 - - - - -
FAUCET MUSTEE 93.6 US-1 N UTILITY SINK FLOOR SUPPORTED, 23"x20-1/2"x46-1/2" HEIGHT,
INTEGRAL GOOSENECK SPOUT
BASIN MUSTEE 17 UTILATUB 2 1-1/2 1/2 1/2 - 2.0 - -
FAUCET MOEN 8230 M-DURA MS-1 N MOP SINK CORNER MOUNTED, 24"x24"x10" HEIGHT, WALL GUARDS,
HEAVY DUTY CHROME PLATED BRASS DUAL HANDLE FAUCET
BASIN MUSTEE 63M 3 2 3/4 3/4 - 2.2 - -
FAUCET KOHLER K-597 S-1 Y SINK SINGLE COMPARTMENT UNDERMOUNT, 20"x18-5/16"x8-7/16" DEPTH,
16-GAUGE SS, PULL-DOWN FAUCET HEAD, ADA
BOWL KOHLER K-33153 2 1-1/2 3/4 3/4 - 1.5 - -
FAUCET KOHLER K-27388-4N L-2 Y LAVATORY WALL HUNG, 20-3/4"x18-1/4",
MANUAL CENTERSET FAUCET, ADA
BOWL KOHLER K-2032-N 2 1-1/2 1/2 1/2 - 0.5 - N
FLUSH VALVE KOHLER K-76321 WC-1 Y WATER CLOSET WALL MOUNTED, MANUAL
FLUSH VALVE, ADA, OPEN FRONT TOILET SEAT
BOWL KOHLER K-84325-L 3 2 1-1/2 - - - 1.28 N
COMPONENT MANUFACTURER MODEL W V CW HW TW ID ADA
(Y/N) TYPE DESCRIPTION BASIS OF DESIGN MANUFACTURER & MODEL NUMBER ROUGH-IN SIZE (IN) GPM GPF ELEC.
CONN. (Y/N)
PLUMBING FIXTURE SCHEDULE
J. COORDINATE ELECTRICAL DISCONNECT, FEEDER SIZE, OVERCURRENT PROTECTION, AND GROUNDING WITH DIVISION 26.
I. PROVIDE FACTORY-SUPPLIED COMPRESSOR CONTROLS INCLUDING START/STOP SWITCH, OVERLOAD PROTECTION, AND PRESSURE GUAGE, IF NOT INTEGRAL TO EQUIPMENT.
H. VERIFY REQUIRED CLEARANCES FOR SERVICE, VENTILATION, AND HEAT REJECTION PER MANUFACTURER REQUIREMENTS.
G. PROVIDE DISCHARGE CHECK VALVE AND ISOLATION VALVE BETWEEN COMPRESSOR PACKAGE AND AIR DISTRIBUTION PIPING.
F. ROUTE CONDENSATE FROM COMPRESSOR, DRYER, AND RECEIVER TO OIL-WATER SEPARATOR PRIOR TO DISCHARGE IN ACCORDANCE WITH LOCAL CODE REQUIREMENTS.
E. AIR RECEIVER SHALL BE ASME RATED WITH PRESSURE RATING NOT LESS THAN SYSTEM MAXIMUM PRESSURE AND SHALL INCLUDE PRESSURE RELIEF VALVE, PRESSURE GAUGE, AUTOMATIC CONDENSATE DRAIN, AND ISOLATION VALVE.
D. PROVIDE VIBRATION ISOLATION AT COMPRESSOR BASE AND FLEXIBLE CONNECTOR AT DISCHARGE PIPING.
C. ANCHOR COMPRESSOR AND RECEIVER TO PAD PER MANUFACTURER BRACING REQUIREMENTS WHERE APPLICABLE.
B. 4" CONCRETE PAD FOR AIR COMPRESSOR TO BE FURNISHED AND INSTALLED BY G.C.
B. PROVIDE AIR DRYER PER MANUFACTURER’S PUBLISHED INSTALLATION REQUIREMENTS.
A. INSTALL AIR COMPRESSOR SYSTEM PER MANUFACTURER’S PUBLISHED INSTALLATION REQUIREMENTS.
GENERAL NOTES:
AC-101 MECHANICAL ROOM VERTICAL FLEXILLA FXS07V080V1 80 3 3 175 60 PISTON TEFC 3/4 7.5 240 1 800
OULET
HP VOLTAGE PHASE
ID (EQUIPMENT ID) LOCATION TYPE MANUFACTURER MODEL TANK SIZE
(GAL)
MAX FLOW
(CFM @100
PSIG)
MAX
PRESSURE
(PSIG)
MAX NOISE
LEVEL (dB) COMPRESSOR TYPE MOTOR TYPE
CONNECTIONS
(IN)
ELECTRICAL DRY
WEIGHT
(LBS)
AIR COMPRESSOR SCHEDULE
1/2" 253 CFH
1-1/4" 3/4" 528 CFH
REQUIRED PIPE SIZE: 1" 945 CFH
1 1/4" 1,940 CFH
1 1/2" 2,910 CFH
1.0 PSI PRESSURE DROP 2" 5,600 CFH
LESS THAN 2.0 PSI PRESSURE 2 1/2" 8,920 CFH
3" 15,800 CFH
SCHEDULE 40 STEEL PIPE 4" 32,200 CFH
GAS: NATURAL GAS PIPE CAPACITIES
TOTAL DEVELOPED LENGTH (FT) 300
TOTAL DEMAND (CFH) 1,859
TOTAL DEMAND (BTUH) 1,859,000
GENERATOR 1 975,000 975,000
HVAC - BOILER 1 285,000 285,000
HVAC - GAS UNIT HEATER 2 200,000 400,000
WATER HEATER 1 199,000 199,000
FIXTURE QTY BTU/HR INPUT TOTAL BTU/HR
GAS CALCULATIONS
2. PROVIDE WITH ISOLATION VALVES AND INLET STRAINER
1. INSTALL PER PLANS.
NOTES:
A. NSF 61 LISTED DEVICE.
GENERAL NOTES:
BV-1 CALEFFI THERMOSETTER 1164 0.35 2.1 3 1/2 1/2 303 STAIN LESS 1, 2
MIN
(GPM)
MAX
(GPM)
INLET DIA.
(IN)
OUTLET DIA.
(IN) MATERIALS ID MANUFACTURER MODEL
FLOW RATE MAX PRESSURE
DROP
(PSI)
VALVE PROPERTIES
NOTES
BALANCING VALVE SCHEDULE
3. PROVIDE AQUASTAT SET TO OPERATE WHEN RETURN WATER TEMPERATURE IS BELOW 105°F.
2. PROVIDE 304 STAINLESS STEEL BODY.
1. ECM MOTOR.
NOTES:
D. IN-LINE CIRCULATOR SHALL BE PROVIDED WITH CONNECTING FLANGE KIT BASED ON PUMP INLET SIZE AND CONNECTING PIPE SIZE.
C. PUMP SHALL BE LEAD FREE AND APPROVED FOR USE IN POTABLE WATER SYSTEMS.
B. POWER TYPE: S = LEGALLY REQUIRED STANDBY POWER
A. POWER AND WIRING DISCONNECTS FURNISHED AND INSTALLED BY DIVISION 26.
GENERAL NOTES:
RCP-101 HOT WATER RECIRCULATION PUMP MECHANICAL ROOM I N-LINE DOMESTIC WATER B & G ECO-CIRC 20-18 120 5 35 1750 1/ 6 120/1 - 1, 2, 3
FLOW
(GPM)
HEAD
(FT) RPM HP VOLT/
PHASE
ID DESCRIPTION LOCATION TYPE FLUID TYPE MANUFACTURER MODE L
FLUID
TEMP.
(F)
PERFORMANCE DATA ELECTRICAL
POWER
TYPE NOTES
CIRCULATION PUMP SCHEDULE
SUPPLY SYSTEM. TABLE 382.40-5.
A. SIZING BASED ON SPS 382 APPENDIX A RECOMMENDED RULES FOR SIZING THE WATER
NOTES:
2 20 - -
1-1/2 12 - -
1-1/4 6.8 - -
1 4.9 - -
3/4 2.9 - -
1/2 1.2 - -
RECIRC HOT WATER
2 38 - 78
4 PSI PRESSURE DROP PER 100 FT LENGTH 1-1/2 19 - 28
1-1/4 11 - 15
RECIRC HOT WATER: UNDER 2 FT/SEC 1 6 - 7
HOT WATER: UNDER 5 FT/SEC 3/4 3 - 3
COLD WATER: UNDER 8 FT/SEC 1/2 1.25 - 0
VELOCITY: HOT WATER
2 70 108 225
1-1/2 34 18.5 66
VELOCITY UNDER 8 FT/SEC 1-1/4 21.5 7 33
2" MAIN IS REQUIRED WITH A 1 12 4 16.5
3/4 6 0 7
1/2 2 0 2
ALL WATER SIZES PER SPS 382. COLD WATER
PIPE SIZE
(IN) MAX FLOW (GPM) MAXIMUM FIXTURE UNITS
(FLUSH VALVES)
MAXIMUM FIXTURE UNITS
(NON FLUSH VALVES)
COPPER PIPE SIZING
1. GAS METER AND UTILITY CONNECTION TO BE PROVIDED AND INSTALLED BY THE GAS UTILITY COMPANY.
NOTES:
GM-101 EXTERIOR BUILDING 2" 2 798 - - 1
ID LOCATION SERVICE OUTLET CONNECTION SIZE (IN) OPERATI NG PRESSURE (PSIG) LOAD (CFH) MANUFACTURER MODEL NOTES
GAS METER SCHEDULE
revision / issue no. date
CALENN
HEPPNER
E-48270
03/09/2026
(BEFORE THICKNESS ADJUSTMENT REQUIRED IN NOTE D) BUT NOT TO THICKNESSES LESS THAN 1 INCH.
D. FOR DIRECT-BURIED HEATING AND HOT WATER SYSTEM PIPING, REDUCTION OF THESE THICKNESSES BY 1-1/2 INCHES SHALL BE PERMITTED
BY 1 INCH (25 MM) SHALL BE PERMITTED (BEFORE THICKNESS ADJUSTMENT REQUIRED IN NOTE 1) BUT NOT TO A THICKNESS LESS THAN 1 INCH.
C. FOR PIPING SMALLER THAN 1-1/2 INCH AND LOCATE IN PARTITIONS WITHIN CONDITIONED SPACES, REDUCTION FOR THESE THICKNESSES
B. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
A. MINIMUM PIPE INSULATION PER CURRENT ASHRAE 90.1, LOCAL ENERGY AND PLUMBING CODES.
GENERAL NOTES:
NON-POTABLE COLD WATER, ABOVE & BELOW GRADE
RECLAIMED WATER, ABOVE & BELOW GRADE
DOMESTIC COLD WATER, ABOVE & BELOW GRADE
IRRIGATION PIPING, INSIDE BUILDING
TRAPS AND TRAP PRIMER LINES (UNHEATED SPACES)
40 - 60 0.21 - 0.27 75 0.5 0.5 1.0 1.0
DOMESTIC HOT WATER SUPPLY/RETURN, ABOVE & BELOW GRADE
SOLAR HOT WATER SUPPLY/RETURN 105 - 140 0.21 - 0.28 100 1.0 1.0 1.5 2.0
DOMESTIC HOT WATER SUPPLY/RETURN, ABOVE & BELOW GRADE
SOLAR HOT WATER SUPPLY/RETURN 141 - 200 0.25 - 0.29 125 1.5 1.5 2.0 2.0
NOMINAL INSULATION THICKNESS (IN)
CONDUCTIVITY
(BTU-IN/(HR-SF-°F))
MEAN RATING
TEMPERATURE (°F) < 1 1 TO < 1-1/2 1-1/2 > 2 SYSTEM FLUID OPERATING
TEMPERATURE RANGE (°F)
INSULATION CONDUCTIVITY NOMINAL PIPE OR TUBE DIAMETE R (IN)
MINIMUM PIPE INSULATION (HOT AND COLD WATER SYSTEMS)
TRAP PRIMING LINES BELOW GRADE 3/4" AND SMALLER COPPER TUBE TYPE L ANNEALED ASTM B88 WROUGHT COPPER SOLDERED
ANSI B16.22
ABOVE GRADE BLACK STEEL SCHEDULE 40 ASTM A53 150 LB
ASTM A234 THREADED
NATURAL GAS
BELOW GRADE
ALL
BLACK STEEL SCHEDULE 40 ASTM A53 150 LB
ASTM A234 WELDED
SANITARY VENT ALL ALL PVC SCHEDULE 40
SOLID CORE DWV
ASTM D1785-15E1,
ASTM D2665-85a, ASTM D3311-82 PVC DWV
PVC SOLVENT CEMENT JOINTS IN ACCORDANCE
W/UPC SECTION 705.6.2, ASTM F656 PRIMER
ASTM D2564 SOLVENT CEMENT
ABOVE GRADE
(OVER SENSITIVE AREA) ALL CAST IRON NO HUB ASTM A888
ASTM A74
STAINLESS STEEL CLAMP
NEOPRENE GASKET ASTM C564
HEAVY DUTY COUPLINGS,
ASTM C1277, FM 1680
ABOVE GRADE ALL PVC SCHEDULE 40
SOLID CORE DWV
ASTM D1785-15E1,
ASTM D2665-85a, ASTM D3311-82 PVC DWV
PVC SOLVENT CEMENT JOINTS IN ACCORDANCE
W/UPC SECTION 705.6.2, ASTM F656 PRIMER
ASTM D2564 SOLVENT CEMENT
SANITARY SEWER
BELOW GRADE ALL PVC SCHEDULE 40
SOLID CORE DWV
ASTM D1785-15E1,
ASTM D2665-85a, ASTM D3311-82 PVC DWV
PVC SOLVENT CEMENT JOINTS IN ACCORDANCE
W/UPC SECTION 705.6.2, ASTM F656 PRIMER
ASTM D2564 SOLVENT CEMENT
2" AND SMALLER COPPER TYPE L ASTM B88 WROUGHT COPPER SOLDERED
ANSI B16.22
ABOVE GRADE
2-1/2" THRU 4" COPPER TYPE L ASTM B88 WROUGHT COPPER BRAZED
ANSI B16.50
DOMESTIC
HOT AND RECIRCULATED HOT WATER
BELOW GRADE 2" AND SMALLER COPPER TYPE K ASTM B88 WROUGH T COPPER SOLDERED
SIZE MATERIAL TYPE STANDARD FITTINGS JOINTS SYSTEM LOCATION SPECIFICATION
PIPE SCHEDULE
drawn by:
checked by:
date:
project #:
sheet title:
sheet
number:
www.dsgw.com
03/10/2026
25323
AWM
CDH
Brule Public
Works
Garage
P0.3
SCHEDULES
4. INLET TO FLI SHALL BE 6 INCHES TO PROMOTE INCREASED SAND FLOW. OUTLET SHALL BE 4 INCHES TO MATCH DOWNSTREAM PIPING SIZE.
3. CONTRACTOR TO SUPPLY AND INSTALL ALL PIPING AND SAMPLING TEES, CLEANOUTS, VENTS, AND FILL WITH CLEAN WATER PRIOR TO FIRST USE.
2. PROVIDE MFG SPECIFIC RISER TO PLACE ACCESS LID AT GRADE.
1. PROVIDE WITH RISERS AND HS-20 TRAFFIC RATED LID.
NOTES:
FLI-101 POLYPRO - UNDERGROUND BURIED GARAGE 100 STRIEM F LI-500 500 100 6/4 71 60 62 860 1, 2
(GAL) (GPM) HEIGHT LENGTH WIDTH ID DESCRIPTION LOCATION SERVICE MANUFACTURER MODEL CAPACITY INLET/OUTLET
(IN)
DIMENSIONS (IN) OPERATING
WEIGHT (LBS) NOTES
FLAMMABLE LIQUID INTERCEPTOR SCHEDULE
1. TANK SHALL HAVE A HEAVY DUTY REMOVABLE BLADDER. VERIFY ACCEPTABLE CHARGE PRESSURE FOR INSTALLATION LOCATION. PROVIDE SIGHT GLASS, PRESSURE GAUGE, TOP & BOTTOM CONNECTIONS, WALL MOUNTING BANDS, & CHARGING VALVE.
NOTES:
DET-101 DOMESTIC WATER EXPANSION TANK MECHANICAL ROOM DOMESTIC WATER THERMAL EXPANSION - POTABLE PROFLO PFXT 5I 40 150 150 2.1 2.1 3/4 3/4 5 30 1,2
(LBS) (LBS) NOTES
WEIGHT WEIGHT ID DESCRIPTION LOCATION SERVICE TYPE MANUFACTURER MODEL
FILL
PRESSURE
(PSIG)
MAX
PRESSURE
(PSIG)
RELIEF
VALVE
(PSIG)
TANK
VOLUME
(GAL)
ACCEPT.
VOLUME
(GAL)
INLET
PIPE SIZE
(IN)
OUTLET
PIPE SIZE
(IN)
SHIPPING
TANK SCHEDULE
1. SERVES ONE EMERGENCY EYEWASH.
EFMV-101 101 MECH/ELEC EWS-1 GUARDIAN G6020 13 30 1/2 1/2 40 120 80 1
FLOW (GPM) PRESSURE DROP (PSI) ID LOCATION SERVICE MANUFACTURER MODEL DESIGN INLET SIZE
(IN)
OUTLET
SIZE (IN)
COLD WATER
INLET TEMP (F)
HOT WATER
INLET TEMP (F)
OUTLET
SETPOINT (F) NOTES
EMERGENCY FIXTURE MIXING VALVE SCHEDULE
THE PROCEDURE SHALL BE REPEATED WHEN A STANDARD BACTERIOLOGICAL TEST FOR DRINKING WATER, PERFORMED BY A LABORATORY CERTIFIED FOR DRINKING
WATER IN WASHINGTON STATE, SHOWS UNSATISFACTORY RESULTS INDICATING THAT CONTAMINATION PERSISTS IN THE SYSTEM.
FOLLOWING THE ALLOWED STANDING TIME, THE SYSTEM SHALL BE FLUSHED WITH CLEAN, POTABLE WATER UNTIL THE CHLORINE RESIDUAL IN THE WATER COMING
FROM THE SYSTEM DOES NOT EXCEED THE CHLORINE RESIDUAL IN THE FLUSHING WATER.
THE SYSTEM OF PARTS THEREOF SHALL BE FILLED WITH A WATER-CHLORINE SOLUTION CONTIANING NOT LESS THAN 50 PARTS PER MILLION OF CHLORINE, AND THE
SYSTEM OR PART THEREOF SHALL BE VALVED-OFF AND ALLOWED TO STAND FOR 24 HOURS; OR, THE SYSTEM OR PART THEREOF SHALL BE FILLED WITH A
WATER-CHLORINE SOLUTION CONTIANING NOT LESS THAN 200 PARTS PER MILLION OF CHLORINE AND ALLOWED TO STAND FOR 3 HOURS.
THE PIPE SYSTEM SHALL BE FLUSHED WITH CLEAN, POTABLE WATER UNTIL POTABLE WATER APPEARS AT THE POINT OF THE OUTLET.
NEW OR REPAIRED POTABLE WATER SYSTEMS SHALL BE DISINFECTED PRIOR TO USE WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION. THE METHOD TO BE
FOLLOWED SHALL BE THAT PRESCRIBED BY THE HEALTH AUTHORITY OR, IN CASE NO METHOD IS PRESCRIBED BY IT, THE FOLLOWING:
DISINFECTION OF POTABLE WATER SYSTEM
2. PROVIDE WITH PRESSURE SWITCH, PRESSURE GAUGE, DRAIN VALVE AND RELIEF VALVE.
1. TANK SHALL HAVE A HEAVY DUTY REMOVABLE BLADDER. VERIFY ACCEPTABLE CHARGE PRESSURE FOR INSTALLATION LOCATION. PROVIDE SIGHT GLASS, PRESSURE GAUGE, TOP & BOTTOM CONNECTIONS, WALL MOUNTING BANDS, & CHARGING VALVE.
NOTES:
WET-101 DOMESTIC WELL WATER EXPANSION TANK MECHANICAL ROOM DOMESTIC WATER WELL WATER - POTABLE B&G WTA-452 40 60 125 100 211 56 2 - 475 2400 1,2
(LBS) (LBS) NOTES
WEIGHT WEIGHT ID DESCRIPTION LOCATION SERVICE TYPE MANUFACTURER MODEL
LOW FILL
PRESSURE
PUMP ON (PSIG)
HIGH FILL
PRESSURE PUMP
OFF (PSIG)
MAX
PRESSURE
(PSIG)
RELIEF
VALVE
(PSIG)
TANK
VOLUME
(GAL)
DRAW
DOWN
(GAL)
INLET
PIPE SIZE
(IN)
OUTLET
PIPE SIZE
(IN)
SHIPPING
DOMESTIC WELL EXPANSION TANK SCHEDULE BY WELL CONTRACTOR
revision / issue no. date
CALENN
HEPPNER
E-48270
03/09/2026
1
2
3
4
5
7
8
A B
2" CW
4" W NATURAL GAS BY
THE UTILITY.
SEE CIVIL FOR
CONTINUATION
4" W
I.E. 6.5' B.F.F.
SEE CIVIL FOR
CONTINUATION
6
2" CW
I.E. 6.5' B.F.F.
SEE CIVIL FOR
CONTINUATION
FLI-101
NATURAL GAS
UP TO METER.
2" CW UP
3" V UP
6" OW
2" W UP
3" W UP
3" W UP
2" V UP
3" W 2" W 3" W
3" W
4" W 4" W
2" W
2" W UP
2" W UP
4" W
3" W 3" W 3" W
9
2" W
2" W UP
6" W UP
4" W UP
1
P5.1
2" W UP
2" V UP 3" W UP
2" W UP
2" V UP 2" V UP
2" W UP
1 1/4" G UP 1 1/4" G TO
GENERATOR.
4" W UP
3" W UP
3" W UP
3" W UP
4" W
GENERAL SHEET NOTES:
A. UTILITY CONNECTIONS 5' -0" FROM BUILDING EDGE.
drawn by:
checked by:
date:
project #:
sheet title:
sheet
number:
www.dsgw.com
03/10/2026
25323
AWM
CDH
Brule Public
Works
Garage
P2.1
UNDERFLOOR
PLAN
SCALE: 1/8" = 1'-0" 1 UNDERFLOOR FLOOR PLAN - PLUMBING
revision / issue no. date
CALENN
HEPPNER
E-48270
03/09/2026
REF.
G
1
2
3
4
5
7
8
A B
meeting room
105
garage
100
staff tlt
103
staff area
104
6" TD-1
WH-1
WH-3
WH-2
WH-2
WH-2
P3.1
1
1" CA
6
storage
102
4" FCO
4" FCO
3/4" CW
1/2" G
4
P5.2
3/4" CA
3/4" CA
3/4" CA
3/4" CW
1
P5.2 3/4" CA DN
1
P5.2 3/4" CA DN
3/4" CA
1
P5.2 3/4" CA DN
3" V DN
4" VTR
Storage
112
Office
110
Hallway
109
Utility
107
Toilet Rm
106
Toilet Rm
108
9
2
P5.1
1 1/2" G
10
P5.1
3/4" CA DN
3/4" CA DN
3/4" CW DN
1
P5.2
1
P5.2
3/4" CA DN 1
P5.2
4
P5.1
1
1
1
GM-101 2GENERATOR
FLI -101
(BELOW)
1 1/4" G DN
4
P5.2 1 1/4" G TO GENERATOR
3
3" V
3/4" CW
3/4" HW
1/2" G
3" V
3/4" CW DN
3/4" HW DN
3/4" CW
3/4" CA
3/4" CA DN 1
P5.2
GENERAL SHEET NOTES:
A. THESE DRAWINGS ARE DIAGRAMMATIC AND INDICATE THE
GENERAL ARRANGEMENT OF SYSTEMS AND EQUIPMENT. FINAL
LOCATIONS OF EQUIPMENT AND PIPING SHALL BE FIELD
DETERMINED.
B. FOR SIZING NOT SHOWN ON FLOOR PLANS, REFER TO DETAI LS AND
DIAGRAMS FOR MORE DETAIL.
C. PROVIDE CLEANOUTS WHERE REQUIRED BY WISCONSIN PLUMBING
CODE AND DETAIL 6/P5.1.
drawn by:
checked by:
date:
project #:
sheet title:
sheet
number:
www.dsgw.com
03/10/2026
25323
AWM
CDH
Brule Public
Works
Garage
P2.2
FLOOR PLAN
SCALE: 1/8" = 1'-0" 1 FLOOR PLAN - PLUMBING
KEYNOTES:
1 COORDINATE FINAL LOCATIONS OF COMPRESSED AIR DROPS WITH
OWNER PROVIDED WORK BENCH.
2 NATURAL GAS METER BY UTILITY COMPANY. MAINTAIN 3' CLEARANCE
BETWEEN GAS REGULATOR AND ELECTRICAL METER AND A 10'
CLEARANCE FROM OPERABLE OPENINGS.
3 COORDINATE FINAL LOCATIONS OF WH-1 WITH OWNER PRO VIDED WORK
BENCH.
revision / issue no. date
CALENN
HEPPNER
E-48270
03/09/2026
REF.
W
5
7
8
A B
GWH-101
US-1
3" FD-1
3" FS-1
6
2" CW DN
3
P5.2
1/2" CW DN
1/2" HW DN
L-1
WC-1
WC-1
L-1 L-1
WC-1
S-1
3" FD-1 3" FD-1
3" FD-1
SB-1
EWS-1
1
P2.2
WH-2
1 1/4" CW
1 1/4" CW
1/2" HW
1 1/4" CW
1/2" HW
1/2" HW DN
1/2" CW DN
1/2" HW
1 1/4" CW
2" CW 3/4" HW
1/2" HW -R
1/2" CW
DF-1
2" W DN
1 1/2" V UP 1/2" G DN
1/2" G DN
3/4" CW UP
3/4" HW UP
3/4" G UP
2
P5.2 AC-101
WET-101
1/2" HW -R
1/2" HW -R DN
2" V DN
1 1/4" CW DN
2" V DN
1
1 1/2" G
1/2" HW DN
3" V DN
1/2" CW DN
RCP-101
DET-101
storage
102
mech/elec
101
staff area
104
staff tlt
103
Toilet Rm
106
Toilet Rm
108
Utility
107
Hallway
109
meeting room
105
MS-1
1 1/2" G
2
6
P5.2
1" CA UP 3
3
4 4
4
3/4" CW
1/2" CW
1/2" HW
1/2" HW -R
1 1/2" CW
1 1/2" CW
1/2" HW -R
1/2" HW
1/2" CW UP
1 1/2" V UP
1 1/2" V UP
1 1/4" CW
1/2" CW
1 1/2" V
1 1/2" V
1/2" CW
1/2" HW -R
2" V
1 1/2" V
1 1/2" CW
1/2" HW -R DN
1/2" HW DN
1 1/2" V DN
1/2" CW DN
WCO-1
WCO-1
7
P5.2
WCO-1
4" W DN
1/2" HW -R DN
2" V DN
1 1/4" CW DN
1 1/2" V DN
2" CW 1 1/2" V DN
3/4" CW
WCO-1
3" W DN
WCO-1
2" V DN
3" V UP
WCO-1
WCO-1
WCO-1
WCO-1
1
P2.2
5 67
8
3" V
2" V
3" V
5
7
A B
6
1" CA 3/4" HW
3/4" CW
1
P2.2
1
P2.2
3/4" G
1/2" G DN
3" V
3/4" CW DN
3/4" HW DN
3/4" G DN
1" CA DN
3" V DN
GENERAL SHEET NOTES:
A. THESE DRAWINGS ARE DIAGRAMMATIC AND INDICATE THE
GENERAL ARRANGEMENT OF SYSTEMS AND EQUIPMENT. FINAL
LOCATIONS OF EQUIPMENT AND PIPING SHALL BE FIELD
DETERMINED.
B. FOR SIZING NOT SHOWN ON FLOOR PLANS, REFER TO DETAI LS AND
DIAGRAMS FOR MORE DETAIL.
C. PROVIDE CLEANOUTS WHERE REQUIRED BY WISCONSIN PLUMBING
CODE AND DETAIL 6/P5.1.
drawn by:
checked by:
date:
project #:
sheet title:
sheet
number:
www.dsgw.com
03/10/2026
25323
AWM
CDH
Brule Public
Works
Garage
P3.1
ENLARGED
FLOOR PLAN
SCALE: 1/4" = 1'-0" 1 OVERHEAD PLAN - PLUMBING
SCALE: 1/4" = 1'-0" 2 FLOOR PLAN - MEZZANINE - PLUMBING
KEYNOTES:
1 DOMESTIC WELL WATER EXPANSION TANK AND PIPING TO W ELL BY THE
WELL CONTRACTOR.
2 COORDINATE WITH OWNER ON FINAL LOCATION OF AC-101 IN STORAGE
ROOM 102.
3 PROVIDE A TRAP PRIMER LINE FROM US-1. REFER TO DET AIL 5 ON P5.2.
4 PROVIDE A TRAP PRIMER LINE FROM L-1. REFER TO DETA IL 5 ON P5.2.
5 PVC VENT PIPING SHALL BE SEALED WITH A FIRE STOP P RODUCT TO
MAINTAIN THE FIRE RESISTANCE RATING OF THE WALL. TYPICAL.
COORDINATE FIRESTOP PRODUCT WITH PEMB MANUFACTURERS FIRE
RATED PANEL.
6 INSULATED PIPING SHALL BE SEALED WITH A FIRE STOP PRODUCT TO
MAINTAIN THE FIRE RESISTANCE RATING OF THE WALL. TYPICAL.
COORDINATE FIRESTOP PRODUCT WITH PEMB MANUFACTURERS FIRE
RATED PANEL.
7 GAS PIPING SHALL BE SEALED WITH A FIRE STOP PRODUC T TO MAINTAIN
THE FIRE RESISTANCE RATING OF THE WALL. COORDINATE FIRESTOP
PRODUCT WITH PEMB MANUFACTURERS FIRE RATED PANEL.
8 LOCATE PIPING AND EQUIPMENT AWAY FROM THE SPACE AB OVE
ELECTRICAL PANELS, TRANSFORMERS AND OTHER ELECTRICAL
EQUIPMENT LOCATED IN THE MECHANICAL ROOM.
revision / issue no. date
CALENN
HEPPNER
E-48270
03/09/2026
INSTALLED BY GAS
UTILITY COMPANY PIPING INTO BUILDING
TEE
CATHODIC PROTECTION
AS REQUIRED (TYP)
FROM SITE
GRADE
2"
5
1
2
4
3
1. GAS MAIN.
2. MAIN SHUT OFF VALVE.
3. GAS REGULATOR, GAS UTILITY COMPANY, SET TO 2 PSI OUT LET.
4. GAS METER BY GAS UTILITY COMPANY.
5. TRACER WIRE BY GAS UTILITY COMPANY.
KEYNOTES:
PIPING TO
GENERATOR
A. SEE SPECIFICATION SECTION 22 05 29 FOR SUPPORT REQUIREMENTS.
B. SEE SPECIFICATION SECTION 22 05 48 FOR VIBRATION ISOLATION AND SEISMIC
RESTRAINT REQUIREMENTS.
GENERAL NOTES:
STRAINER
REDUCER (TYP)
UNION (TYP)
SHUTOFF
VALVE (TYP)
DRAIN VALVE
PRESSURE -
TEMPERATURE
TEST PLUG (TYP)
PUMP
MOTOR
PIPE
CLEVIS HANGER
INSULATION
PIPE RING HANGER
GALVANIZED
STEEL SHIELD
HIGH DENSITY
INSULATION
INSERT OR WOOD
BLOCK SEE
SPECIFICATIONS
SIDE VIEW DETAIL
VENT
CONCRETE SLAB
NATIVE SOIL
ANCHOR KIT
CRUSHED
AGGREGATE OR
SAND
ANCHOR KIT ANCHOR KIT
RISERS TO GRADE
2-WAY CLEANOUT
TEE
2-WAY CLEANOUT TEE
EXCAVATION AND BACKFILL DETAIL
FLOW FLOW
CLEAN OUT TO GRADE
ON OUTLET PIPE OF
EACH UNIT
CLEAN OUT TO GRADE
ON INLET PIPE OF
EACH UNIT
NOTES:
SCHIER FLAMABLE LIQUID INTERCEPTORS ARE RATED AND MANUFACTURED WITH AN INTERNAL FLOW CONTROL SYSTEM ALREADY IN PLACE. THEY D O NOT
REQUIRE AN EXTERNAL FLOW CONTROL SYSTEM OR AIR INTAKE VENT. SCHIER FLAMABLE LIQUID INTERCEPTORS ARE NOT TO BE INSTALLED IN AN Y OTHER
MANNER EXCEPT AS SHOWN. CONSULT LOCAL CODES FOR SEPARATE TRAPPING REQUIREMENTS, CLEANOUT LOCATIONS AND ADDITIONAL INSTALLATI ON
INSTRUCTIONS.
FOR UNIT DETAILS REFER TO SPECIFICATION SHEET FOR SELEC TED UNIT
INVERT: -XX" BFF.
OPTIONAL OIL DRAW -
OFF
SEE PLANS
FOR SIZE ABOVE FLOOR
40"
HOSE BIBB
WALL SUPPORT BRACKETS AT 48" O.C.
MIN. BUT NOT LESS THAN TOP, BOTTOM
AND CENTER.
SHUT -OFF VALVE
BALL VALVE (TYP)
CHECK VALVE (TYP) DIGITAL TEMPERATURE
& PRESSURE
RECIRCULATION
RETURN SENSOR
DIGITAL TEMPERATURE
& PRESSURE MIXING
OUTLET SENSOR
DIGITAL TEMPERATURE
& PRESSURE COLD
INLET SENSOR
DIGITAL TEMPERATURE
& PRESSURE HOT
INLET SENSOR
UNION (TYP)
INCOMING HW
INCOMING CW
INCOMING HW -ROUTGOING TW
DIGITAL MIXING VALVE
AND ELECTRONIC
ACTUATOR
IF THIS ANGLE EXCEEDS 135° (2.36 RAD) -
A CLEANOUT IS REQUIRED
UPPER TERMINAL
CO
45° (TYP)
WC LAV
BT
4'
1/8 BENDS
4' -6"
A. CLEANOUTS SHALL BE PERMITTED TO BE OMITTED ON A HORIZONTAL
DRAIN LINE LESS THAN 5' (1,524 MM) IN LENGTH UNLESS SUCH LINE IS
SERVING SINKS OR URINALS.
B. CLEANOUTS SHALL BE PERMITTED TO BE OMITTED ON A HORIZONTAL
DRAINAGE PIPE INSTALLED ON A SLOPE OF 72° (1.26 RAD) OR LESS
FROM THE VERTICAL ANGLE (ONE -FIFTH BEND).
C. EXCEPT FOR THE BUILDING DRAIN, ITS HORIZONTAL BRANCHES, AND
URINALS, A CLEANOUT SHALL NOT BE REQUIRED ON A PIPE OR PIPING
THAT IS ABOVE THE FLOOR LEVEL OF THE LOWEST FLOOR O F THE
BUILDING.
D. AN APPROVED TYPE OF TWO -WAY CLEANOUT FITTING, INSTALLED
INSIDE THE BUILDING WALL NEAR THE CONNECTION BETWEEN THE
BUILDING DRAIN AND THE BUILDING SEWER OR INSTALLED OUTSIDE
OF A BUILDING AT THE LOWER END OF A BUILDING DRAIN AND
EXTENDED TO GRADE, SHALL BE PERMITTED TO BE SUBSTITUTED FOR
AN UPPER TERMINAL CLEANOUT.
EXCEPTIONS:
CLEANOUTS ARE REQUIRED AT UPPER
TERMINAL OF HORIZONTAL LINES
IF LESS THAN 5' (1,524 MM), CLEANOUTS ARE NOT
REQUIRED EXCEPT ON ALL URINALS AND
LOWEST LEVEL SINKS. CLEANOUTS ARE NOT
REQUIRED ON SINKS ABOVE THE LOWEST LEVEL.
UPPER TERMINAL LESS THAN 5' (1,524 MM) -
A CLEANOUT IS NOT REQUIRED
UPPER TERMINAL
CO
CO
A CLEANOUT IS REQUIRED AT THE JUNCTION BETWEEN
THE BUILDING DRAIN AND THE BUILDING SEWER
CO
[W} 707.4 LOCATION.
EACH HORIZONTAL DRAINAGE PIPE SHALL BE PROVIDED WITH A
CLEANOUT AT ITS UPPER TERMINAL, AND EACH RUN OF PIPING,
THAT IS MORE THAN 100 FEET (30,480 MM) IN TOTAL DEVELOPED
LENGTH, SHALL BE PROVIDED WITH A CLEANOUT FOR EACH 100
FEET (30,480 MM), OR FRACTION THEREOF, IN LENGTH OF SUCH
PIPING. AN ADDITIONAL CLEANOUT SHALL BE PROVIDED IN A
DRAINAGE LINE FOR EACH AGGREGATE HORIZONTAL CHANGE
IN DIRECTION EXCEEDING 135° (2.36 RAD).
TABLE 707.1 CLEANOUTS
SIZE OF PIPE
(INCHES)
SIZE OF CLEANOUT
(INCHES)
THREADS
(PER INCHES)
1-1/2
2
2-1/2
3
4 & LARGER
1-1/2
2-1/2
2-1/2
3-1/2
1-1/2
11 -1/2
11 -1/2
8
8
8
16 GA. GALVANIZED SHEET
METAL INSULATION
PROTECTION SHIELD - 12"
MIN. LENGTH ON PIPE
BELOW 60° F
CALCIUM SILICATE
INSULATION ON
INSUL. PIPE TO 4" SIZE
SUPPORT NUT
LOCKING NUT
PIPE
INSULATION
ALL THREAD
HANGER ROD.
SUPPORT
FROM
STRUCTURE*
* PROVIDE CONCRETE INSERTS OR FASTEN TO TOP
CHORDS AT BAR JOISTS OR OTHER STRUCTURAL
BEAMS. DO NOT FASTEN TO ROOF DECK OR JOIST
BRIDGING.
BOLT PIPE ROLLERS
TO CHANNEL
ROLLER AND STAND ON
PIPING ABOVE 60° F
SUPPORT
CHANNEL OR
ANGLE
STEEL PIPE SHOE ON
PIPES ABOVE 4" SIZE
(12" MIN LENGTH)
WELD
PIPE
INSULATION UNINSULATED PIPE
SLOPE SLOPE
REFER
TO STRUCT
TRENCH DRAIN
ANCHORAGE. REFER
TO STRUCTURAL.
TRENCH DRAIN GRATING AND
FRAME. REFER TO DRAINS
AND CLEANOUT SCHEDULE.
REINFORCED
CONCRETE FLOOR
SLAB. REFER TO
STRUCTURAL.
FLOOR SLAB
REINFORCING
CONTINUOUS 1/8"/FT
SLOPE AT TRENCH
BOTTOM TO DRAIN
REFER TO
PLUMBING
PLANS FOR
CONTINUATION
REFER TO ARCH REFER
TO STRUCT
REFER
TO STRUCT
WATERSTOP INSERT
DEPTH 12"
TRENCH DRAIN WITHOUT
TRAP BY MECHANICAL
FLOW
FLOOR
WALL
CLEANOUT PLUG
30"
SEAL
HUB
PIPE
USE LONG SWEEP ELL AND 45 WHEN
CO OCCURS AT END OF LINE.
SPIGOT
WALL ACCESS COVER
AND FRAME
drawn by:
checked by:
date:
project #:
sheet title:
sheet
number:
www.dsgw.com
03/10/2026
25323
AWM
CDH
Brule Public
Works
Garage
P5.1
DETAILS
NOT TO SCALE 2 GAS METER DETAIL
NOT TO SCALE 7 INLINE CIRCULATING PUMP DETAIL
NOT TO SCALE 8 INSULATED PIPE AT HANGER DETAIL
NOT TO SCALE 1 FLAMABLE LIQUID INTERCEPTORS DETAIL
NOT TO SCALE 4 INTERIOR HOSE BIBB PIPING RISER
NOT TO SCALE 3 DIGITAL MASTER MIXING VALVE DETAIL
NOT TO SCALE 5 SANITARY CLEANOUTS
NOT TO SCALE 6 TRAPEZE PIPE HANGER DETAIL
NOT TO SCALE 10 TRENCH DRAIN DETAIL
NOT TO SCALE 9 WALL CLEAN OUT DETAIL
revision / issue no. date
CALENN
HEPPNER
E-48270
03/09/2026
WALL
COMPRESSED
AIR MAIN
STRAP RISER TO WALL @
48" O.C., BUT NOT LESS
THAN TOP, BOTTOM &
CENTER
REGULATOR/FILTER
WITH DRAIN
1/2" QUICK CONNECT
COUPLING
FINISHED
FLOOR
6" DIRT LEG
BALL VALVE
& UNION
42"
1/2" RISER
CHECK OTHER DETAILS AND
SPECIFICATIONS FOR
CONFIGURATION.
2 STAGE AIR COMPRESSOR
AIR RECEIVER
FLOOR DRAIN
80 GAL.
PRESSURE GAUGE
PRESSURE REDUCING VALVE
WITH AUTOMATIC SHUTOFF.
SEE SCHEDULE FOR FLOW AND
PRESSURE REQUIREMENTS.
1" RELIEF VALVE
2" TO SYSTEM
2" AFTER COOLER (AIR COOLED)
2"
1"
3/4"
AIR
INTAKE
FILTER
AUTOMATIC
DRAIN TRAP
RELIEF
VALVE
VIBRATION
ISOLATORS
MOTOR WITH
STARTER
PRESSURE
CONTROL
SWITCH
CONCRETE PAD - 6" LARGER ALL AROUND
THAN RECEIVER INSTALLED
PRESSURE
GAUGE
COMBINATION
MOISTURE AND OIL
SEPARATOR
2" BYPASS
AUTOMATIC
DRAIN TRAP
FLEXIBLE TUBING
12" MINIMUM
LENGTH
DIRT LEG
EQUIPMENT
SHUT -OFF VALVE
PRESSURE REGULATOR
PIPE VENT OUTLET WITH
DOWNTURN ELBOW
UNION
WALL BRACKET
INLET
EYE -FACE WASH WITH
STAINLESS STEEL BOWL
EYEWASH VALVE
A. PROVIDE A LOOSE -KEY LOCKSHIELD TYPE SHUT -OFF VALVE IN
DOMESTIC WATER SUPPLY TROP TO EYEWASH STATION. LABEL
VALVE TO PREVENT UNAUTHORIZED SHUT -OFF.
B. PROVIDE WITH MANUFACTURER'S WALL MOUNTING BRACKET.
GENERAL NOTES:
MIXING VALVE
FLOW SWITCH
FLOW ALARM
ANNUNCIATOR
HW
SUPPLY CW SUPPLY
BALL VALVE WITH
MEMORY STOP AND
LABELING TO PREVENT
UNAUTHORIZED
SHUT -OFF
EYEWASH SANITARY DRAIN
A. PRIME FLOOR DRAINS, FLOOR SINKS, AND SIMILAR TRAPS.
B. REFER TO SPECIFICATIONS FOR ALLOWABLE TRAP PRIMER LINE PIPE MATERIALS.
GENERAL NOTES:
1. HOT AND COLD WATER SUPPLY STOP.
2. REFER TO MANUFACTURER LITERATURE FOR INSTALLATION INSTRUCTIONS.
KEYNOTES:
FINISHED FLOOR
TO SEWER
FACTORY TAPPED
P-TRAP
1/2" TUBING
TRAP PRIMER HOSE
ESCUTCHEON
1/2" COMPRESSION
FITTING
SLIP JOINT
NUT
TRAP PRIMER HOSE
1/2" COMPRESSION FITTING
SLIP JOINT NUT
ESCUTCHEON
1
WALL
1 1/2" P -TRAP
FLOOR DRAIN
1
DRAIN VALVE
(TYP)
NEUTRALIZER
HOT WATER
SUPPLY LINE
INCOMING CW
SUPPLY LINE
FLOOR SINK
ROUTE INTAKE/EXHAUST TO
ROOF OR APPROVED LOCATION
3/4" HW
3/4" G 3/4" CW
S
HW -R FROM
FIXTURES
1/2" HW -R
AIR SEPARATOR
EXPANSION TANK
RECIRCULATION PUMP
AUTOMATIC
AIR VENT
HW TO
FIXTURES
DIELECTRIC
UNION (TYP)
CHECK VALVE (TYP)
PRESSURE
RELIEF VALVE
CONDENSATE
DRAIN
BALL VALVE (TYP)
INCOMING G
SUPPLY LINE
DOMESTIC WELL. SEE
CIVIL DRAWINGS FOR
WELL LOCATION.
PITLESS ADAPTER
WELL CAP
CONDUIT
EXPANSION JOINT
WELL CASING
MIN. 6'
DEEP
2" CW
WELL PUMP
CONTROLLER
PRESSURE
TANK
PRESSURE SWITCH
2" CW
WELL PUMP
WELL SCREEN
WET-1
PIPING BEFORE THIS POINT
BY WELL CONTRACTOR &
PIPING BEYOND THIS POINT
BY PLUMBING CONTRACTOR
CHECK VALVE
DRAIN VALVE
ISOLATION VALVE
drawn by:
checked by:
date:
project #:
sheet title:
sheet
number:
www.dsgw.com
03/10/2026
25323
AWM
CDH
Brule Public
Works
Garage
P5.2
DETAILS
NOT TO SCALE 1 COMPRESSED AIR WALL OUTLET
NOT TO SCALE 2 VERTICAL AIR COMPRESSOR DETAIL
NOT TO SCALE 4 GAS PIPING CONNECTION FOR EQUIPMENT DETAIL
NOT TO SCALE 3 EMERGENCY EYEWASH PIPING DETAIL
NOT TO SCALE 5 SINK TAILPIECE TRAP PRIMER DETAIL
NOT TO SCALE 6 TANKLESS WATER HEATER - GAS
NOT TO SCALE 7 DOMESTIC WELL WATER SYSTEM DETAIL
revision / issue no. date
CALENN
HEPPNER
E-48270
03/09/2026
L-1
WC-1
WCO-1
FD-1
S-1
FD-1
WC-1
WC-1
MS-1
L-1
DF-1
FD-1
FS-1
FD-1
US-1
FCO
FCO
FLI-101
4" W
I.E. 6.5' B.F.F.
SEE CIVIL FOR
CONTINUATION
TD-1
4" VTR
4" W (6 DFU) 3" W (7
DFU) 4" W (13 DFU)
4" W (16 DFU)
L-1
3" W (4 DFU)
3" W (10 DFU)
3" W (19.5 DFU)
4" W (35.5 DFU)
3" W (6 DFU)
2" W (3 DFU)
2" V (6 DFU)
2" V (13 DFU)
3" V (25.5 DFU)
3" V (32.5 DFU)
3" V (44.5 DFU)
EWS-1
2" W (2 DFU)
3" V
6" W
2" W (2 DFU)
WCO-1
WCO-12" W (1 DFU)
4" W
3" W (6 DFU)
2" V (6 DFU)
2" W (0.5 DFU)
1 1/2" V (0.5 DFU)
2" V (3 DFU)
3" W (3 DFU)
2" V (3 DFU)
3" W (3 DFU)
2" V (3 DFU)
3" W (6 DFU)
3" W (3 DFU)
3" W (6 DFU)
2" V (6 DFU)
2" V (6 DFU)
2" V (3 DFU)
2" W (1 DFU)
1 1/2" V (1 DFU)
4" W (14 DFU)
4" W
4" W (3 DFU)
4" W (11 DFU)
3" V
1-1/2" V (2 DFU)
1-1/2" V (1 DFU)
1-1/2" V (3 DFU)
1-1/2" V (1 DFU)
1-1/2" V (2 DFU)
2" V (3 DFU)
1-1/2" V (1 DFU)
2" V (5.5 DFU)
2" V (12.5 DFU)
2" V (7 DFU)
3" V (35.5 DFU)
3" V (37.5 DFU)
L-1
WC-1
WC-1
DF-1
L-1
L-1
WC-1
S-1
SB-1
US-1
EWS-1
GWH-101
DET-101
RCP-101
WET-101
WH-2
2" CW
I.E. 6.5' B.F.F.
SEE CIVIL FOR
CONTINUATION
WH-3
WH-1
WH-2
WH-2
WH-2
3/4" CW (4 WSFU)
1/2" CW (2 WSFU)
1-1/4" CW
(7.0 WSFU)
MS-1
1-1/2" CW
(7.25 WSFU)
1-1/4" CW
(7.0 WSFU)
3/4" CW
(7 WSFU)
1" CW (12.5
WSFU)
2" CW
(22.25 WSFU)
3/4" HW
(4.5 WSFU)
1-1/2" CW
(13 WSFU) 3/4" HW
(2.5 WSFU)
1-1/4" CW (6.5 WSFU)
3/4" CW
(4 WSFU)
3/4" CW
(4 WSFU)
3/4" CW (3 WSFU)
3/4" CW
(4 WSFU)
3/4" CW
(5 WSFU)
3/4" CW (6 WSFU)
3/4" CW
(4 WSFU)
3/4" CW
(8 WSFU)
1/2" CW (1.5
WSFU)
1/2" HW
(1.5 WSFU)
1/2" HW -R
1/2" CW (0.5 WSFU)
1/2" CW
(0.5 WSFU)
1/2" HW
(0.5 WSFU)
1-1/4" CW
(6.5 WSFU)
1/2" HW -R
3/4" HW
(3 WSFU)
EM
1/2" CW
1/2" HW
1/2" TW
3/4" CW (6 WSFU)
1/2" CW (0.25 WSFU)
1-1/4" CW
(6.5 WSFU)
1-1/4" CW
(7 WSFU)
1/2" CW
(0.5 WSFU)
1/2" HW
(0.5 WSFU)
1/2" HW
(2 WSFU)
1/2" HW -R
1/2" CW
(2 WSFU)
1/2" HW
(2 WSFU)
1/2" CW
(0.5 WSFU)
1/2" HW
(0.5 WSFU)
2" CW
(29.25 WSFU)
3/4" HW
(5 WSFU)
1/2" CW
(1.5 WSFU)
1/2" HW
(1.5 WSFU)
3/4" HW
(6.5 WSFU)
1" HW
(9.5 WSFU)
1" CW
(9.5 WSFU)
2" CW
(43.25 WSFU)
2" CW
(20.25 WSFU)
2" CW
(30.75 WSFU)
1/2" HW -R
B-1
GWH-101
GM-101
GUH-1
GUH-2
NATURAL GAS BY
THE UTILITY.
SEE CIVIL FOR
CONTINUATION
TO 70 KW
GENERATOR
1-1/4" G (975 CFH)
1-1/2" G (800 CFH)
3/4" G (400 CFH)
1/2" G (200 CFH)
1-1/2" G (400 CFH)
1/2" G (285 CFH)
1/2" G (200 CFH)
4
P5.2
4
P5.2
4
P5.2
4
P5.2
2
P5.1
4
P5.2
drawn by:
checked by:
date:
project #:
sheet title:
sheet
number:
www.dsgw.com
03/10/2026
25323
AWM
CDH
Brule Public
Works
Garage
P6.1
DIAGRAMS
NOT TO SCALE 2 WASTE AND VENT ISOMETRIC
NOT TO SCALE 3 DOMESTIC WATER ISOMETRIC
NOT TO SCALE 1 NATURAL GAS ISOMETRIC
revision / issue no. date
CALENN
HEPPNER
E-48270
03/09/2026
T
M
ABBREVIATIONS
A AMPERES
AFCI ARC FAULT CIRCUIT INTERRUPTER
AFF ABOVE FINISHED FLOOR
AIC AMPERE INTERRUPTING CAPACITY
AL ALUMINUM
ATS AUTOMATIC TRANSFER SWITCH
AWG AMERICAN WIRE GAUGE
A/V AUDIO VISUAL
BKR BREAKER
C CONDUIT
CKT CIRCUIT
CO CONDUIT ONLY
CU COPPER
CLG CEILING
CT CURRENT TRANSFORMER
DAS DISTRIBUTED ANTENNA SYSTEM
DIA. DIAMETER
(E) EXISTING
EGC EQUIPMENT GROUNDING CONDUCTOR
ERRCS EMERGENCY RESPONDER RADIO COVERAGE
F FUSE
FACP FIRE ALARM CONTROL PANEL
FC FOOT CANDLE
FLA FULL LOAD AMPERES
FSD FIRE SMOKE DAMPER
FTL FEED -THRU LUGS
GEC GROUNDING ELECTRODE CONDUCTOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GFPE GROUND FAULT PROTECTION OF EQUIPMENT
GND GROUND
HP HORSEPOWER
IDF INTERMEDIATE DISTRIBUTION FRAME
IG ISOLATED GROUND
KCMIL THOUSAND CIRCULAR MIL
KVA KILOVOLT -AMP
KW KILOWATT
LTG LIGHTING
MCA MINIMUM CIRCUIT AMPERES
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDF MAIN DISTRIBUTION FRAME
MDP MAIN DISTRIBUTION PANEL
MDU MEDIA DISTRIBUTION UNIT
MIN MINIMUM
MLO MAIN LUG ONLY
MOCP MAXIMUM OVERCURRENT PROTECTION
MTS MANUAL TRANSFER SWITCH
(N) NEW
NAC NOTIFICATION APPLIANCE CIRCUIT
OC ON CENTER
P POLE
PH PHASE
PNL PANEL
PWR POWER
(R) RELOCATE
ROW RIGHT -OF -WAY
S SWITCH
SDP SUB -DISTRIBUTION PANEL
SIM SIMILAR
SPD SURGE PROTECTIVE DEVICE
TR TAMPER RESISTANT
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
UPS UNINTERRUPTIBLE POWER SUPPLY
V VOLTS
VA VOLT -AMPERES
VFD VARIABLE FREQUENCY DRIVE
W WIRE
WP WEATHERPROOF
(X) DEMOLISH
XFMR TRANSFORMER
LIGHTING CONTROLS SYMBOLS LEGEND
STANDARD SWITCH
STANDARD SWITCH W/ SWITCHING SUBSCRIPT
3-WAY SWITCH
4-WAY SWITCH
$
$
a
$3
$4
LOW VOLTAGE SWITCH $L
OCCUPANCY SENSOR SWITCH $O
KEYED SWITCH $K
DIMMER SWITCH $D
TIMER SWITCH $T
OCCUPANCY SENSOR CEILING MOUNT
PHOTOCELL CEILING MOUNT
OCCUPANCY SENSOR WALL MOUNT
PHOTOCELL WALL MOUNT
LOW VOLTAGE SWITCH PER SCHEDULE $L#
OS
PC
OS
PC
NOTE: ANY COMBINATION OF LETTERS MAY APPLY TO A SWI TCH FOR MULTIPLE
FUNCTIONS
ONE-LINE SYMBOLS LEGEND
FEEDER CALLOUT
CONDUIT CAP
CONDUIT CONTINUATION
AUTOMATIC TRANSFER SWITCH
CIRCUIT BREAKER
TRANSFORMER
FUSED SWITCH
ELECTRICITY METER
CURRENT TRANSFORMERS
SURGE PROTECTIVE DEVICE SPD
GROUND CONNECTION
GENERATOR
XXXX
BUS DUCT PLUG -IN CIRCUIT BREAKER
GENERAL SYMBOLS
DETAIL/PLAN CALLOUT
REVISION CLOUD
REVISION TAG
KEYNOTE 1
X
XXX
X
NORTH ARROW
N
MATCHLINE
CONTINUATION SYMBOL
LIGHTING SYMBOLS LEGEND
RECESSED DOWNLIGHT - ROUND/SQUARE
LINEAR SURFACE LUMINAIRE
LINEAR RECESSED LUMINAIRE
LINEAR STRIP LUMINAIRE
LINEAR PENDANT LUMINAIRE
SURFACE DOWNLIGHT - ROUND/SQUARE
RECESSED 2x2 LUMINAIRE
RECESSED 2x4 LUMINAIRE
SURFACE OR PENDANT 2x2 LUMINAIRE
SURFACE OR PENDANT 2x4 LUMINAIRE
PENDANT OR FLUSH MOUNT LUMINAIRE
LINEAR WALL LUMINAIRE
WALL MOUNTED LUMINAIRE
NOTE: SHADED LUMINAIRE INDICATES EMERGENCY POWER
POLE MOUNTED AREA LUMINAIRE
EXIT SIGN, SHADING INDICATES FACES,
ARROWS PER PLAN
BOLLARD OR POST TOP LUMINAIRE
GROUND MOUNT FLOOD
CONTINUOUS TAPE OR UNDERCABINET LUMINAIRE
RECESSED STEP LIGHT
RECESSED HEAT LAMP
TYPICAL LUMINAIRE LABELING
R1
A:12.
a
LUMINAIRE TYPE
PANEL & CIRCUIT
SWITCH INDICATOR
EMERGENCY BUGEYE
EQUIPMENT SYMBOLS LEGEND
EQUIPMENT CABINET AS NOTED
BRANCH PANEL RECESSED
BRANCH PANEL SURFACE
EQUIPMENT ENCLOSURE, SEE PLAN NOTES AND
NAMING CONVENTIONS FOR DESCRIPTION
UTILITY METER
TRANSFORMER
ELECTRIC WALL HEATER
TYPICAL DEVICE MOUNTING HEIGHTS
RECEPTACLES +18 ” AFF
RECEPTACLES, ABOVE COUNTER +6 ” ABOVE COUNTER, +46" AFF
MAX, COORDINATE WITH
CASEWORK
PHONE/DATA/CATV OUTLET +18 ” AFF
SWITCHES +46 ” AFF
THERMOSTATS +46 ” AFF
CARD READERS +46 ” AFF
PANELBOARDS +72 ” TO TOP OR PER NEC 404.8
CONTROL PANELS +72 ” TO TOP
NOTES:
1. MEASUREMENTS ARE TYPICAL UNO ON PLANS
2. MEASUREMENTS ARE TO CENTER OF BOX UNO
3. COMPLY WITH ALL ADA ACCESSIBILITY GUIDELINES
TECHNOLOGY SYMBOLS LEGEND
TELECOMMUNICATIONS OUTLET, PROVIDE BACKBOX
AND CONDUIT/PULL STRING TO ACCESSIBLE SPACE.
(XX) = QUANTITY OF CABLES
(XX)
CABLE TV OUTLET, PROVIDE BACKBOX AND
CONDUIT/PULL STRING TO ACCESSIBLE SPACE.
WIRELESS ACCESS POINT, PROVIDE BACKBOX AND
CONDUIT/PULL STRING TO ACCESSIBLE SPACE.
W
AUDIO/VISUAL OUTLET, PROVIDE BACKBOX AND
CONDUIT/PULL STRING TO ACCESSIBLE SPACE.
AV
SECURITY DEVICES SYMBOLS LEGEND
CARD READER, PROVIDE BACK BOX AND CONDUIT
ROUGH -IN
DOOR CONTACT, PROVIDE CONDUIT ROUGH -IN
CR
DC
ELECTRIC STRIKE, PROVIDE CONDUIT ROUGH -IN ES
MOTION DETECTOR, PROVIDE BACK BOX AND
CONDUIT TO ACCESSIBLE SPACE MD
TELEPHONE ENTRY SYSTEM, PROVIDE BACK BOX
AND CONDUIT ROUGH -IN TE
PUSH BUTTON / DOOR OPERATOR
FIRE ALARM DEVICES SYMBOLS LEGEND
SMOKE DETECTOR
120V COMBINATION CARBON
MONOXIDE/SMOKE DETECTOR
120V MAGNETIC DOOR HOLD M
SD
SD c
TECHNOLOGY DEVICE ROUGH-IN SCHEDULE
DEVICE BACK BOX MUD RING CONDUIT NOTES
TELECOM 4"SQ, 2 -1/8"D 1-GANG 1" 1
OUTLET
TV OUTLET 4"SQ, 2 -1/8"D 1-GANG 1" 1
A/V OUTLET 4-11/16"SQ 2-GANG 1-1/4" 1,2
SECURITY 4"SQ, 2 -1/8"D 1-GANG 3/4" 1,2
DEVICE
*ALL ROUGH -INS ARE TYPICAL UNO ON PLANS
NOTES:
1. USE PLASTIC BUSHING AT CONDUIT TERMINATION IN
ACCESSIBLE SPACE.
2. REFER TO ROUGH -IN DETAILS FOR MORE INFORMATION.
1. COMPLETED INSTALLATION SHALL COMPLY WITH NEC AND ALL LOCAL LAWS,
ORDINANCES, AND REGULATIONS.
2. PLANS ARE DIAGRAMMATIC IN NATURE TO COMMUNICATE SCO PE OF WORK AN D
GENERAL INTENT. CONTRACTOR SHALL PROVIDE ALL FITTIN GS, BOXES, AN D
APPURTENANCES NECESSARY FOR A COMPLETE AND OPERABLE ELECTRICAL
SYSTEM.
3. DEVICE LOCATIONS ON PLANS MAY NOT BE EXACT. REFER T O ARCHITECTUR AL
PLANS FOR MORE DETAILED INFORMATION REGARDING DIMEN SIONS AND
LAYOUTS. COORDINATE ALL DEVICE AND EQUIPMENT LOCATI ONS WITH
ARCHITECTURAL AND OTHER TRADES.
4. EQUIPMENT FOR OTHER DISCIPLINES MAY BE SHOWN FOR RE FERENCE ONLY.
REFER TO OTHER DISCIPLINES ’ DRAWINGS FOR MORE DETAIL REGARDING
EQUIPMENT SPECIFICATIONS AND INFORMATION.
5. PLANS SHALL GOVERN IN MATTERS OF QUANTITY, SPECIFIC ATIONS SHALL
GOVERN IN MATTERS OF QUALITY. IN CASE OF DISCREPANC Y BETWEEN
DRAWINGS AND SPECIFICATIONS, THE SPECIFICATIONS SHA LL GOVERN. PL ANS
ARE TO BE TIED TO SPECIFICATIONS FOR A COMPLETE DES IGN PACKAGE.
6. ANYTHING MENTIONED IN THE SPECIFICATIONS AND NOT SH OWN ON THE
DRAWINGS, OR SHOWN ON THE DRAWINGS AND NOT MENTIONED IN THE
SPECIFICATIONS, SHALL BE OF LIKE EFFECT AS IF SHOWN OR MENTIONED IN
BOTH.
7. WIRE SIZE AND QUANTITIES ARE NOT GENERALLY INDICATE D ON PLANS. F OR A
TYPICAL 20A/1P CIRCUIT BREAKER, PROVIDE (3) #12 CU CONDUCTORS (P HASE,
NEUTRAL, GROUND). FOR A TYPICAL 20A/2P CIRCUIT BREAKER, PROVIDE (3) #12 CU
CONDUCTORS (PHASE, PHASE, GROUND). FOR A TYPICAL 20 A/3P CIRCUIT
BREAKER, PROVIDE (4) #12 CU CONDUCTORS (THREE PHASES PLUS GROUND ).
8. TO COMPENSATE FOR VOLTAGE DROP, ON 20A, 120V CIRCUI TS: OVER 100 FEET,
PROVIDE #10 AWG, OVER 150 FEET, PROVIDE #8 AWG. ON 20A, 277V CIRCUITS:
OVER 250 FEET, PROVIDE #10 AWG.
9. CIRCUIT NUMBERS ARE GENERALLY INDICATED AS XX:##. W HERE (XX) IND ICATES
PANEL NAME AND (##.) INDICATES THE CIRCUIT NUMBER. IN SOME CASES THE
PANEL MAY BE COMMON TO A LARGE AREA, AND THE CIRCUI T NUMBER ONLY MAY
BE CALLED OUT ON THE PLANS.
10. MAINTAIN AT LEAST 12 ” SEPARATION BETWEEN POWER AND COMMUNICATIONS
WIRING ROUTED PARALLEL. SMALLER SEPARATION MAY BE ALLOWED WHEN
CROSSING.
11. PROVIDE FIRE STOPPING FOR ALL PENETRATIONS OF FIRE RATED ASSEMBL IES.
FIRE PROOFING MUST BE EQUIVALENT OR HIGHER TO THAT OF THE PENETR ATED
ASSEMBLY. REFER TO ARCHITECTURAL PLANS.
12. REFER TO ARCHITECTURAL PLANS FOR FIRE RATED ASSEMBL IES. MAINTAIN 24 ”
SEPARATION BETWEEN DEVICES IN FIRE -RATED WALLS. PROVIDE FIRE -RAT ED
BOXES OR “PUTTY PADS ” AS REQUIRED TO MAINTAIN FIRE RATING.
13. REFER TO ARCHITECTURAL PLANS FOR ACOUSTIC ASSEMBLIE S. PROVIDE
ACOUSTIC BOXES OR “PUTTY PADS ” AS REQUIRED TO MAINTAIN ACOUSTIC
RATING.
14. ELECTRICAL EQUIPMENT IS DESIGNED BASED ON A SPECIFI C MANUFACTURE R.
VERIFY FINAL CLEARANCES AND SPACE REQUIREMENTS WITH EQUIPMENT
SUBMITTALS. THE CONTRACTOR IS RESPONSIBLE FOR ANY R EDESIGN OR
RELOCATION OF EQUIPMENT IF APPROVED EQUIPMENT DOES NOT MATCH BAS IS
OF DESIGN.
15. PROVIDE 4" HIGH CONCRETE "HOUSEKEEPING PADS" FOR FR EE STANDING A ND
FLOOR MOUNTED ELECTRICAL EQUIPMENT.
16. ALL CONDUIT ROUTING SHALL FOLLOW BUILDING LINES WHERE POSSIBLE.
COORDINATE ROUTING WITH ARCHITECTURAL ELEMENTS. ALL ROUTING OF
EXPOSED CONDUITS SHALL BE APPROVED BY THE ARCHITECT.
17. LIGHTING CONTROL: PLANS ARE DIAGRAMMATIC TO SHOW GE NERAL INTENT. ALL
LIGHTING CONTROL DEVICES MAY NOT BE SHOWN ON THE PL ANS. REFER TO
LIGHTING CONTROL NARRATIVE FOR DETAILED INFORMATION REGARDING
FUNCTIONALITY.
18. COORDINATE UNDERGROUND CONDUIT ROUTING WITH CIVIL AND STRUCTURAL
PLANS.
19. CONSULT STRUCTURAL ENGINEER OF RECORD FOR ALL STRUCTURAL
PENETRATIONS.
* NOTE *
ALL OF GENERAL NOTES ON THIS SHEET ARE TO BE APPLIE D TO ALL OTHER DRAWINGS
IN THIS SET. THE SYMBOLS AND ABBREVIATIONS SHOWN ON THIS SHEET MAY OR MAY
NOT BE USED IN THIS SET OF DRAWINGS.
GENERAL PROJECT NOTES POWER DEVICE SYMBOLS LEGEND
SIMPLEX RECEPTACLE
DUPLEX RECEPTACLE
QUADPLEX RECEPTACLE
REMOTE GFCI DEVICE
SPECIAL PURPOSE RECEPTACLE, VERIFY NEMA
CONFIGURATION
* INDICATES ABOVE COUNTER OR NON -STANDARD HEIGHT
FOR ALL WALL DEVICES. REFER TO ARCHITECTURAL /
INTERIOR ELEVATIONS FOR EXACT LOCATION, UNO.
JUNCTION BOX WITH POWER OR DATA WHIP, SEE PLANS
IN -CEILING DEVICES
DUPLEX RECEPTACLE ON CEILING
DOUBLE DUPLEX RECEPTACLE ON CEILING
SPECIAL PURPOSE RECEPTACLE ON CEILING, VERIFY
NEMA CONFIGURATION
IN -FLOOR DEVICES
DUPLEX FLOOR RECEPTACLE
DUPLEX FLOOR RECEPTACLE
COMBINATION FLOORBOX, REFER TO SCHEDULE FOR
POWER, DATA, AND AV SCOPE
NUMBER INDICATES SCHEDULED ENCLOSURE TYPE.
REFER TO SCHEDULE FOR ADDITIONAL INFO.
DEVICE TYPE / WIRING KEY
17.
G
FB = FLOORBOX
PT = POKE -THROUGH
FF = FURNITURE FEED
LETTER INDICATOR KEY
CIRCUITING:
E = EMERGENCY
U = UPS
S = STANDBY
C = CRITICAL
D = DED. CKT
DEVICE TYPE:
B = INTEGRAL USB
G = GFCI
W = WEATHER PROOF GFCI
T = ISOLATED GND
CIRCUIT NUMBER
DEVICE TYPE INDICATOR
ABOVE COUNTER / NON -STANDARD HEIGHT
SHADING INDICATES SWITCHING OR CONTROL, SEE PLANS
E CIRCUITING INDICATOR. MAY BE REPLACED WITH CIRCUIT
NUMBER CALLOUT IN FINAL CONSTRUCTION DOCUMENTS.
FB1
DISCONNECT: F = FUSED, B = BREAKER
DISCONNECT SWITCH
MOTOR CONNECTION
EQUIPMENT CONNECTION, SEE SCHEDULES
JUNCTION BOX
$ POWER DEVICE SWITCH, SEE PLANS FOR ADDITIONAL
INFORMATION.
F
J
LINE VOLTAGE THERMOSTAT T
COMMON DEVICES
G
J
ELECTRICAL TAGS
MECHANICAL EQUIPMENT TAG.
EQUIP. SPECIFIED BY DIV 21, 22, OR 23.
BUILDING EQUIPMENT TAG.
EQUIP. NOT SPECIFIED BY DIV 21, 22, OR 23. XX -XX
XX-XX
EQUIPMENT NAMING LEGEND
LINE -LINE VOLTAGE *
4 = 480V
2 = 208V
POWER BRANCH
N = NORMAL
S = STANDBY, LEGALLY REQ. SB
E = LIFE SAFETY
BUILDING SYSTEM
R = RECEPTACLE LOADS
L = LIGHTING SYSTEMS
M = MECHANICAL SYSTEMS
W = WATER SYSTEMS
T = TELECOM SYSTEMS
LEVEL : P1, 1, 2...
SECTOR INDICATOR
A = SECTOR A
B = SECTOR B
...
# IN SERIES **
LINE -LINE VOLTAGE *
EQUIPMENT
MDP = MAIN DIST. PANEL
SDP = SUB DIST. PANEL
X = XFMR
SE = SERVICE ENTRANCE
...
SERVICE ***
R = RESIDENTIAL SERVICE
H = HOUSE SERVICE
EV = EV SERVICE
POWER BRANCH **
EXAMPLE: 4MDP -R
MAIN DIST. EQUIPMENT MAY OMIT BUILDING SYSTEM, LEVE L,
SECTOR, ETC. FOR NAMING SIMPLIFICATION.
NOTES :
* USED WHEN MULTIPLE L -L VOLTAGES ARE PRESENT.
** OMITTED AS NEEDED FOR SIMPLIFICATION.
*** USED ONLY ON MULTI -SERVICE PROJECTS
EXAMPLE: 4NM -1A -2
TYPICAL PANELBOARD CONVENTION
drawn by:
checked by:
date:
project #:
sheet title:
sheet
number:
www.dsgw.com
03/10/2026
25323
JRB
LM
Brule Public
Works
Garage
E0.1
COVER SHEET
ELECTRICAL SHEET LIST
E0.1 COVER SHEET - ELECTRICAL
E0.2 SCHEDULES - ELECTRICAL
E1.0 SITE PLAN - ELECTRICAL
E2.1 FLOOR PLAN - ELECTRICAL
E3.1 LIGHTING RCP - ELECTRICAL
E5.1 DETAILS - ELECTRICAL
E6.1 ONE-LINE DIAGRAM - ELECTRICAL
revision / issue no. date
03/09/2026
GENERAL LUMINAIRE SCHEDULE NOTES:
A. REFER TO SPECIFICATIONS SECTIONS 26 5100 AND 26 5600 FOR ADDITIONAL REQUIREMENTS.
B. FINISH FOR ALL LUMINAIRES LISTED ABOVE SHALL BE PER ARCHITECT AND INTERIOR DESIGNER.
C. LUMEN OUTPUT LISTED ABOVE IS DELIVERED LUMENS.
D. MOUNTING HEIGHTS:
a. CONFIRM MOUNTING HEIGHTS FOR WALL MOUNTED AND SUSPE NDED LUMINAIRES WITH ARCHITECT AND INTERIOR DESIGNER.
b. WALL MOUNTED LUMINAIRES: UNLESS NOTED OTHERWISE, SPECIFIED MOUNTING HEIGHTS ARE TO CENTER OF LUMINAIRE FROM FINISHED FLOOR.
c. SUSPENDED LUMINAIRES: UNLESS NOTED OTHERWISE, SPECIFIED MOUNTING HEIGHTS ARE TO BOTTOM OF LUMINAIRE FR OM FINISHED FLOOR.
LUMINAIRE NOTES:
1. PROVIDE WITH CONTROLS TO REDUCE LIGHT LEVELS WHEN NO MOTION IS DETECTED.
2. INCLUDE 20W EMERGENCY BATTERY PACK.
GENERAL MECHANICAL SCHEDULE NOTES
A. LOADS FOR EQUIPMENT LISTED ABOVE ARE BASIS OF DESIG N LOADS ONLY. CONTRACTOR IS RESPONSIBLE FOR COORDIN ATING EXACT REQUIREMENT S WITH
APPROVED SUBMITTALS FOR DIVISION 22 AND 23.
B. PROVIDE DISCONNECTING MEANS IF REQUIRED PER NEC FOR ALL MECHANICAL EQUIPMENT (MAY NOT BE SHOWN ON PLANS). PROVIDE MOTOR START ERS
INCORPORATING MOTOR OVERLOAD AND SHORT CIRCUIT PROT ECTION PER NEC ARTICLE 430 AS REQUIRED. COORDINATE WITH MECHANICAL PLANS A ND
EQUIPMENT.
C. FEEDER REFERS TO FEEDER SCHEDULE ON SHEET E6.1.
MECHANICAL SCHEDULE NOTES
1. INDOOR UNIT (FCU) IS POWERED BY THE OUTDOOR UNIT (C U).
2. MULTIPLE OCCURANCES OF DEVICE.
3. PROVIDE 120V RECEPTACLE WITHIN 6 FT OF FAN COIL FOR CONDENSATE PUMP.
GENERAL BUILDING EQUIPMENT SCHEDULE NOTES
A. LOADS FOR EQUIPMENT LISTED ABOVE ARE BASIS OF DESIG N LOADS ONLY. CONTRACTOR IS RESPONSIBLE FOR COORDIN ATING EXACT REQUIREMENT S WITH APPROVED SUBMITTALS FROM FOOD
SERVICE CONTRACTOR.
B. FEEDER REFERS TO FEEDER SCHEDULE ON SHEET E6.1.
BUILDING EQUIPMENT SCHEDULE NOTES
1. PROVIDE NEMA 14 -50R RECEPTACLE.
2. MULTIPLE OCCURANCES OF DEVICE.
GENERAL LIGHTING CONTROL MATRIX NOTES
A. BOD SPACE BY SPACE PROVISIONS FOR THE LIGHTING C ONTROL SYSTEM ARE DEFINED IN THE MATRIX BELOW.
B. PROVIDE CONTROL DEVICE SETTINGS PER SPACE TYPE A S REQUIRED PER THE WISCONSIN STATE ENERGY CODE.
LIGHTING CONTROL MATRIX NOTES
1. PROVIDE 2 HOUR OVERIDE FOR VACANCY LIGHTING IN G ARAGE.
GENERAL FLOORBOX SCHEDULE NOTES
A. COVER TYPE, COLOR/FINISH PER ARCHITECT / INTERIOR D ESIGNER.
B. PROVIDE SUBMITTAL WITH SELECTED OPTIONS FOR ARCHITE CT AND ENGINEER REVIEW PRIOR TO AQUISITION.
C. RECEPTACLE TO BE NEMA 5 -20R.
drawn by:
checked by:
date:
project #:
sheet title:
sheet
number:
www.dsgw.com
03/10/2026
25323
JRB
LM
Brule Public
Works
Garage
E0.2
SCHEDULES
LUMINAIRE SCHEDULE
TAG LUMINAIRE DESCRIPTION MOUNTING MOUNTING
HEIGHT LAMP COLOR
TEMP
LUMEN
OUTPUT POWER SUPPLY MANUFACTURER & MODEL VOLTAGE INPUT
WATTS NOTES
L1 4' STRIP LIGHT, ROUND DIFFUSE LENS SURFACE OR
CHAIN-HUNG CEILING LED 3500K 4,000 INTEGRAL ELECTRONIC
DRIVER LITHONIA CLX SERIES OR EQUIVALENT 120 V 30 W
L1E 4' STRIP LIGHT, ROUND DIFFUSE LENS W/BATTERY
PACK
SURFACE OR
CHAIN-HUNG CEILING LED 3500K 4,000 INTEGRAL ELECTRONIC
DRIVER
LITHONIA CLX SERIES W/E10W
EMERGENCY BATTERY PACK, OR
EQUIVALENT
120 V 30 W
R1 2' x 2' TROFFER RECESSED N/A LED 3500K 2,100 INTEGRAL ELECTRONIC
DRIVER, 0-10V DIMMING LITHONIA CPX SERIES OR EQUIVALENT 120 V 16 W
R1E 2' x 2' TROFFER W/BATTERY PACK RECESSED N/A LED 3500K 2, 100 INTEGRAL ELECTRONIC
DRIVER, 0-10V DIMMING
LITHONIA CPX SERIES W/E10W
EMERGENCY BATTERY PACK, OR
EQUIVALENT
120 V 16 W
R2 1' x 4' TROFFER RECESSED N/A LED 3500K 2,000 INTEGRAL ELECTRONIC
DRIVER, 0-10V DIMMING LITHONIA CPX SERIES OR EQUIVALENT 120 V 17 W
S1 COMPACT HIGH BAY SURFACE +18'-0" AFF LED 3500K 4,000 INTEGRAL ELECTRONIC
DRIVER, 0-10V DIMMING
LITHONIA CPHB SERIES OR
EQUIVALENT 120 V 138 W
S1E COMPACT HIGH BAY W/BATTERY PACK SURFACE +18'-0" AFF LE D 3500K 4,000 INTEGRAL ELECTRONIC
DRIVER, 0-10V DIMMING
LITHONIA CPHB SERIES W/20W
EMERGENCY BATTERY PACK, OR
EQUIVALENT
120 V 138 W
SW1 WALL PACK AREA LIGHT, FORWARD THROW
DISTRIBUTION WALL +18'-0" AFF LED 4000K 8,700 INTEGRAL ELECTRONIC
DRIVER
LITHONIA WDGE3 SERIES OR
EQUIVALENT 120 V 60 W 1
SW2 WALL PACK AREA LIGHT, FORWARD THROW
DISTRIBUTION WALL +8'-6" AFF LED 4000K 4,300 INTEGRAL ELECTRONIC
DRIVER
LITHONIA WDGE2 SERIES OR
EQUIVALENT 120 V 47 W 1,2
X1 THERMOPLASTIC EXIT SIGN WALL, PENDANT,
CEILING LED RED -- INTEGRAL ELECTRONIC
DRIVER LITHONIA LE OR EQUIVALENT 120 V 5 W
FLOORBOX SCHEDULE
BOX TYPE BOX DESCRIPTION DEVICE SPECS MANUFACTURER ALTE RNATES BOX NOTES
FB1 CONFERENCE ROOM FLOORBOX
WITH DATA, AND POWER.
(1) DUPLEX DEVICE, (2)
DATA PORT WIREMOLD FSR
FB2 CONFERENCE ROOM FLOORBOX
WITH DATA, AV, AND POWER.
(1) DUPLEX DEVICE, (2)
DATA PORTS, (1) HDMI WIREMOLD FSR
MECHANICAL AND PLUMBING EQUIPMENT CONNECTION SCHEDULE
TAG EQ DESCRIPTION VOLTAGE PHASE LOAD (VA) FLA MCA FEEDER M OCP PANEL CIRCUIT NOTES
AC-101 AIR COMPRESSOR 240 V 1 5760 VA 24.0 A 30.0 A 402 40 A 2MDP 51,53
B-1 BOILER 120 V 1 1440 VA 12.0 A 15.0 A 202 20 A 2MDP 29
BP-1 BOOSTER PUMP 120 V 1 156 VA 1.3 A 1.6 A 202 15 A 2MDP 63
CEF-01 CEILING EXHAUST FAN 120 V 1 120 VA 1.0 A 1.3 A 202 1 5 A 2N-A 13
CEF-02 CEILING EXHAUST FAN 120 V 1 120 VA 1.0 A 1.3 A 202 1 5 A 2N-A 13
CU-1 CONDENSING UNIT 240 V 1 3264 VA 13.6 A 17.0 A 302 30 A 2N-A 6,8
CU-2 CONDENSING UNIT 240 V 1 1728 VA 7.2 A 9.0 A 202 15 A 2N -A 10,12
EDH-1 ELECTRIC DUCT HEATER 120 V 1 500 VA 4.2 A 5.2 A 202 1 5 A 2MDP 49
EDH-2 ELECTRIC DUCT HEATER 240 V 1 4001 VA 16.7 A 20.8 A 3 02 30 A 2N-A 29,31
EF-01 EXHAUST FAN 120 V 1 1176 VA 9.8 A 12.3 A 202 20 A 2MDP 10
EF-02 EXHAUST FAN 120 V 1 336 VA 2.8 A 3.5 A 202 15 A 2MDP 12
ERV-01 ENERGY RECOVERY VENTILATOR 120 V 1 204 VA 1.7 A 2. 1 A 202 15 A 2MDP 27
ERV-02 ENERGY RECOVERY VENTILATOR 240 V 1 552 VA 2.3 A 2. 9 A 202 15 A 2N-A 2,4
EUH-1 ELECTRIC UNIT HEATER 240 V 1 1001 VA 4.2 A 5.2 A 202 15 A 2MDP 34,36
EUH-2 ELECTRIC UNIT HEATER 240 V 1 499 VA 2.1 A 2.6 A 202 1 5 A 2N-A 25,27
EUH-3 ELECTRIC UNIT HEATER 240 V 1 1001 VA 4.2 A 5.2 A 202 15 A 2N-A 14,16
EUH-4 ELECTRIC UNIT HEATER 240 V 1 1001 VA 4.2 A 5.2 A 202 15 A 2MDP 38,40
FC-1 FAN COIL 240 V 1 0 VA 0.0 A 0.0 A 202 15 A 1,3
FC-2 FAN COIL 240 V 1 0 VA 0.0 A 0.0 A 202 15 A 1,3
GUH-1 GAS UNIT HEATER 120 V 1 552 VA 4.6 A 5.8 A 202 15 A 2M DP 23
GUH-2 GAS UNIT HEATER 120 V 1 552 VA 4.6 A 5.8 A 202 15 A 2M DP 21
GWH-101 GAS WATER HEATER 120 V 1 600 VA 5.0 A 6.3 A 202 15 A 2MDP 30
LV-2 MOTORIZED DAMPER 120 V 1 240 VA 2.0 A 2.5 A 202 15 A 2M DP 61
P-1 WATER PUMP 120 V 1 156 VA 1.3 A 1.6 A 202 15 A 2MDP 35
P-2 WATER PUMP 120 V 1 156 VA 1.3 A 1.6 A 202 15 A 2MDP 37
P-3 WATER PUMP 120 V 1 156 VA 1.3 A 1.6 A 202 15 A 2MDP 39
P-4 WATER PUMP 120 V 1 156 VA 1.3 A 1.6 A 202 15 A 2MDP 41
RCP-101 RECIRC PUMP 120 V 1 120 VA 1.0 A 1.3 A 202 15 A 2MDP 26
VEF-1 VEHICLE EXHAUST FAN 120 V 1 1536 VA 12.8 A 16.0 A 20 2 20 A 2MDP 19 2
WP-1 WELL PUMP 240 V 1 4800 VA 20.0 A 25.0 A 302 30 A 2MDP 18 ,20
BUILDING EQUIPMENT CONNECTION SCHEDULE
TAG EQ DESCRIPTION LOCATION LOAD TYPE VOLTAGE PHASE FLA MC A FEEDER MOCP PANEL CIRCUIT NOTES
BE-1 OVERHEAD GARAGE DOORS GARAGE M 120 V 1 10.0 A 12.5 A 2 02 20 A 2MDP 22 2
BE-2 GARAGE WELDER OUTLET GARAGE G 240 V 1 39.9 A 49.9 A 50 2 50 A 2MDP 5,7 1,2
BE-3 GEN BLOCK HEATER, BATT CHARGER GENERATOR G 240 V 1 8 .3 A 10.4 A 302 30 A 2MDP 57,59
GENERAL NARRATIVE
1. THE PURPOSE OF THIS NARRATIVE IS TO DESCRIBE THE IN TENDED FUNCTIONALITY OF THE LIGHTING CONTROL SYSTEM . COMPLETED INSTALLATIO N SHALL COMPLY WITH STATE AND LOCAL ENERGY CODES AND OWNER SPECIFICATIONS.
2. COMMISSIONING AGENT SHALL ENSURE FULLY FUNCTIONAL S YSTEM TO COMPLY WITH THE WISCONSIN STATE ENERGY COD E.
3. GENERAL NOTES
A. LIGHTING CONTROL DESIGN IS INTENDED TO FUNCTION WIT H A VARIETY OF MANUFACTURERS IN CONFORMANCE WITH TH IS NARRATIVE.
B. THE LIGHTING CONTROL SYSTEM IS A DEFERRED SUBMITTAL . CONTRACTOR IS REQUIRED TO SUBMIT LIGHTING CONTROL SHOP DRAWINGS DEMONSTR ATING FULL FUNCTIONALITY TO COMPLY WITH THIS NARRAT IVE. SHOP DRAWINGS SHALL
INDICATE DEVICE LOCATIONS AND QUANTITIES AND WIRING DIAGRAMS FOR INSTALLATION.
C. ALL LIGHTING SWITCHING AND CONTROL DEVICES ARE TO B E CONCEALED IN ACCESSIBLE SPACE OR BACK -OF -HOUSE ROOMS.
D. FINISHES AND COLORS OF ALL VISIBLE LIGHTING CONTROL DEVICES ARE TO BE SPECIFIED BY THE ARCHITECT.
E. UNLESS LUMINAIRE -LEVEL LIGHTING CONTROLS (LLLC) ARE USED, PROVIDE A SEPARATE RELAY FOR EACH CONTROL ZONE INDICATED ON T HE PLANS.
F. PROVIDE DIMMING FUNCTIONALITY FOR DIMMABLE ZONES FU LLY COMPATIBLE WITH THE TYPE OF DIMMING LOAD TO BE CONTROLLED.
4. AUTOMATIC SWITCHING DEVICES - RELAYS/POWER PACKS
A. PROVIDE AUTOMATIC SWITCHING DEVICES TO CONFORM WITH THE INTENT OF THIS NARRATIVE. RELAYS AND POWER PAC KS MAY NOT BE SHOWN ON PLANS.
B. SWITCHING DEVICES MAY BE REMOTE OR CONTAINED IN A R ELAY PANEL OR ENCLOSURE.
5. EMERGENCY LIGHTING
A. FOR EMERGENCY LIGHTING FIXTURES WITH A SELF -CONTAINED BACKUP BATTERY POWER SOURCE, CONNECT THE FIXTURE TO THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL LIGHTING IN THE AREA AND PROVIDE AN UNSWITCHED
PHASE WIRE IN ADDITION TO THE SWITCHED WIRE. THE BR ANCH CIRCUIT SHALL BE CLEARLY IDENTIFIED AT THE DISTRIBUTION PANEL.
B. FOR EXIT SIGNS, PROVIDE AN UNSWITCHED PHASE WIRE OF THE SAME BRANCH CIRCUIT AS THAT SERVING THE EMERGE NCY LIGHTING IN THE ARE A.
6. MANUAL SWITCHES
A. PROVIDE SWITCHES AS NOTED ON PLANS. SWITCH FUNCTION IS GENERALLY INDICATED BY A SUBSCRIPT WHICH MATCHES ITS ASSOCIATED LUMINA IRES IN A GIVEN AREA.
B. REFER TO AREA DESCRIPTIONS IN THIS NARRATIVE FOR DE TAILS REGARDING EACH SWITCHES TYPE AND FUNCTIONALIT Y.
7. OCCUPANCY SENSORS
A. ALL OCCUPANCY SENSORS SHALL BE DUAL TECHNOLOGY, REFER TO SPECIFICATIONS.
B. IN CORRIDORS, STAIRWAYS, RESTROOMS, ENTRANCE AREAS AND LOBBIES, AND OTHER AREAS NOTED ON PLANS, OCCUPA NCY SENSORS SHALL PROVI DE AUTOMATIC FULL -ON FUNCTIONALITY.
C. PROVIDE EXTENDED RANGE OCCUPANCY SENSORS WHERE NECESSARY, COORDINATE WITH CEILING HEIGHTS.
D. ALL OTHER OCCUPANCY SENSORS SHALL FUNCTION IN VACANCY MODE AND SHALL BE MANUAL -ON AND VACANCY OFF.
E. OCCUPANCY SENSORS SHALL SWITCH OFF LIGHTING WITHIN 30 MINUTES OF VACANCY. TIME -OUT PERIODS FOR SPECIFIC AREAS ARE TO BE SET AS FOL LOWS:
a. OFFICES: 20 MIN
b. RESTROOMS: 20 MIN
c. CORRIDORS: 10 MIN
d. STORAGE: 5 MIN
F. OCCUPANCY SENSORS SHALL HAVE AN ASSOCIATED MANUAL OVERRIDE SWITCH AS NOTED ON PLANS.
8. DAYLIGHT SENSORS/PHOTOCELLS
A. SENSOR LOCATIONS ARE SHOWN ON THE PLANS. EXACT LOCA TION TO BE FIELD COORDINATED BUT MUST REMAIN INSIDE THE ASSOCIATED DAYLIGH T ZONE.
B. DAYLIGHT ZONE OUTLINES ARE SHOWN ON THE PLANS. LUMI NAIRES INSIDE DAYLIGHT ZONES ARE TO BE CONTROLLED B Y SWITCHING OR DIMMING ACCORDING TO THIS NARRATIVE.
C. DAYLIGHT SENSORS SHALL BE CONFIGURED TO CONTINUOUSL Y DIM THE ASSOCIATED FIXTURES IN RESPONSE TO AVAILA BLE DAYLIGHT WHILE MAIN TAINING UNIFORM ILLUMINATION, AND COMPLETELY SHUT O FF THE CONTROLLED FIXTURES
WHEN AVAILABLE DAYLIGHT IS AT A MAXIMUM. SENSOR SHA LL INCLUDE A TIME -DELAY FEATURE THAT PREVENTS CYCLING OF LIGHT LEVEL CHANGES OF LESS THAN THREE MINUTES.
D. DAYLIGHT SENSORS SHALL HAVE MULTI -ZONING CAPABILITY TO CONTROL PRIMARY AND SECONDARY DAYLIGHT ZONES SEPARATELY PER WSEC.
9. TIME SCHEDULE CONTROLS
A. LUMINAIRES CONTROLLED BY A TIME SCHEDULE ARE DESCRIBED IN THIS NARRATIVE.
B. THE TIME SCHEDULE CONTROL SHALL HAVE THE FOLLOWING CAPABILITIES:
a. MINIMUM 7 DAY CLOCK WITH OPTION OF BEING SET FOR 7 DIFFERENT DAYS PER WEEK
b. HOLIDAY SHUTOFF FEATURE, TURN OF ALL LOADS FOR 24 H OURS THEN RESUME NORMAL OPERATION
c. PROGRAM BACKUP CAPABILITY TO WITHSTAND AT LEAST 10 HOURS OF POWER LOSS
d. MANUAL OVERRIDE CONTROL WHICH PERMITS LIGHTING TO R EMAIN ON NOT LONGER THAN 2 HOURS
LIGHTING CONTROLS NARRATIVE
EXTERIOR PARKING AREAS X INTEGRAL X X
GARAGE X X X X X X SEE NOTE 1
LOBBY BOH SWEEP X X X
OTHER SPACES < 300 SF X X X X
STORAGE/MAINT X X X
SINGLE-OCC. RESTROOMS X X X X
OFFICE X X X X
STAFF AREA X X X X X
MEETING ROOM X X X X X
SPACE TYPE LOCAL
SWITCH
DIMMER OR
SCENE
FULL
ON PARTIAL ON MANUAL
ON
FULL
OFF
PARTIAL
OFF
DAYLIGHT
CONTROLS
PLUG LOAD
CONTROL
TIME
CLOCK
OCC.
SENSOR
OCC. SENSOR SETTINGS
MANUAL CONTROLS AUTOMATIC ON/OFF CONTROLS OTHER CONTROLS
LIGHTING CONTROLS MATRIX
VARIES
VARIES
revision / issue no. date
03/09/2026
ELECTRIC UTILITY COORDINATION NOTES:
A. PER SCOPE MATRIX, CONTRACTOR TO PROVIDE EXCAVATION FOR
TRENCHING. REFER TO CIVIL PLANS FOR LOCATIONS.
B. ELECTRIC UTILITY POINT OF CONTACT:
TESSA NELSON
DAHLBERG LIGHT & POWER COMPANY
Tessa@dahlberglightandpower.com
SCOPE ITEM EC / GC UTILITY
SERVICE EQUIPMENT AND PRIMARY
TRENCHING / EXCAVATION X
PRIMARY CONDUITS X
PRIMARY CONDUCTORS X
SERVICE XFMR INSTALL X
SECONDARY TRENCHING / EXCAVATION X
SECONDARY CONDUITS X
SECONDARY CONDUCTOR X
XFMR UTILITY PRIMARY SECONDARY
PRIMARY VAULT(S) INSTALL X
COMMUNICATION UTILITY COORDINATION NOTES:
NORVADO
715 -798 -3303
SCOPE ITEM EC / GC UTILITY
PRIMARY RACEWAY DIRECT BURIAL BY UTILITY
X
FROM EXTERIOR INTO I.T.
CLOSET
SECONDARY
RACEWAY
CONDUCTORS
GENERAL SITE PLAN NOTES:
A. PRIMARY WORK SHOWN FOR REFERENCE ONLY. REFER TO
ELECTRICAL UTILITY DESIGN FOR MORE DETAIL AND DIVIS ION OF
RESPONSIBILITY.
B. COORDINATE COMMUNICATIONS INFRASTRUCTURE WITH
COMMUNICATIONS PROVIDERS.
C. ROUTE LOW VOLTAGE CONDUITS ALONG WITH POWER CONDUIT S
WHERE POSSIBLE. ENSURE MAXIMUM POSSIBLE SEPARATION
BETWEEN POWER AND LOW VOLTAGE CONDUITS (12 ” MINIMUM).
PROVIDE HANDHOLES, PEDESTALS, CONDUITS, AND INSTALLATION
ACCESSORIES OF ALL LOCAL ISP SERVICES DESIRED BY OWNER.
ASSUME (4) 1" CONDUITS ROUTED TO BUILDING.
D. ALL 20A CIRCUITS ON SITE TO BE #10 CU MINIMUM UNLES S NOTED
OTHERWISE.
E. ALL UNDERGROUND CONDUITS TO BE 1 ” MINIMUM UNLESS NOTED
OTHERWISE.
old hwy 2
hill dr
dump rd
garage
admin
laydown area
future parking lot
expansion area
gated road 70 KW GENERATOR
UTILITY XFRM
UTILITY METER/CT CABINET
RETENTION POND
TO UTILITY POLE
UNDERGROUND ELECTRICAL
SERVICE
drawn by:
checked by:
date:
project #:
sheet title:
sheet
number:
www.dsgw.com
03/10/2026
25323
JRB
LM
Brule Public
Works
Garage
E1.0
SITE PLAN
SCALE: 1" = 50'-0" 1 SITE PLAN - ELECTRICAL
revision / issue no. date
03/09/2026
G
G
G G
G W
W
W
W
FB1
FB1
FB1
FB2
G G G
G G G
G G
G G
G
G
G
G G G
G
J
GENERAL POWER NOTES:
A. DRAWINGS ARE DIAGRAMMATIC TO CONVEY DESIGN INTENT A ND
SHALL NOT BE USED FOR EXACT DIMENSIONS, UNLESS
DIMENSIONS ARE PROVIDED.
B. MECHANICAL AND PLUMBING EQUIPMENT IS PROVIDED BY OT HER
DIVISIONS, AND IS SHOWN IN PLANS FOR DIVISION 26 RE FERENCE.
REFER TO MECHANICAL AND PLUMBING EQUIPMENT CONNECT ION
SCHEDULE FOR CONNECTION CHARACTERISTICS, INSTALLATION
NOTES, AND DETAILS.
C. ROUTE ALL NEW WIRING CONDUITS CONCEALED INSIDE WALLS OR
ABOVE CEILINGS. ALL CONDUIT ROUTING SHALL FOLLOW BU ILDING
LINES WHERE POSSIBLE AND BE FULLY CONCEALED, EXCLUDING
THE PARKING GARAGE AND BACK -OF -HOUSE SPACES.
COORDINATE ALL EXPOSED CONDUIT ROUTING WITH ARCHITE CT
PRIOR TO INSTALL.
D. PROVIDE 1" CONDUIT ROUTED TO ACCESSIBLE CEILING SPA CE FOR
ALL DATA OUTLETS SHOWN IN PLANS. MAINTAIN AT LEAST 12 ”
SEPARATION BETWEEN POWER AND COMMUNICATIONS WIRING
ROUTED PARALLEL. SMALLER SEPARATION MAY BE ALLOWED
WHEN CROSSING.
E. GARAGE SPACE IS A HAZARDOUS CLASSIFIED AREA FROM FL OOR
TO A MINIMUM OF 18" A.F.F.
1
2
3
4
5
7
8
A B
meeting room
105
garage
100
staff tlt
103
staff area
104
(2)
AV 1
2
22.
BE-1
5,7.
BE-2
14.
16.
25.
5,7.
BE -2
BE -1
BE -1
BE -1
24.
BE -1
(TYP.)
3
W
2MDP
2N -A
21.
21.
21.
19.
19.
13.
13.
13.
13.
13.
5.
15. 17. 17.
31.
31.
31.
43. 43.
28.
31.
5. 5. 1.
17.
23.
1.
1.
11.
11.
3.
3.
9.
9.
32.
32.
32.
32.
2.
4.
6.
8.
15.
15.
9.
9.
11.
11.
13.
13.
2.
GWH-101
6
GUH-2
P-4
P-3
P-2
P-1
GUH-1
ERV-01
ERV-02
FC-2
FC-1
CEF-02 CEF-01
3.
W
CU-1 CU-2
UC REFER.
MICRO
17.
REFER.
EUH-02
EUH-03
EUH-01
UTILITY METER/CT CABINET
ATS
DISC SWITCH
3.
mech/elec
101
Toilet Rm
106
Utility
107
Toilet Rm
108
Hallway
109
Office
110
Storage
112
storage
102
12.
10.
19.
23.
21.
33.
35.
37.
39.
41.
27.
29.
30.
AC-101
51,53.
10,12. 6,8.
2,4.
13. 13.
5.
1.
25,27.
34,36.
14,16.
B-1
EUH-04
7.
DRINKING FOUNTAIN.
9
45,47.
6.
8.
4.
38,40.
VEF-2
VEF-1
EDH-1
EDH-2
29,31.
49.
4
RCP-101
26.
2.
BE -2
WP-1
18,20.
5
GENERATOR REMOTE
ANNUNCIATOR PANEL
55.
LV-2
61.
BP-1
63.
4
EF-01
EF-02
6
drawn by:
checked by:
date:
project #:
sheet title:
sheet
number:
www.dsgw.com
03/10/2026
25323
JRB
LM
Brule Public
Works
Garage
E2.1
FLOOR PLAN
CIRCUITING NOTES:
A. POWER - GARAGE CIRCUITS TO BE FED FROM PANEL 2MDP AND
OFFICE CIRCUITS FROM PANEL 2N -A, UNLESS NOTED OTHERWISE.
B. MECHANICAL, PLUMBING, AND BUILDING EQUIPMENT - UNLESS
INDICATED IN PLAN, REFER TO EQUIPMENT SCHEDULES FOR
CIRCUITING AND CONNECTION DETAILS.
SCALE: 1/8" = 1'-0" 1 FLOOR PLAN - POWER
KEYNOTES:
1 PROVIDE POWER AND DATA TO WALL MOUNTED TELEVISION.
MOUNT AT +60" AFF, COORDINATE EXACT LOCATION PRIOR TO
ROUGH-IN.
2 PROVIDE (1) 3/4"C FOR POWER, (1) 1"C FOR DATA AND (1) 1-1/4"C
FOR AUDIO/VISUAL PROVISIONS.
3 ALL RECEPTACLES IN GARAGE TO BE MOUNTED AT +48" AF F,UNO.
4 PROVIDE 1" CONDUIT FROM THIS LOCATION UNDERSLAB AN D STUB
UP AT IT CLOSET LOCATION FOR FIBER SERVICE. EXTEND 4' ABOVE
GRADE OUTSIDE.
5 ROUTE SERVICE UNDERSLAB TO DISCONNECT SWITCH IN
MECH/ELEC ROOM.
6 PROVIDE 240V, 30A BRANCH CIRCUIT TO JUNCTION BOX W ITH
BLANK COVER FOR FUTURE DISPLAY BOARD. MOUNT JUNCTION
BOX AT 11'-0" AFF. COORDINATE EXACT LOCATION WITH
ARCHITECT/OWNER PRIOR TO ROUGH-IN.
CIRCUITED TO
PANEL 2MDP
CIRCUITED TO
PANEL 2N -A
revision / issue no. date
03/09/2026
$3
$
$$
$
$D
$ $ D $D
$D $
$3
$D$
GENERAL LIGHTING NOTES:
A. DRAWINGS ARE DIAGRAMMATIC TO CONVEY DESIGN INTENT A ND
SHALL NOT BE USED FOR EXACT DIMENSIONS, UNLESS
DIMENSIONS ARE PROVIDED.
B. REFER TO INTERIORS AND ARCHITECTURAL DESIGN PLANS F OR
EXACT DIMENSIONS AND INSTALLATION DETAILS OF ALL
LUMINAIRES AND DEVICES IN FRONT -OF -HOUSE SPACES.
C. REFER TO LIGHTING CONTROL SEQUENCE OF OPERATIONS MA TRIX
AND LIGHTING CONTROLS NARRATIVE FOR SPACE -BY -SPACE
CONTROL REQUIREMENTS.
1
2
3
4
5
7
8
A B
25.
SW2
25.
SW1
25.
SW1
25.
SW1
25.
SW1
25.
SW1
meeting room
105
garage
100
staff area
104 staff tlt
103
27.
R1E
27.
R1
27.
R1
27.
R1
27.
R1
27.
R1 27.
R1E
27.
R1
27.
R1
27.
R1
27.
R1
6
storage
102
25.
X1
27.
X1
27.
R1
27.
R1
27.
R1
27.
R1E
27.
R1
27.
R1
27.
R1
27.
R1
27.
R1
27.
R1
27.
R1
27.
R1
27.
R1
27.
R1
27.
R1E
27.
R1
27.
R1
27.
R1
27.
R1
27.
R1
27.
R1
23.
S1
23.
S1
23.
S1
23.
S1
23.
S1E
23.
S1
23.
S1
23.
S1
23.
S1
23.
S1
23.
S1E
23.
S1
27.
L1
27.
X1
27.
R2
27.
R1E
27.
R1
mech/elec
101
Toilet Rm
106
Utility
107 Toilet Rm
108
Hallway
109
Office
110
Storage
112
27.
L1E
27.
L1
27.
R1
27.
R1
27.
R1
ba
aaa
a a a
aaa
aaab
b
b
b
27.
X1
27.
X1
9
25.
SW2
25.
SW2
25.
SW2
drawn by:
checked by:
date:
project #:
sheet title:
sheet
number:
www.dsgw.com
03/10/2026
25323
JRB
LM
Brule Public
Works
Garage
E3.1
LIGHTING RCP
CIRCUITING NOTES:
SHADED REGIONS WITHIN LUMINAIRES INDICATE EMERGENCY POWER.
A. NORMAL POWER - PROVIDE BRANCH CIRCUITS SHOWN IN PLAN
FROM PANEL 2N -A, UNLESS NOTED OTHERWISE.
B. EXIT SIGNAGE - PROVIDE UNSWITCHED POWER FROM NEAREST
NORMAL POWER GENERAL RECEPTACLE BRANCH CIRCUIT.
SCALE: 1/8" = 1'-0" 1 LEVEL 1 PLAN - LIGHTING
revision / issue no. date
03/09/2026
BUILDING STEEL
NEC 250.52(A)(2)
CONCRETE ENCASED
ELECTRODE - 20' MIN.
NEC 250.52(A)(3)
METAL UNDERGROUND
WATER PIPING
NEC 250.52(A)(1)
#4 CU
(2) DRIVEN GROUND RODS,
MIN 8 -FT SEPARATION
NEC 250.52(A)(5)
#4 CU #6 CU
#4 CU
MAIN SERVICE DISCONNECT
NEUTRAL BUS
GROUND BUS
#4 CU
MAIN BONDING
JUMPER PER
NEC 250.28
GROUNDING LEGEND
GEC - GROUNDING ELECTRODE CONDUCTOR
EGC - EQUIPMENT GROUNDING CONDUCTOR
MBJ - MAIN BONDING JUMPER
SSBJ - SUPPLY SIDE BONDING JUMPER
NTRL - NEUTRAL (THE GROUNDED CONDUCTOR)
PANEL NAME
480Y/277V, 3PH, 4W DISTRIBUTION SYSTEM
1000A/MLO/FEED-THRU
FED FROM MDP
BUS RATING & PANEL
INFO PER ONE -LINE
PANEL SUPPLIED FROM
1/2" TEXT SIZE
1/4" TEXT SIZE,
TYP.
PANEL NAME
RECESSED FLOOR BOX, LOCATE
PER PLAN
RECESSED WALL BOX
ROUGH-IN CONDUITS
POWER CONDUIT
TO BRANCH PANEL
ACCESSIBLE CLG. SPACE
CEILING
FINISHED FLOOR
DATA CONDUIT
POWER, DATA, AND AV CONDUITS
SEE SCHEDULE FOR SIZING
drawn by:
checked by:
date:
project #:
sheet title:
sheet
number:
www.dsgw.com
03/10/2026
25323
JRB
LM
Brule Public
Works
Garage
E5.1
DETAILS
NOT TO SCALE 1 BUILDING GROUNDING DIAGRAM (SMALL)
NOT TO SCALE 3 CONFERENCE ROOM ROUGH IN DETAIL - TV
NOT TO SCALE 4 EQUIPMENT IDENTIFICATION NAMEPLATE DETAIL
revision / issue no. date
03/09/2026
PANEL
1PH, 3W
2MDP
240/120V
M
T 400A
2P
F
PANEL
1PH, 3W
2N-A
240/120V
PRIMARY CONDUITS
PER UTILITY
UTILITY
TRANSFORMER
GENERATOR : NATURAL GAS,
70KW, 240/120V, 1PH, 3W
UTILITY METER/CT
CABINET
240/120V, 1PH, 400A
DISCONNECT
SWITCH
400A,2P
400AF, CLASS R
ATS
400A
4003
4003
4003
4003
4003
2003
23.6 kA
19.2 kA
19.2 kA
19.2 kA
13.9 kA
400A 200A
drawn by:
checked by:
date:
project #:
sheet title:
sheet
number:
www.dsgw.com
03/10/2026
25323
JRB
LM
Brule Public
Works
Garage
E6.1
ONE -LINE
DIAGRAM
SCALE: NOT TO SCALE 1 ONE-LINE DIAGRAM - ELECTRICAL
4000 # 12 600 KCM AL 500 KCM CU 4"
3000 # 10 500 KCM AL 400 KCM CU 4"
2500 # 10 350 KCM AL 350 KCM CU 4"
2000 # 8 350 KCM AL 250 KCM CU 4"
1600 # 6 400 KCM AL #4/0 CU 4"
1200 # 4 500 KCM AL #3/0 CU 4"
1000 # 4 350 KCM AL #2/0 CU 3"
800 # 3 400 KCM AL #1/0 CU 3"
600 # 2 500 KCM AL #1 CU 4"
500 # 2 350 KCM AL #2 CU 3"
450 # 2 300 KCM AL #2 CU 3"
400 # 2 250 KCM AL #3 CU 3"
350 # 2 #4/0 AL #3 CU 3"
300 # 1 500 KCM AL #4 CU 4"
250 # 1 350 KCM AL #4 CU 3"
225 # 1 300 KCM AL #4 CU 3"
200 # 1 250 KCM AL #6 CU 3"
175 # 1 #4/0 AL #6 CU 3"
150 # 1 #3/0 AL #6 CU 2"
125 # 1 #2/0 AL #6 CU 2"
110 # 1 #1/0 AL #6 CU 2"
100 # 1 #1 CU #8 CU 1-1/2"
90 # 1 #2 CU #8 CU 1-1/2"
80 # 1 #3 CU #8 CU 1-1/4"
70 # 1 #4 CU #8 CU 1-1/4"
60 # 1 #4 CU #10 CU 1-1/4"
50 # 1 #6 CU #10 CU 1"
40 # 1 #8 CU #10 CU 3/4"
30 # 1 #10 CU #10 CU 3/4"
20 # 1 #12 CU #12 CU 3/4"
AMPS WIRE
SYS CONDUCTORS MAT. CONDUCTOR MAT.
FEEDER TAG
# OF
SETS
PHASE AND NEUTRAL
CONDUCTORS GROUND
RACEWAY
FEEDER SCHEDULE (CU & AL)
FEEDER SCHEDULE NOTES: EXAMPLE TAG: 12004 = 1200A, 3PH-4W SYSTEM
A. PROVIDE GROUND CONDUCTOR WITH ALL FEEDERS EXCEPT SERVICE ENTRANCE FEEDERS.
B. WIRE SYS INDICATES THE FEEDER WIRING SYSTEM: 2=2 WIRE, 3=3 WIRE, 4=4 WIRE.
C. FEEDER TAGS ENDING WITH X REFER TO TRANSFORMER SCHEDULE FOR GEC AND BONDING.
D. ALL RACEWAYS ARE SIZED FOR SYSTEMS FOR FUTURE CAPACITY.
R = RECEPTACLE 17800 VA 78.09% 13900 VA
M = MOTOR 6000 VA 100.00% 6000 VA TOTAL DEMAND AMPS: 314 A
LM = LARGEST MOTOR 0 VA 0.00% 0 VA TOTAL DEMAND LOAD: 753 93 VA
L = LIGHTING 0 VA 0.00% 0 VA TOTAL CONNECTED LOAD: 79293 VA
K = KITCHEN EQUIPMENT 0 VA 0.00% 0 VA
PROTECTED HM = HOTEL/MOTEL 0 VA 0.00% 0 VA
(GFP) = GROUND FAULT H = HVAC EQUIPMENT 26177 VA 100.00 % 26177 VA
(S) = SHUNT TRIP G = GENERAL NON-CONTINUOUS LOAD 22074 VA 100.00% 22074 VA
(N) = SWITCHED NEUTRAL E = ELECTRIC HEAT 7242 VA 100.00 % 7242 VA
(L) = LOCKABLE D = DWELLING UNIT 0 VA 0.00% 0 VA
(G) = GFCI C = CONTINUOUS GENERAL LOAD 0 VA 0.00% 0 VA
(A/G) = AFCI/GFCI FEV = FUTURE EV CHARGING LOAD 0 VA 0. 00% 0 VA
(A) = AFCI EV = EV CHARGING LOAD 0 VA 0.00% 0 VA
BREAKER KEY LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
341 A 320 A
40937 VA 38356 VA
71 -- 72
69 -- -- SPD 2 -- 70
67 68
65 66
63 20 A 1 EQ: BP-1 H 156 64
61 20 A 1 EQ: LV-2 E 240 62
59 1000 60
57 30 A 2 GEN. BLOCK HEATER, BATT CHARGER G 1000 58
55 20 A 1 GENERATOR REMOTE ANNUNCIATOR PANEL G 1000 56
53 2880 54
51 20 A 2 EQ: AC-101 H 2880 52
49 20 A 1 EQ: EDH-1 E 500 50
47 0 48
45 50 A 2 EQ: WEST WELDING RECP - (BE-2) G 0 46
43 15 A 1 R: STAFF AREA R 360 44
41 15 A 1 EQ: P-4 H 156 42
39 15 A 1 EQ: P-3 H 156 500 40
37 15 A 1 EQ: P-2 H 156 500 H EQ: EUH-02 2 20 A 38
35 15 A 1 EQ: P-1 H 156 500 36
33 20 A 1 EQ: VEF-1 (SOUTH) H 1536 500 E EQ: EUH-01 2 20 A 34
31 15 A 1 R: STAFF AREA R 720 720 R R: STORAGE, MECH/ELEC, GARAGE WEST 1 15 A 32
29 20 A 1 EQ: B-1 H 1440 600 H EQ: GWH-02 1 15 A 30
27 15 A 1 EQ: ERV-01 H 204 1440 R R: MICROWAVE - STAFF AREA 1 20 A 28
25 20 A 1 M: OH DOOR 4 - (BE-1) M 1200 120 H EQ: RCP-101 1 20 A 26
23 15 A 1 EQ: GUH-1 H 552 1200 M M: OH DOOR 5 - (BE-1) 1 20 A 24
21 15 A 1 EQ: GUH-2 H 552 1200 M M: OH DOOR 1 - (BE-1) 1 20 A 22
19 20 A 1 EQ: VEF-1 (NORTH) H 1536 2400 20
17 20 A 1 R: UC REFRIGERATOR - STAFF AREA R 1440 2400 H EQ: WP-1 2 20 A 18
15 15 A 1 R: GARAGE WEST R 720 1200 M M: OH DOOR 3 - (BE-1) 1 20 A 16
13 20 A 1 R: GARAGE EAST R 720 1200 M M: OH DOOR 2 - (BE-1) 1 20 A 14
11 20 A 1 R: GARAGE EAST R 720 336 H EQ: EF-02 1 15 A 12
9 15 A 1 R: GARAGE NORTH R 540 1176 H EQ: EF-01 1 20 A 10
7 8938 720 R R: GARAGE WEST 1 15 A 8
5 50 A 2 EQ: EAST WELDING RECPS - (BE-2) G 8938 720 R R: GARAGE WEST 1 15 A 6
3 9522 720 R R: GARAGE WEST 1 15 A 4
1 200 A 2 PANEL 2N-A R; G;... 10142 1080 R R: GARAGE WEST/SOUTH 1 15 A 2
CKT TRIP POLE DESCRIPTION TYPE A B TYPE DESCRIPTION POLE TRIP CKT
MAINS: 400 A MCB FEED-THRU LUGS: NO 2MDP
BUS RATING: 400 A INTEGRAL SPD: NO MOUNTING: SURFACE SUPPLY FROM:
EQUIPMENT NAME: VOLTAGE: 240/120V, 1PH, 3W AIC RATING: SEE ONE-LINE NEMA RATING: NEMA-1 LOCATION: mech/elec 101
R = RECEPTACLE 7180 VA 100.00% 7180 VA
M = MOTOR 0 VA 0.00% 0 VA TOTAL DEMAND AMPS: 82 A
LM = LARGEST MOTOR 0 VA 0.00% 0 VA TOTAL DEMAND LOAD: 196 64 VA
L = LIGHTING 0 VA 0.00% 0 VA TOTAL CONNECTED LOAD: 19664 VA
K = KITCHEN EQUIPMENT 0 VA 0.00% 0 VA
PROTECTED HM = HOTEL/MOTEL 0 VA 0.00% 0 VA
(GFP) = GROUND FAULT H = HVAC EQUIPMENT 5784 VA 100.00% 5784 VA
(S) = SHUNT TRIP G = GENERAL NON-CONTINUOUS LOAD 1200 VA 100.00% 1200 VA
(N) = SWITCHED NEUTRAL E = ELECTRIC HEAT 5501 VA 100.00 % 5501 VA
(L) = LOCKABLE D = DWELLING UNIT 0 VA 0.00% 0 VA
(G) = GFCI C = CONTINUOUS GENERAL LOAD 0 VA 0.00% 0 VA
(A/G) = AFCI/GFCI FEV = FUTURE EV CHARGING LOAD 0 VA 0. 00% 0 VA
(A) = AFCI EV = EV CHARGING LOAD 0 VA 0.00% 0 VA
BREAKER KEY LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
85 A 79 A
10142 VA 9522 VA
41 42
39 40
37 38
35 600 36
33 30 A 2 G: BUILDING DISPLAY BOARD G 600 34
31 2000 32
29 30 A 2 EQ: EDH-2 E 2000 30
27 250 28
25 20 A 2 EQ: EUH-02 E 250 26
23 20 A 1 R: IT RACK R 0 24
21 15 A 1 R: OFFICE/STORAGE R 540 22
19 15 A 1 R: SECURE STORAGE, 123 OFFICE R 720 20
17 15 A 1 R: LOBBY R 540 18
15 20 A 1 R REFRIGERATOR - LOBBY R 1440 500 16
13 20 A 1 R: TOILET, 126 TOILET, 153 VEST. R; H 1140 500 E EQ: EUH-01 2 20 A 14
11 15 A 1 R: MEETING ROOM FLOOR BOX R 360 864 12
9 15 A 1 R: MEETING ROOM FLOOR BOX R 360 864 H EQ: CU-2 2 20 A 10
7 20 A 1 R: DRINKIN FOUNTAIN (G) R 160 1632 8
5 15 A 1 R: MEETING ROOM R 720 1632 H EQ: CU-1 2 20 A 6
3 15 A 1 R: MEETING ROOM R 720 276 4
1 15 A 1 R: MEETING ROOM R 720 276 H EQ: ERV-02 2 20 A 2
CKT TRIP POLE DESCRIPTION TYPE A B TYPE DESCRIPTION POLE TRIP CKT
MAINS: MLO FEED-THRU LUGS: NO 2N-A
BUS RATING: 200 A INTEGRAL SPD: NO MOUNTING: SURFACE SUPPLY FROM: 2MDP
EQUIPMENT NAME: VOLTAGE: 240/120V, 1PH, 3W AIC RATING: SEE ONE-LINE NEMA RATING: NEMA-1 LOCATION: Utility 107
NO/EXTERNAL
revision / issue no. date
03/09/2026
Source: Town of Brule website. First collected Oct 11, 2026.